Ascon Tecnologic - K31D - OPERATING INSTRUCTIONS - PAG. 2

equipped with 

Fast

 and 

Oscillatory Auto-tuning

Self-tuning

 

and 

Fuzzy overshoot control

 for 

adjusting the PID

.  The 

instrument offers the possibility of having 

2 programmable 

digital inputs 

and 

an RS485 serial communications port

 

using MODBUS-RTU communications protocol with a 

trans-

mission speed

 up to 

38.4 kbaud

.

The

 process value

 is displayed on a 

4 digit red display

, while  

the outputs status is shown by 

4 LED

s.

The controller is equipped with a programmable 

3 LEDs shift 

display

 (

   

), stores 

2 Set Points

 and 

can have up to 

4 outputs

 [relay or solid state relays drive type (SSR)].  A 

model is also available with 

Out1 analogue control output

 

(0/4 ÷ 20 mA or 0/2 ÷ 10 V type).
Other important available functions are: 

Loop-Break Alarm

 

function, 

reaching of the Set Point at controlled speed

ramp

 and 

dwell function

Soft-Start

 function, 

protection 

compressor

 function for 

neutral zone

 control, 

parameters 

protection

 on different levels.

1.2  Front Panel Description

P

U

K31D

Tun

Out1 Out2

Out3 Out4

10

3

2

4

1

9

8

7

5
6

12

13

11

: This key is used to access the programming param-

eters and to confirm selection;

: This key is used to decrease the values to be set and 

to select the parameters.  If the key is held down, the user 
returns to the previous programming level until it exits the 
programming mode;

: This key is used to increase the values to be set and 

to select the parameters.  If the key is held down, the user 
returns to the previous programming level until it exits the 
programming mode.  Outside the programming mode it 
permits the visualisation of the output control power;

: This key is used to display the temperatures read by 

the probes (

Pr1

 and 

Pr2

) and their difference (

Pr1 - Pr2

). 

It can also be programmed through the 

USrb

 parameter 

for: Activating Auto-tuning or Self-tuning, setting the in-
strument to manual regulation, setting the alarm, chang-
ing the active Set Point and deactivating the control;

LED 

OUT1

: Indicates the state of output 

Out1

;

LED 

OUT2

: Indicates the state of output 

Out2

;

LED 

OUT3

: Indicates the state of output 

Out3

;

LED 

OUT4

: Indicates the state of output 

Out4

;

LED 

Tun

: Indicates that the Self-tuning function is activat-

ed (light ON) or that Auto-tuning is in progress (flashing);

10 

LED 

SET

: When flashes, indicates the access to the 

programming mode;

11 

LED 

 Shift index 

-

: Indicates that the process value is 

lower than 

the one programmed for parameter 

AdE

;

12 

LED   Shift index 

=

: Indicates that the process value is 

within the range

 [

SP

 + 

AdE

÷

SP

 - 

AdE

];

13 

LED 

 Shift index 

+

: Indicates that the process value is 

higher than

 the one set for parameter 

AdE

.

2.  PROGRAMMING

2.1  Set Point Fast Programming

This procedure allows you to quickly set the active Set Point 
and, when required, the alarm thresholds (paragraph 2.3).
Press and release the 

 key, the display the display will 

alternate between “

SP

 

n

” and the set value (

n

 is the number 

of the Set Point active at that moment).
To increase/decrease the Set Point value press the 

/

  keys.  

These keys change the value one digit a time but when pressed 
for more than one second, the value increases or decreases 
rapidly and, if pressed for more than two seconds, the changing 
speed increases further to allow the rapid achievement of the 
desired value.
Once the desired value has been reached, pressing key 

 

it is possible to exit the Set Point fast programming mode or 
switch to the alarm thresholds display (paragraph 2.3).
To exit the Set Point fast programming mode it is necessary to 
press the 

 key after the last Set Point has been displayed, 

alternatively, operating no keys for about 15 seconds the dis-
play will return to normal operation.

2.2  Control Status and Parameter Selection

By pushing key 

 and holding it down for about 2 s it is pos-

sible to enter into the main selection menu.  Using the 

/

 

keys, it is then possible to roll over the selections:

oPEr

To enter into the operating parameters menu

ConF

To enter into the configuration parameters menu

oFF

To swap the controller into the OFF state

rEG

To swap the controller into the automatic control state

tunE

To activate the Auto-tuning or Self-tuning function

oPLo

To swap the controller to the manual control state 
and therefore to program the % control value using 
the 

/

 keys

Once the desired item has been selected, push key 

 to 

confirm.  Selecting 

oPEr

 and 

ConF

 gives the possibility of 

accessing other menus containing additional parameters and 
more precisely:

oPEr

  Operating parameters Menu

:

 normally contains the 

Set Point parameters but it can contain all the desired 
parameters (paragraph 2.3).

ConF

  Configuration parameters Menu: contains all the operat-

ing parameters and the functioning configuration param-
eters (alarm configuration, control, input, etc.).

AUTOTUNING

SELFTUNING

Hold 

for 2 s

oFF

SET

PASSWORD

ConF

menu

oPEr

menu

rEG

oPLo

AT-ST

reg  .

0per.

Conf.

off  .

tune.

oplo.

282.8

off

282.8

oplo

PASS = OFF

To enter the menu 

oPEr

, select the option 

oPEr

 and press 

.

Содержание K31D

Страница 1: ...an therefore be used in applications that require a control for the temperature difference between 2 different environments such as liquid coolers chillers natural air conditioning systems through the air recirculation heating by solar panels or in many other applications where 2 temperature readings are needed The controller is also Index 1 Instrument description 1 1 1 General description 1 1 2 F...

Страница 2: ...that the process value is lower than the one programmed for parameter AdE 12 LED Shift index Indicates that the process value is within the range SP AdE SP AdE 13 LED Shift index Indicates that the process value is higher than the one set for parameter AdE 2 PROGRAMMING 2 1 Set Point Fast Programming This procedure allows you to quickly set the active Set Point and when required the alarm threshol...

Страница 3: ...r or disappear on this level by fol lowing this procedure Enter the menu ConF and select the parameter to be made programmable or not programmable in the menu oPEr Once the parameter has been selected if the LED SET is OFF this means that the parameter is programmable only in the menu ConF if instead the SET LED is ON this means that the parameter is also programmable in the menu oPEr To modify th...

Страница 4: ...entioned rule must adopt all the necessary protective measures The instrument MUST NOT be used in dangerous environments flammable or explosive without adequate protection The installer must ensure that EMC rules are respected also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for fl...

Страница 5: ...probe is not connected The instrument allows the measurement calibration that can be used to recalibrate the instrument according to application needs This can be done through parameters OFS1 OFS2 and rot Setting rot 1000 and oFS 1 2 it is possible to set a posi tive or negative offset that is simply added to the value read by the probe before visualisation which remains constant for all the measu...

Страница 6: ...2HL the process value considered by the controller is Pr1 P2LL When P2HL and P2LL thresholds are exceeded by Pr2 tem perature a control takes place as if the Pr2 temperature is the value of the limit regardless of the value actually read The aim of this function is to limit the differential regulation to within a maximum range of the Pr2 measurement With the differential control the working mode F...

Страница 7: ...gle Action PID control can be obtained by program ming parameter Cont Pid and works on 1 rEG output depend ing on the active Set Point SP the functioning mode Func and on the instrument PID algorithm with 2 freedom degrees If the Out1 analogue output is present 0 4 20 mA 0 2 10 V the output will operate as a regulation output providing a value proportional to the regulation power calculated by the...

Страница 8: ...h Func CooL 4 If FAST Auto tuning is desired to start automati cally all times the Set Point is changed or at the end of the programmed Softstart cycle The Auto tuning starts anyway if PV is lower than SP SP 5 with Func HEAt or higher than SP SP 5 with Func CooL 1 If OSCILLATORY Auto tuning is desired to start auto matically all times the instrument is switched ON 2 If OSCILLATORY Auto tuning is d...

Страница 9: ...d when the relative parameters are set to InF If is desired only one ramp e g to reach SP1 it is enough to program the parameter SLor with the desired value The ramp SLor will always be active at Power ON and when the Active Set Point value is changed On the contrary if an automatic cycle is to be executed at Power ON program nSP 2 then the two Set Point values SP1 and SP2 and naturally parameters...

Страница 10: ...AL1 and is deactivated when thePV goes below the value AL1 HAL1 In this way is possible to program with AL1L and AL1H parameters the minimum and the maximum limits of AL1 thresholds LoAb OUT AL1 AL1 PV HAL1 time HiAb off off off OUT AL1 AL1 PV HAL1 time off off off ON ON ON ON LodE Deviation low alarm The alarm is activated when the process value goes below the value SP AL1 and is deactivated when...

Страница 11: ...f a measurement error yES Alarm active no Alarm deactivated 5 12 Loop Break Alarm Function All the parameters referring to the Loop Break alarm function are contained in the group LbA The Loop Break alarm is available on all the instruments which intervenes when for any reason short circuit of a thermocouple thermocouple inversion load interruption the loop control is interrupted First of all it i...

Страница 12: ...nSP 2 and when active it disables the selection of the active Set Point through the parameter SPAt and through the key 5 15 RS485 Serial Interface The instrument can be equipped with a RS485 serial com munications interface by means of which it is possible to connect the controller to a network to which other instru ments PLC controllers are connected All these devices typically depend on a Person...

Страница 13: ...nfiguration or to keep a copy of the parameters setting of an instrument and allow its rapid retransmission The same device allows to connect a PC via USB with which through the appropriate configuration software for AT Univer salConf tool the operating parameters can be configured To use the A01 device it is necessary that the device or instrument are being supplied AC supply Supply adapter 12 VD...

Страница 14: ...Number of decimal figures 0 1 0 12 Aot Analogue control Output type 0 20 0 20mA 4 20 4 20 mA 0 10 0 10 V 2 10 0 10 V 0 10 13 Unit Temperature unit of measurement C F C 14 FiL Input digital filter oFF Not active 0 1 20 0 s 1 0 15 oFS1 Measuring Offset Pr1 1999 9999 0 16 oFS2 Measuring Offset Pr2 1999 9999 0 17 rot Rotation of the measuruing straigìht line 0 000 2 000 1 000 18 InE oPE functioning in...

Страница 15: ... 1 33 AL1d AL1 Alarm activation delay oFF Not active 1 9999 s OFF 34 AL1i Alarm AL1 activation in case of probe error no yES no Group AL2 AL2 Alarm Parameters Parameter Description Range Default Note 35 OAL2 Output where alarm AL2 is addressed oFF Not active Out1 Out2 Out3 Out4 oFF 36 PrA2 AL2 Alarm PV reference Pr1 Pr2 P1 2 P1 L Pr1 37 AL2t AL2 Alarm type LoAb Absolute Low HiAb Absolute High LHAb...

Страница 16: ... error no yES no Group lba Loop Break Alarm Parameters Parameter Description Range Default Note 55 OLbA Output where LbA alarm is addressed oFF Not active Out1 Out2 Out3 Out4 OFF 56 LbAt Time necessary to activate alarm LbA oFF Not active 0 9999 s OFF Group reg Control Parameters Parameter Description Range Default Note 57 Cont Control type Pid PID on FA Asymmetrical ON OFF on FS Symmetrical ON OF...

Страница 17: ...SP Active Set Point selection oFF Control in OFF mode noF 78 diSP Displayed Variable Pr1 Pr1 Value Pr2 Pr2 Value P1 2 Pr1 Pr2 Value Pou Control Power SP F Active Set Point Value SP o Operative Set Point value AL1 AL1 threshold AL2 AL2 threshold AL3 AL3 threshold P1 2 79 AdE Shift value for the shift index functioning 0 OFF 1 9999 2 80 Edit Fast programming Active Set Points and Alarms SE Set Point...

Страница 18: ... contact our sales department to obtain authorisation for sending the instru ment to our company The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of different agreements 8 5 Disposal The appliance or the product must be disposed of separately in compliance with the local standa...

Страница 19: ...61010 1 10 HOW TO ORDER Model K31D Instrument with mechanical keys a Power supply H 100 240 VAC L 24 VAC DC F 12 VAC DC b Inputs 2 For PTC NTC Thermistors or Pt1000 resistance thermometer d Output 2 Out2 R Relay SPDT 8A resistive load O Vdc for SSR Not present e Output 3 Out3 R Relay SPST NO 5A resistive load O Vdc for SSR Not present f Output 4 Out4 R Relay SPST NO 5A resistive load O Vdc for SSR...

Страница 20: ...Ascon Tecnologic K31D OPERATING INSTRUCTIONS PAG 20 ...

Отзывы: