ASCON TECNOLOGIC - TLK33 - OPERATING INSTRUCTIONS 

- PAG. 7

With  this  mode  is  possible  to  program  the  minimum  and  the 
maximum set  of  “AL1” by “AL1L” and “AL1H” parameters. 

LoAb

off

ON

AL1

AL1

PV

HiAb

HAL1

time

off

ON

AL1

PV

time

HAL1

off

off

ON

OUT

off

off

ON

OUT

AL1

LodE

 = DEVIATION LOW ALARM: The alarm is activated when the 

process  value  goes  below  the  value  [SP1  +  AL1]  and  will  be 
deactivated when it goes above the value [SP1 + AL1 + HAL1]. 
With  this  mode  is  possible  to  program  the  minimum  and  the 
maximum set  of  “AL1” by “AL1L” and “AL1H” parameters. 

HidE

 = DEVIATION HIGH ALARM: The alarm is activated when the 

process  value  goes  above  the  value  [SP1  +  AL1]  and  will  be 
deactivated when it goes below the value [SP1 +  AL1 - HAL1]. 
With  this  mode  is  possible  to  program  the  minimum  and  the 
maximum set  of  “AL1” by “AL1L” and “AL1H” parameters. 

LodE

ON

off

PV

SP

-AL1

HAL1

time

off

ON

SP

AL1

PV

HidE

time

HAL1

ON

off

off

off

off

ON

OUT

AL1

OUT

AL1

LHAb

  =  ABSOLUTE  BAND  ALARM:  The  alarm  is  activated  when 

the process value goes under the alarm threshold set on parameter 
"AL1L"  or  goes  higher  than  the  alarm  threshold  set  on  parameter 
"AL1H" and will be deactivated when it goes below the value [AL1H 
- HAL1] or when it goes above the value [AL1L + HAL1].

LHdE

  =  DEVIATION  BAND  ALARM:  The  alarm  is  activated  when

the  process  value  goes  below  the  value  [SP1  +  AL1L]  or  goes
above than the value [SP1 + AL1H] and will be deactivated when it
goes below the value [SP1 + AL1H - HAL1] or when it goes above
the value [SP1 + AL1L + HAL1].

LHAb

ON

off

AL1H

AL1L

PV

ON

time

off

HAL1

HAL1

SP

AL1L

AL1H

PV

time

LHdE

HAL1

HAL1

off

off

ON

ON

off

off

OUT

AL1

OUT

AL1

"

Ab1" - ALARM CONFIGURATION:

 This parameter can assume a 

value between 0 and 15. 
The  number  to  be  set,  which  will  correspond  to  the  function 
desired, is obtained by adding the values reported in the following 
descriptions : 
ALARM  BEHAVIOUR  AT  SWITCH  ON:  the  alarm  output  may 
behave in two different ways, depending on the value added to par. 
“Ab1”. 
+0  =  NORMAL  BEHAVIOUR:  The  alarm  is  always  activated  when
there are alarm conditions.
+1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched
on, the instrument is in alarm condition, the alarm is not activated.
It  will  be  activated  only  when  the  process  value  is  in  non-alarm
conditions  and then back in alarm conditions.

P V

+ 1

+ 0

t i m e

A L 1

O N

O N

O N

o f f

o f f

o f f

o f f

A b 1

exemple with absolute low alarm 

ALARM  DELAY:    the  alarm  output  may  behave  in  two  different 
ways depending on the value added to par. “Ab1”. 
+0  =  ALARM  NOT  DELAYED:  The  alarm  is  immediately  activated
when the alarm condition occurs.
+2  =  ALARM  DELAYED:  When  the  alarm  condition  occurs,  delay
counting  begins,  as  programmed  on  par.  “AL1d”  (expressed  in
sec.) and the alarm will be activated only after the elapsing of that
time.
ALARM  LATCH:  :    the  alarm  output  may  behave  in  two  different
ways depending on the value added to par. “Ab1”.
+ 0  =  ALARM  NOT  LATCHED:  The alarm remains active in alarm
conditions only.
+ 4  =  ALARM  LATCHED:  The  alarm  is  active  in  alarm  conditions
and  remains  active  even  when  these  conditions  no  longer  exist,
until    the  correctly  programmed  key  “U”,  (“USrb”=Aac)  has  been
pushed.

A L 1

P V

O N

O N

t i m e

+ 0

A b 1

+ 4

o f f

o f f

o f f

exemple with absolute high alarm

 

ALARM  AKNOWLEDGEMENT:  :    the  alarm  output may behave in 
two different ways depending on the value added to par. “Ab1”. 
+ 0  =  ALARM  NOT  AKNOWLEDGED:  The  alarm  always  remains
active in alarm conditions.
+ 8  =  ALARM  AKNOWLEDGED:  The  alarm  is  active  in  alarm
conditions  and  can  be  deactivated  by  key  “U”  if  properly
programmed (“USrb”=ASi), and also if alarm conditions still exist.

"AL1i"  -  ALARM  ACTIVATION  IN  CASE  OF  MEASUREMENT 
ERROR:

  This  allows  one  to  establish  how the alarm have behave 

in  the  event  of  a measurement error (yES=alarm active; no=alarm 
deactivated). 

4.6 - FUNCTIONING OF KEY “U”

 

The function of key “U” can be set through par. 

“USrb”

 contained 

in the group “

]

PAn”.

The parameter can be programmed as : 

= noF

 : no function 

=  tunE

  :  Pushing  the  key  for  1  sec.  at  least,  it  is  possible  to 

activate/deactivate Auto-tuning or Self-tuning 

= OPLO

 : Pushing the key for 1 sec. at least, it is possible to swap 

from automatic control (rEG) to manual one (OPLO) and vice versa. 

=  Aac

  :  Pushing  the  key  for  1  sec.  at  least,  it  is  possible  to 

acknowledge the alarm. (see par. 4.5) 

=  ASi 

:  Pushing  the  key  for  1  sec.  at  least,  it  is  possible  to 

acknowledge an active alarm (see par. 4.5) 
 

= CHSP

 : Pushing the key for 1 sec. at least, it is possible to select 

one of the 4 pre-programmed Set Points on rotation.  

= OFF

  :  Pushing  the  key  for  1  sec. at least, it is possible to swap 

from automatic control (rEG) to OFF control (OFF) and vice versa. 

4.7 - DIGITAL INPUTS 

The instrument can be equipped with 2 digital inputs. 

Содержание TLK 33

Страница 1: ...PUTS 4 8 RS 485 SERIAL INTERFACE 4 9 PARAMETERS CONFIGURATION BY A01 5 PROGRAMMABLE PARAMETERS TABLE 6 PROBLEMS MAINTENANCE AND GUARANTEE 6 1 ERROR SIGNALLING 6 2 CLEANING 6 3 GUARANTEE AND REPAIRS 7...

Страница 2: ...an one second the value increases or decreases rapidly and after two seconds in the same condition the changing speed increases in order to allow the desired value to be reached rapidly Once the desir...

Страница 3: ...electing the desired state from the main selection menu suing the keyboard By using the key U on the keyboard suitably programming par USrb USrb tunE USrb OPLO USrb OFF it is possible to pass from rEG...

Страница 4: ...upply for each instrument as there is no isolation between the power supply and input We recommend that a check should be made that the parameters are those desired and that the application functions...

Страница 5: ...is possible to obtain a heating effect polarizing in one direction and a cooling effect when polarizing in the other direction The Double Action PID control works on the output depending on the active...

Страница 6: ...Point SP2 after a set time thus obtaining a simple automatic process cycle These functions are available for all the programmable controls PID single and double action ON OFF and Neutral Zone ON OFF...

Страница 7: ...onditions and then back in alarm conditions P V 1 0 t i m e A L 1 O N O N O N o f f o f f o f f o f f A b 1 exemple with absolute low alarm ALARM DELAY the alarm output may behave in two different way...

Страница 8: ...485 GND B HOST PC PLC 120 ohm Rt 10 8 9 10 8 9 If the instrument is equipped with a serial interface the parameters to be programmed are the following all present in the parameters group SEr Add Addre...

Страница 9: ...9 9999 0 16 rot Rotation of the measuring straight line 0 000 2 000 1 000 17 InE OPE functioning in case of measuring error Our Or Ur OUr 18 OPE Output power in case of measuring error 100 100 0 19 dI...

Страница 10: ...the correct functioning of the probe uuuu The measured variable is under the probe s limits under range oooo The measured variable is over the probe s limits over range ErAt Auto tuning not possible b...

Страница 11: ...34 MAX 12 mm 7 4 FUNCTIONAL FEATURES Control PID double action Measurement range according to the used probe see range table Display resolution according to the probe used 1 0 1 0 01 0 001 Overall acc...

Страница 12: ...a b c d e f g hh i a POWER SUPPLY G 12 24 VDC b INPUT D thermoresistances Pt100 thermocouples J K S I R mV E thermistors PTC NTC thermocouples J K S I R mV I normalized signals 0 4 20 mA V normalized...