Ascon Tecnologic - K31D - OPERATING INSTRUCTIONS - PAG. 12

sequentially, one of the 2 pre-programmed Set Points;

oFF

  Pressing the key for at least 1 s, is possible to swap 

between automatic control (

rEG

) to OFF control (

oFF

and vice-versa.

5.14  Digital Input

The instrument can be equipped with 2 digital inputs that are 
managed by 1 parameter .
The function of the digital input can be set through param-
eter 

diF

 contained in the group 

]

InP

.

The parameter can 

diF

 be programmed as:

noF

  No function;

Aac

  Closing the contact connected to digital input 1 is pos-

sible to acknowledge the alarm (paragraph 5.11);

ASi

  Closing the contact connected to digital input 1 is pos-

sible to acknowledge an active alarm (paragraph 5.11);

HoLd

  Closing the contact connected to digital input 1 the 

istrument holds the measure in that instant (

m

 not 

the reading on the display, therefore the indication 
could settle with a delay proportional to the measure 
filter).  With the hold function activated, the instrument 
operates the control according to the stored measure.  
Opening the contact, the instrument returns to the 
normal acquisition of the measure;

oFF

  When the instrument is in 

rEG

 state, closing the 

contact connected to digital input 1, the instrument is 
placed in 

oFF

 status.  Opening the contact, the instru-

ment returns to the 

rEG

 automatic control status;

CHSP

  Closing the contact connected to digital input 1 is pos-

sible to select, sequentially, one of the 2 pre-pro-
grammed Set Points;

SP1.2

  Closing the contact connected to digital input 1 is pos-

sible to select as active the 

SP2

 Set Point.  Opening 

the contact the 

SP1

 Set Point is selected as active.  

SP1.2

 can be selected only when 

nSP

 = 

2

 and, when 

active, it disables the selection of the active Set Point 
through the parameter 

SPAt

 and through the 

 key;

HE.Co

  Closing the contact connected to digital input 1 is 

possible to select as active the Set Point SP2 in 

CooL

 

mode.  Opening the contact the 

SP1

 Set Point is se-

lected as active in 

HEAt

 mode.  

HE.Co 

can be selected 

only when 

nSP

 = 

2

 and, when active, it disables the 

selection of the active Set Point through the parameter 

SPAt

 and through the 

 key.

5.15  RS485 Serial Interface

The instrument can be equipped with a 

RS485

 serial com-

munications interface, by means of which it is possible to 
connect the controller to a network to which other instru-
ments (PLC controllers) are connected.  All these devices 
typically depend on a Personal Computer that acts as a 
plant supervisor.  Using a Personal Computer is possible to 
acquire all the function information and to program all the 
instrument configuration parameters.  The software protocol 
adopted for 

K31D

 is a 

MODBUS RTU

 type, widely used in 

several PLC and supervision programs available on the mar-
ket (the manual of the comminications protocol of the 

K31D

 

series is available on request).
The interface circuit allows the connection of up to 

32

 instru-

ments on the same line.
To maintain the line in rest conditions a 120

W

 resistance (

Rt

must be connected to the end of the line.
The instrument has two terminals called 

A

 and 

B

 that must 

be connected to all network terminals with the same label.
For wiring the line, then a twisted pair of telephone type is 
sufficient.
However, especially when the network is very long or dis-
turbed, it is advisable to adopt a 3-pole wired and shielded 
cable connected as shown.
If the instrument is equipped with a serial interface, the pa-
rameters to be programmed are the following, all present in 
the parameters group 

]

SEr

:

Add

  Address of the station. Set a different number for each 

station.  Values: 1 ÷ 255.

baud

  Transmission speed (baud-rate).  Values:1200 ÷ 38400 

baud.  All the stations on the line must have the same 
transmission speed.

PACS

  Programming access.  If programmed as 

LoCL

 it 

means that the instrument is only programmable from 
the keyboard, if programmed as 

LorE

 it is programma-

ble both from the keyboard and serial line.
If an attempt is made to enter the programming from the 
keyboard whilst a communication through the serial port 
is in progress the instrument shows the message 

buSy

 

to indicate the busy state.

A
B

GND

Host

(OP/PC/PLC)

RS485

Interface

Shield

10

Rt

120

9 8

A

GND

B

K31D no. 1

10 9 8

A

GND

B

K31D no. 2

10 9 8

A

GND

B

K31D no. 31

Содержание K31D

Страница 1: ...an therefore be used in applications that require a control for the temperature difference between 2 different environments such as liquid coolers chillers natural air conditioning systems through the air recirculation heating by solar panels or in many other applications where 2 temperature readings are needed The controller is also Index 1 Instrument description 1 1 1 General description 1 1 2 F...

Страница 2: ...that the process value is lower than the one programmed for parameter AdE 12 LED Shift index Indicates that the process value is within the range SP AdE SP AdE 13 LED Shift index Indicates that the process value is higher than the one set for parameter AdE 2 PROGRAMMING 2 1 Set Point Fast Programming This procedure allows you to quickly set the active Set Point and when required the alarm threshol...

Страница 3: ...r or disappear on this level by fol lowing this procedure Enter the menu ConF and select the parameter to be made programmable or not programmable in the menu oPEr Once the parameter has been selected if the LED SET is OFF this means that the parameter is programmable only in the menu ConF if instead the SET LED is ON this means that the parameter is also programmable in the menu oPEr To modify th...

Страница 4: ...entioned rule must adopt all the necessary protective measures The instrument MUST NOT be used in dangerous environments flammable or explosive without adequate protection The installer must ensure that EMC rules are respected also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for fl...

Страница 5: ...probe is not connected The instrument allows the measurement calibration that can be used to recalibrate the instrument according to application needs This can be done through parameters OFS1 OFS2 and rot Setting rot 1000 and oFS 1 2 it is possible to set a posi tive or negative offset that is simply added to the value read by the probe before visualisation which remains constant for all the measu...

Страница 6: ...2HL the process value considered by the controller is Pr1 P2LL When P2HL and P2LL thresholds are exceeded by Pr2 tem perature a control takes place as if the Pr2 temperature is the value of the limit regardless of the value actually read The aim of this function is to limit the differential regulation to within a maximum range of the Pr2 measurement With the differential control the working mode F...

Страница 7: ...gle Action PID control can be obtained by program ming parameter Cont Pid and works on 1 rEG output depend ing on the active Set Point SP the functioning mode Func and on the instrument PID algorithm with 2 freedom degrees If the Out1 analogue output is present 0 4 20 mA 0 2 10 V the output will operate as a regulation output providing a value proportional to the regulation power calculated by the...

Страница 8: ...h Func CooL 4 If FAST Auto tuning is desired to start automati cally all times the Set Point is changed or at the end of the programmed Softstart cycle The Auto tuning starts anyway if PV is lower than SP SP 5 with Func HEAt or higher than SP SP 5 with Func CooL 1 If OSCILLATORY Auto tuning is desired to start auto matically all times the instrument is switched ON 2 If OSCILLATORY Auto tuning is d...

Страница 9: ...d when the relative parameters are set to InF If is desired only one ramp e g to reach SP1 it is enough to program the parameter SLor with the desired value The ramp SLor will always be active at Power ON and when the Active Set Point value is changed On the contrary if an automatic cycle is to be executed at Power ON program nSP 2 then the two Set Point values SP1 and SP2 and naturally parameters...

Страница 10: ...AL1 and is deactivated when thePV goes below the value AL1 HAL1 In this way is possible to program with AL1L and AL1H parameters the minimum and the maximum limits of AL1 thresholds LoAb OUT AL1 AL1 PV HAL1 time HiAb off off off OUT AL1 AL1 PV HAL1 time off off off ON ON ON ON LodE Deviation low alarm The alarm is activated when the process value goes below the value SP AL1 and is deactivated when...

Страница 11: ...f a measurement error yES Alarm active no Alarm deactivated 5 12 Loop Break Alarm Function All the parameters referring to the Loop Break alarm function are contained in the group LbA The Loop Break alarm is available on all the instruments which intervenes when for any reason short circuit of a thermocouple thermocouple inversion load interruption the loop control is interrupted First of all it i...

Страница 12: ...nSP 2 and when active it disables the selection of the active Set Point through the parameter SPAt and through the key 5 15 RS485 Serial Interface The instrument can be equipped with a RS485 serial com munications interface by means of which it is possible to connect the controller to a network to which other instru ments PLC controllers are connected All these devices typically depend on a Person...

Страница 13: ...nfiguration or to keep a copy of the parameters setting of an instrument and allow its rapid retransmission The same device allows to connect a PC via USB with which through the appropriate configuration software for AT Univer salConf tool the operating parameters can be configured To use the A01 device it is necessary that the device or instrument are being supplied AC supply Supply adapter 12 VD...

Страница 14: ...Number of decimal figures 0 1 0 12 Aot Analogue control Output type 0 20 0 20mA 4 20 4 20 mA 0 10 0 10 V 2 10 0 10 V 0 10 13 Unit Temperature unit of measurement C F C 14 FiL Input digital filter oFF Not active 0 1 20 0 s 1 0 15 oFS1 Measuring Offset Pr1 1999 9999 0 16 oFS2 Measuring Offset Pr2 1999 9999 0 17 rot Rotation of the measuruing straigìht line 0 000 2 000 1 000 18 InE oPE functioning in...

Страница 15: ... 1 33 AL1d AL1 Alarm activation delay oFF Not active 1 9999 s OFF 34 AL1i Alarm AL1 activation in case of probe error no yES no Group AL2 AL2 Alarm Parameters Parameter Description Range Default Note 35 OAL2 Output where alarm AL2 is addressed oFF Not active Out1 Out2 Out3 Out4 oFF 36 PrA2 AL2 Alarm PV reference Pr1 Pr2 P1 2 P1 L Pr1 37 AL2t AL2 Alarm type LoAb Absolute Low HiAb Absolute High LHAb...

Страница 16: ... error no yES no Group lba Loop Break Alarm Parameters Parameter Description Range Default Note 55 OLbA Output where LbA alarm is addressed oFF Not active Out1 Out2 Out3 Out4 OFF 56 LbAt Time necessary to activate alarm LbA oFF Not active 0 9999 s OFF Group reg Control Parameters Parameter Description Range Default Note 57 Cont Control type Pid PID on FA Asymmetrical ON OFF on FS Symmetrical ON OF...

Страница 17: ...SP Active Set Point selection oFF Control in OFF mode noF 78 diSP Displayed Variable Pr1 Pr1 Value Pr2 Pr2 Value P1 2 Pr1 Pr2 Value Pou Control Power SP F Active Set Point Value SP o Operative Set Point value AL1 AL1 threshold AL2 AL2 threshold AL3 AL3 threshold P1 2 79 AdE Shift value for the shift index functioning 0 OFF 1 9999 2 80 Edit Fast programming Active Set Points and Alarms SE Set Point...

Страница 18: ... contact our sales department to obtain authorisation for sending the instru ment to our company The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of different agreements 8 5 Disposal The appliance or the product must be disposed of separately in compliance with the local standa...

Страница 19: ...61010 1 10 HOW TO ORDER Model K31D Instrument with mechanical keys a Power supply H 100 240 VAC L 24 VAC DC F 12 VAC DC b Inputs 2 For PTC NTC Thermistors or Pt1000 resistance thermometer d Output 2 Out2 R Relay SPDT 8A resistive load O Vdc for SSR Not present e Output 3 Out3 R Relay SPST NO 5A resistive load O Vdc for SSR Not present f Output 4 Out4 R Relay SPST NO 5A resistive load O Vdc for SSR...

Страница 20: ...Ascon Tecnologic K31D OPERATING INSTRUCTIONS PAG 20 ...

Отзывы: