= 6

 - Selecting the active set point (SP/SPE) with contact normally

open:  on  closing the  digital input the temperature set  point “SPE”
is  activated.  When  instead  the  input  is  open  the  set  point  “SP”  is
active.

= 7

 - Switching on/switching off (Stand-by) of instrument by contact

normally  open:  on    closing  the  digital  input  the  instrument  is
switched on while it is placed in Stand-by when opened.

= 8

 - "Turbo" cycle activation command with normally-open contact:

closing the input starts a "turbo" cycle.

=  -1,  -2,  -3,  etc.   

-  Like  function  with  positive  values  but  with

function logic reversed (contact normally closed)

4.5 - OUTPUTS AND BUZZER CONFIGURATION

The  instrument  outputs  can  be  configured  by  the  relative
parameters 

“o.o1” , “o.o2” “o.o3”.

The outputs can be configured for the following functions:

=  ot

  -  to  control  the  compressor  or  however,  the  temperature

control device 

= dF

 - to control the defrosting device

= Fn

 - to control the fans

= Au

 - to control the auxiliary device

= At

 - to control a silenceable alarm device through a contact that

is normally open, and then closed when the alarm sounds

=  AL

  -  to  control  an  alarm  that  cannot  be  silenced  through  a

contact that is normally open and closed when the alarm sounds.

=  An

  -  to  control  an  alarm  with  a  memory  function  through  a

contact  that  is  normally  open  and  closed  when  the  alarm  sounds
(see alarm memory).

= -t

 - to control a silenceable alarm device through a contact that is

normally closed, and then open when the alarm sounds.

=  -L

  -  control  an  alarm  that  cannot  be  silenced  through  a  contact

that is normally closed and open when the alarm sounds.

= -n

 - to control an alarm with a memory function through a contact

that is normally closed and open when the alarm sounds.

= on

 - Output on when the instrument is in on state. This mode can

be  used  to  control  lights,  non-misting  resistance  on  room  door  or
other utilities

=  HE

  -  to  control  an  heating  device  in  neutral  zone  control  mode

(“r.HC” = nr).

= oF

 - Disabled output

The  function  carried  out  for  auxiliary  output  (par.  desired  output  =
Au)  is  defined  by  the  parameter 

“o.Fo”

  and  the  function  is

conditioned by the time set in parameter 

“o.tu”.

The parameter “o.Fo” can be configured for the following functions:

= oF

  - Auxiliary output not active

=  1

  -  Temperature  control  output  delayed  with  contact  normally

open: the auxiliary output is activated with delay that can be set on
the parameter "o.tu" compared to the output configured as ot. The
output  is  then  turned  off  at  the  same  time  as  the  ot  output  is
disabled.  This  function  mode  can  be  used  as  a  command  for  a
second compressor or for all other working utilities according to the
same  ot  output  conditions,  but  which  must  be  delayed  after  the
start up of the compressor to avoid excess electricity absorption.

=  2

  -  Activation  by  front  key  (U  or  DOWN/AUX):  the  output  is

activated  by  pressing  the  keys  U  or  DOWN/AUX  suitably
configured (“t.UF” or “t.Fb” = 1) These commands have a bi-stable
function,  Which  means  that  when  first  pressed,  the  output  key  is
activated  while  the  second  is  disabled.  In  this  mode,  the  AUX
output can be turned off automatically after a certain time that can
be  set  on  the  parameter  "o.tu".  With  "o.tu"  =  oF  the  output  is
activated  and  deactivated  only  manually,  using  the  key  (U  or
DOWN/AUX)  or  via  the  digital  input.  Differently,  the  output,  once
activated,  is  turned  off  automatically  after  the  set  time.  This
function  can  be  used,  for  example,  as  a  cell  light  command,  for
non-misting resistance or other utilities.

=  3

  -  Light  output  managed  by  Active  set  point  (  "economy"

function). 
This output will be on in “normal” mode (Set Point "SP" active) and
off in economy mode operation (Set Point "SP2" active).

= 4

 - Internal Light output managed by digital input. This output will

be on when door is opened (“i.Fi”= 1, 2, 3).
The  internal  buzzer  (if  present)  can  be  configured  by  par. 

“o.bu”

for the following functions:

oF

 = Buzzer always disable

1

 = Buzzer signal active alarms only

2

 = Buzzer signal key pressed only (no alarm) 

3

 = Buzzer signal active alarms and key pressed

4.6 - TEMPERATURE CONTROL

The instrument's method of regulation is of ON/OFF type acting on
the "ot"- and "HE"-configured outputs in response to: the reading of
the  Pr1  probe;  the  active  set  point(s) 

“SP” 

(or

  “SPE” 

and/or

“SPH”

);  the  intervention  differential 

“r.d”

  (or

  “r.Ed”

  and/or

“r.Hd”

); and the operating mode 

“r.HC”

.

Via the parameter 

“r.HC”

 the following functions can be obtained:

= C (Cooling) or = H (Heating)
As  regards  the  operating  mode  programmed  in  the  "r.HC"
parameter, the regulator automatically assumes that the differential
has positive values for a Refrigeration control (“r.HC”=C), negative
values for the Heating control (“r.HC”=H).

ON

r.HC=C

(ot)

Out

Pr1

Temp.

SP

off

ON

ON

off

r.HC=H

ON

ON

Out

(ot)

time

r.d

SP

off

Temp.

Pr1

off

ON

time

r.d

= nr (Neutral Zone or Cooling and Heating a single set point)
If  the  parameter  “r.HC”  is  programmed  such  that  “r.HC”  =  nr  the
output configured as “ot” operates with a cooling action (as “r.HC” =
C) whereas  the output configured as “HE” operates with  a heating
action.  In  this  case  the  regulating  set  point  for  both  outputs  is
whichever  of  SP,  SPE  and  SPH  is  active,  and  the  intervention
differential (“r.d” or “r.Ed” or “r.Hd”) is automatically assumed by the
regulator  to  have  positive  values  for  the  cooling  action,  negative
values for the heating action.

off

Out

Out

(ot)

(HE)

off

0N

SP

Pr1

Tem p.

off

0N

r.d

r.d

time

0N

off

= HC (Cooling and Heating with two independent set points)

SP

(ot)

Out

(HE)

Out

ON

off

off

Pr1

Temp.

time

r.d

r.HC=HC

SPH

r.Hd

off

off

ON

ON

ON

ON

off

off

Similarly, if the parameter “r.HC” is programmed such that “r.HC” =
HC, the output configured as “ot” operates with a cooling action (as
“r.HC” = C) whereas the output configured as “HE” operates with a
heating action.
In this case the regulating set point for the "ot" output is whichever
of SP, SPE and SPH is active, whereas for the output "HE" the set
point is SPH. 

ASCON TECNOLOGIC - Y33 

 

- OPERATING INSTRUCTIONS - Vr. 01 - 04/16 -  ISTR-MY33-ENG01 -  PAG. 6

Содержание Y33

Страница 1: ...EVAPORATOR FANS CONTROL 4 9 DEFROST DISPLAY LOCK 4 8 5 DEFROSTS IN EVENT OF EVAPORATOR PROBE ERROR 4 8 4 END DEFROST 4 8 3 MANUAL DEFROST 4 8 2 AUTOMATIC DEFROST STARTS 4 8 1 DEFROST CONTROL 4 8 COMPRESSOR PROTECTION FUNCTION AND DELAY AT POWER ON 4 7 TEMPERATURE CONTROL 4 6 OUTPUTS AND BUZZER CONFIGURATION 4 5 DIGITAL INPUT 4 4 MEASURING AND DISPLAY 4 3 NORMAL MODE ECONOMIC MODE AND TURBO MODE 4 ...

Страница 2: ...d silenced or memorized flashing 11 Led AUX Indicates AUX output status on on off off or inhibited flashing 12 CLOCK LED Indicates that the internal clock is activated When on indicates that the current time is presumably correct If blinking indicates that there was a supply black out and therefore the current time may not be correct 13 Led Stand By Indicate the Stand by status 2 PROGRAMMING 2 1 F...

Страница 3: ...hich will be possible to have access to the protected parameters 2 5 RESET PARAMETERS TO DEFAULT VALUE LEVEL The instrument allows the reset of the parameters to values programmed in factory as default To restore to the values of default the parameters set the value 48 to r P password request Once confirmed the password with the key P the display it shows for 2 sec therefore the instrument effects...

Страница 4: ...he controller uses the control functions STAND BY means that the controller does not use any control function and the display is turned off except for the Stand by led If there is no power and then power returns the system always sets itself in the condition it was in before the black out The ON Stand by function can be selected Pressing the key U for at least 1 sec if the parameter t UF 3 Pressin...

Страница 5: ...e Pr1 P1 the measurement of the probe Pr2 P2 the measurement of the probe Pr3 P3 the active set point value SP the label Eco when the instrument is in Eco mode Ec or it can have the numerical display switched off oF Through the parameter i CU it is possible to program an measu re offset that will be applied to the temperature show on the display only if i dS P1 P2 P3 Ec The normal visualisation on...

Страница 6: ...figured t UF or t Fb 1 These commands have a bi stable function Which means that when first pressed the output key is activated while the second is disabled In this mode the AUX output can be turned off automatically after a certain time that can be set on the parameter o tu With o tu oF the output is activated and deactivated only manually using the key U or DOWN AUX or via the digital input Diff...

Страница 7: ...off ON ON Pr1 ot Out During the output inhibition the led OUT Cool o Heat blinking It is also possible to prevent activation of the output after the instrument is turned on for the time set in the parameter P od During the power on delay phase the display shows the indication od alternating with the normal visualisation All the functions are disabled by relative parameters oF 4 8 DEFROST CONTROL T...

Страница 8: ... of the temperature difference between cell and evaporator Every variation of the value of the Active Set Point of the differential r d the start of a continuous cycle or the a defrost execution delete this reference value and any reduction will be performed until the acquisition of a new reference value Defrost by evaporator temperature The instrument starts a defrost cycle when the evaporator te...

Страница 9: ...ssible to delay the start up of the fans even after the end of the defrosting of the time set in the parameter F Fd When this delay is active the led FAN flashing to signal the delay in progress When the evaporator probe is used the fans as well as being conditioned by the parameters F tn F tF and F FE are also conditioned by a temperature control It is possible to set the disablement of the fans ...

Страница 10: ...nstrument visualising AL and the variable set in parameter i dS alternately on the display In alarm conditions with i Fi 5 all the control outputs will be off 4 10 3 OPEN DOOR ALARM The instrument can signal an open door alarm by activating the digital input with the function programmed as i Fi 1 2 or 3 When the digital input is activated the instrument show oP and after the delay programmed in pa...

Страница 11: ...99 9 S HS Minimum Set Point S LS 1 S parameters relative to Set Point Note Def Range Description Par oF oF 0 01 9 59 min sec 99 5 min sec x10 Ritardo compressore dopo sbrinamento sgocciolamento d td 34 20 0 oF 0 01 9 59 min sec 99 5 min sec x10 Lenght max of defrost cycle d dE 33 oF oF 0 01 9 59 hrs min 99 5 hrs min x10 Delay start Defrost by continuous compressor running time d cd 32 oF oF on Lb ...

Страница 12: ...e cycle no without compr output condictioning Et Electrical heating with evaporator tempe rature control d dt 35 3 oF 1 2 3 Buzzer function mode o bu 65 Fn oF ot dF Fn Au At AL An t L n on HE OUT3 function see o o1 o o3 64 dF oF ot dF Fn Au At AL An t L n on HE OUT2 function see o o1 o o2 63 ot oF ot dF Fn Au At AL An t L n on HE OUT1 function oF No function ot Temperature control compressor dF De...

Страница 13: ...ring flaws or faulty material that are found within 12 months from delivery date The guarantee is limited to repairs or to the replacement of the instrument The eventual opening of the housing the violation of the instrument or the improper use and installation of the product will bring about the immediate withdrawal of the warranty s effects In the event of a faulty instrument either within the p...

Страница 14: ...acy 0 5 fs 1 digit Sampling rate 130 ms Display 3 Digit Red Blue optional h 15 5 mm Software class and structure Class A Compliance Directive 2004 108 CE EN55022 class B EN61000 4 2 8KV air 4KV cont EN61000 4 3 10V m EN61000 4 4 2KV supply and relay outputs 1KV inputs EN61000 4 5 supply 2KV com mode 1 KV diff mode EN61000 4 6 3V Directive 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN...

Отзывы: