5.2
ELECTRICAL INSTALLATION, cont.
5.2.4 Multi-Cabinet Connections
Multi-cabinet systems should have each cabinet’s output connections paralleled at the switchgear
panel. The converters’ terminal blocks are sized for a single, appropriated sized cable per phase,
neutral, and grounding conductor.
Multi-cabinet systems are constructed from one cabinet which serves as the system Master, and an
additional cabinet(s) which serves as the Slave(s). A paralleling cable assembly (
P/N 605150
) is
shipped pre-connected to the Slave cabinet and coiled at the base of the cabinet near the Input and
Output connection terminal blocks. It must be connected to the interface connector at the base of
the Master cabinet (see Figure 4 on page 19 for details). Do not substitute cable assemblies. If a
longer cable is needed for a given installation, contact the factory for the appropriate cable.