To come back at the group selection mode keep the U key pressed
for 1 sec. until will show the code group.
Pressing the UP and DOWN  keys, it is possible to select another
group  of  parameters,  another  parameter  and  change  it  as
described.
To exit the programming mode, do not press any key for about 30
seconds,  or  keep  the  U  key  pressed  for  2  sec.  until  it  exits  the
programming mode.

2.3 - PARAMETER PROTECTION USING THE PASSWORD

The  instrument  has  a  parameter  protection  function  using  a
password that can be personalised, through the  

“t.PP”

 parameter.

If  one  wishes  to  have  this  protection,  set  the  password  number
desired  in  the  parameter  “t.PP”.  When  the  protection  is  activate,
press  the  P  key  to  access  the  parameters  and  keep  it  press  for
about 5 seconds, after which the display will show 

“r.P”

 .

At  this  point  press  P,  the  display  show  “0”,  using  the    UP  and
DOWN    keys,  set  the  password  number  programmed  and  press
the key P.
If  the  password  is  correct,  the  display  will  visualise  the  code  that
identifies  the  first  group  of  parameters  and  it  will  be  possible  to
program the instrument in the same ways described in the previous
section.
Protection  using  a  password  can  be  disabled  by  setting  the
parameter “t.PP” = oF.

Note:

 If the Password gets lost, just swith off and on the instrument

supply,  push  P  key  during  the  initial  test  and  keeping  the  key
pressed for 5 seconds.
In this way it’s possible to have access to all the parameters, verify
and modify the par. “t.PP”.

2 sec.

Hold for

5 sec.

Hold for

2.4  -  CUSTOMIZED  MODE  PARAMETER  PROGRAMMING   
(PARAMETERS PROGRAMMING LEVEL)

The  password  protection  hides  all  the  configuration  parameters
behind  a  factory  set  password  to  avoid  unwanted  changes  being
made to the programming of the controller.

5 sec.

Hold for

2 sec.

Hold  for

To  make  a  parameter  accessible  without  having  to  enter  the
password  when  “t.PP”  password  protection  is  activate  follows  this
procedure.

Enter  the  programming  using  the  Password  “t.PP”  and  select  the
parameter  which  is  desired  to  be  accessible  with  no  password
protection.
Once  the  parameter has  been selected,  if  the SET  led  is blinking,
this  means  that  the  parameter  is  programmable  by  entering  the
password  (it’s  then  “protected”)  if  it’s  instead  on,  this  means    the
parameter is programmable without password (not protected).
If  you  want  to  change  the  accessibility  of  the  parameter    push  P
key, keep it pressed and press together also the key UP.
The led SET will change its state indicating the new access level of
the  parameter  (on  =  not  protected;  blinking  =  protected  by
password).
In case some parameters are not protected, when one tries to have
access  at  the  programming,  the  display  will  show  all  the
parameters not protected and the par. 

“r.P”

 (through which will be

possible to have access to the “protected” parameters.)

2.5 - RESET PARAMETERS TO DEFAULT VALUE/LEVEL

The  instrument  allows  the  reset  of  the  parameters  to  values
programmed in factory as default.  
To restore to the values of default the parameters set the value 

-48

to “r.P” password request.
Once  confirmed  the  password  with  the  key  P  the  display  it  shows
"---"  for  2  sec.  therefore  the  instrument  effects  the  parameters
reset..

2.6 - KEYBOARD LOCK FUNCTION

On the instrument  it’s possibile to lock completely the keyboard. 
This  function  is  particularly useful  when  the  regulator is  reachable
by the users and it’s desired to avoid any modification.
To  activate  the keyboard  lock it’s  enough  program the  par. 

“t.Lo”

to a different value to oF. 
The value program to this parameter it is the time of inactivity of the
keys afterwhich the keyboard will be locked.
Insofar  not  pressing    any  key  for  the  time  "t.Lo"  the  instrument
automatically disable the normal functions of the keys.
When  the  keyboard  is  lock,  if  any  of  the  key  is  pushed,  on  the
display will appear  

“Ln” 

to indicate the active lock.

To unlock  the keyboard it’s enough to contemporarily push   key P
and UP and keep them pushed for 5 sec., afterwhich the label 

“LF”

will appear on the display and all the keys functions will be availab-
le again .

3 - INFORMATION ON INSTALLATION AND USE

3.1 - PERMITTED USE

The 

instrument 

has 

been 

projected 

and

manufactured as a measuring and control device to
be  used  according  to  EN60730-1  for  the  altitudes
operation until 2000 ms.

 

The use of the instrument

for  applications  not  expressly  permitted  by  the

above  mentioned  rule  must  adopt  all  the  necessary  protective
measures. 
The  instrument  CANNOT  be  used  in  dangerous  environments
(flammable or explosive) without adequate protection. 
The  instrument used  with  NTC 103AT11  probe (identifiable  by  the
printed  code  “103AT-11”  visible  on  the  sensor  part)  is  compliant
with standard EN 13485 ("Thermometers for measuring the air and
product  temperature  for  the  transport,storage  and  distribution  of
chilled, frozen,  deep-frozen/quick-frozen food and ice cream”)  with
the following classification: [EN13485 air, S, A, 2,- 50°C +90°C]
Remember  that  the  end  user  must  periodically  checks  and  verify
the thermometers in compliance with standard EN 13486.
The installer must ensure that EMC rules are respected, also after
the  instrument  installation,  if  necessary  using  proper  filters.
Whenever  a  failure  or  a  malfunction  of  the  device  may  cause
dangerous  situations  for  persons,  thing  or  animals,  please
remember that the plant has to be equipped with additional devices
which will guarantee safety..  

3.2 - MECHANICAL MOUNTING

The instrument, in case 78 x 35 mm, is designed for flush-in panel
mounting. Make a hole 71 x 29 mm and insert the instrument, fixing
it  with  the  provided  special  brackets.  We  recommend  that  the

ASCON TECNOLOGIC - Y33 

 

- OPERATING INSTRUCTIONS - Vr. 01 - 04/16 -  ISTR-MY33-ENG01 -  PAG. 3

Содержание Y33

Страница 1: ...EVAPORATOR FANS CONTROL 4 9 DEFROST DISPLAY LOCK 4 8 5 DEFROSTS IN EVENT OF EVAPORATOR PROBE ERROR 4 8 4 END DEFROST 4 8 3 MANUAL DEFROST 4 8 2 AUTOMATIC DEFROST STARTS 4 8 1 DEFROST CONTROL 4 8 COMPRESSOR PROTECTION FUNCTION AND DELAY AT POWER ON 4 7 TEMPERATURE CONTROL 4 6 OUTPUTS AND BUZZER CONFIGURATION 4 5 DIGITAL INPUT 4 4 MEASURING AND DISPLAY 4 3 NORMAL MODE ECONOMIC MODE AND TURBO MODE 4 ...

Страница 2: ...d silenced or memorized flashing 11 Led AUX Indicates AUX output status on on off off or inhibited flashing 12 CLOCK LED Indicates that the internal clock is activated When on indicates that the current time is presumably correct If blinking indicates that there was a supply black out and therefore the current time may not be correct 13 Led Stand By Indicate the Stand by status 2 PROGRAMMING 2 1 F...

Страница 3: ...hich will be possible to have access to the protected parameters 2 5 RESET PARAMETERS TO DEFAULT VALUE LEVEL The instrument allows the reset of the parameters to values programmed in factory as default To restore to the values of default the parameters set the value 48 to r P password request Once confirmed the password with the key P the display it shows for 2 sec therefore the instrument effects...

Страница 4: ...he controller uses the control functions STAND BY means that the controller does not use any control function and the display is turned off except for the Stand by led If there is no power and then power returns the system always sets itself in the condition it was in before the black out The ON Stand by function can be selected Pressing the key U for at least 1 sec if the parameter t UF 3 Pressin...

Страница 5: ...e Pr1 P1 the measurement of the probe Pr2 P2 the measurement of the probe Pr3 P3 the active set point value SP the label Eco when the instrument is in Eco mode Ec or it can have the numerical display switched off oF Through the parameter i CU it is possible to program an measu re offset that will be applied to the temperature show on the display only if i dS P1 P2 P3 Ec The normal visualisation on...

Страница 6: ...figured t UF or t Fb 1 These commands have a bi stable function Which means that when first pressed the output key is activated while the second is disabled In this mode the AUX output can be turned off automatically after a certain time that can be set on the parameter o tu With o tu oF the output is activated and deactivated only manually using the key U or DOWN AUX or via the digital input Diff...

Страница 7: ...off ON ON Pr1 ot Out During the output inhibition the led OUT Cool o Heat blinking It is also possible to prevent activation of the output after the instrument is turned on for the time set in the parameter P od During the power on delay phase the display shows the indication od alternating with the normal visualisation All the functions are disabled by relative parameters oF 4 8 DEFROST CONTROL T...

Страница 8: ... of the temperature difference between cell and evaporator Every variation of the value of the Active Set Point of the differential r d the start of a continuous cycle or the a defrost execution delete this reference value and any reduction will be performed until the acquisition of a new reference value Defrost by evaporator temperature The instrument starts a defrost cycle when the evaporator te...

Страница 9: ...ssible to delay the start up of the fans even after the end of the defrosting of the time set in the parameter F Fd When this delay is active the led FAN flashing to signal the delay in progress When the evaporator probe is used the fans as well as being conditioned by the parameters F tn F tF and F FE are also conditioned by a temperature control It is possible to set the disablement of the fans ...

Страница 10: ...nstrument visualising AL and the variable set in parameter i dS alternately on the display In alarm conditions with i Fi 5 all the control outputs will be off 4 10 3 OPEN DOOR ALARM The instrument can signal an open door alarm by activating the digital input with the function programmed as i Fi 1 2 or 3 When the digital input is activated the instrument show oP and after the delay programmed in pa...

Страница 11: ...99 9 S HS Minimum Set Point S LS 1 S parameters relative to Set Point Note Def Range Description Par oF oF 0 01 9 59 min sec 99 5 min sec x10 Ritardo compressore dopo sbrinamento sgocciolamento d td 34 20 0 oF 0 01 9 59 min sec 99 5 min sec x10 Lenght max of defrost cycle d dE 33 oF oF 0 01 9 59 hrs min 99 5 hrs min x10 Delay start Defrost by continuous compressor running time d cd 32 oF oF on Lb ...

Страница 12: ...e cycle no without compr output condictioning Et Electrical heating with evaporator tempe rature control d dt 35 3 oF 1 2 3 Buzzer function mode o bu 65 Fn oF ot dF Fn Au At AL An t L n on HE OUT3 function see o o1 o o3 64 dF oF ot dF Fn Au At AL An t L n on HE OUT2 function see o o1 o o2 63 ot oF ot dF Fn Au At AL An t L n on HE OUT1 function oF No function ot Temperature control compressor dF De...

Страница 13: ...ring flaws or faulty material that are found within 12 months from delivery date The guarantee is limited to repairs or to the replacement of the instrument The eventual opening of the housing the violation of the instrument or the improper use and installation of the product will bring about the immediate withdrawal of the warranty s effects In the event of a faulty instrument either within the p...

Страница 14: ...acy 0 5 fs 1 digit Sampling rate 130 ms Display 3 Digit Red Blue optional h 15 5 mm Software class and structure Class A Compliance Directive 2004 108 CE EN55022 class B EN61000 4 2 8KV air 4KV cont EN61000 4 3 10V m EN61000 4 4 2KV supply and relay outputs 1KV inputs EN61000 4 5 supply 2KV com mode 1 KV diff mode EN61000 4 6 3V Directive 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN...