Ascon tecnologic TLK 33 Скачать руководство пользователя страница 6

ASCON TECNOLOGIC - TLK33 - OPERATING INSTRUCTIONS -

 PAG. 6

3) Exit from the parameter programming.
4) Connect the instrument to the controlled plant.
5) Activate the Auto-tuning by switch off and turn on the instrument
if “Auto”=1 or 2 , or by selecting par. 

“tunE”

 in the main menu (or

by correctly programming key “U” ).
At this point the Auto-tuning function is activated and is indicated by
the flashing led AT/ST.
The regulator carries out several operations on the connected plant
in order to calculate the most suitable PID parameters.
If,  at  the  Auto-tuning  start,  the  condition  for  the  lower  or  higher
process  value  is  not  found  the  display  will  show 

“ErAt”

  and  the

instrument  will  be  swapped  to normal control conditions according
to the previously programmed parameters.
To make the error “ErAt” disappear, press key P.
The  Auto-tuning  cycle  duration  has  been  limited  to  12  hours
maximum.
If Auto-tuning is not completed within 12 hours, the instrument will
show 

"noAt" 

on the display

.

In case of probe error, the instrument automatically stops the cycle
in progress.
The  values  calculated  by  Auto-tuning  are  automatically  stored  in
the instrument’s memory at the end of the correct PID parameters
tuning.

Note :

 The instrument is already programmed in our factory to carry

out auto-tuning at  the first instrument switch on ("Auto" = 2).

To activate the SELF-TUNING function proceed as follows 
1) Program and activate the desired Set Point.
2) Program par. 

"SELF"

 = yES

3) Exit from the parameter programming.
4) Connect the instrument to the controlled plant.
5) Activate  Self-tuning  selecting par. 

“tunE”

 in the main menu (or

by correctly programming key “U”).
When  the  Self-tuning  function  is  active,  the  led  AT/ST  is
permanently  lit  up  and  all  the  PID  parameters  ("Pb",  "Int",  "dEr",
etc.) are no longer visualized.

Note  :

  It’s  always  preferable  tuning    the  instrument  using  the

Autotuning  and  to  activate  the  Selftuning  after  because  the tuning
through Selftuning is more slow.

To stop the Auto-tuning cycle or deactivate the Self-tuning function 
select  one  of  the  control  types  :  "rEG", "OPLO" or "OFF" from the 
menu “SEL”. If the instrument is switched off during Auto-tuning or 
with  the  Self-tuning  function  activated,  these  functions  will  remain 
activated the next time it is switched on. 

4.8 - REACHING OF THE SET POINT AT CONTROLLED SPEED 
AND  AUTOMATIC  SWITCHING  BETWEEN  TWO  SET  POINTS 
(RAMPS AND DWELL TIME)

 

All the parameters referring to the ramps functioning are contained 
in the group 

]

rEG”.

It is possible to reach the set point in a predetermined time (in any 
case  longer  than  the  time  the  plant  would  naturally  need).  This 
could  be  useful  in  those  processes  (heating  or  chemical 
treatments, etc.) where the set point has to be reached gradually, in 
a predetermined time. 
Once  the  instrument  has  reached  the  first  Set  Point  (SP1)  it  is 
possible to have automatic switching to the second Set Point (SP2) 
after a set time, thus obtaining a simple automatic process cycle. 
These  functions  are  available  for  all  the  programmable  controls 
(PID  single  and  double  action,  ON/OFF  and  Neutral  Zone 
ON/OFF). 
The function is determined by the following parameters :  

"SLor"

 - Gradient of first ramp expressed in unit/minute  

"SLoF"

 - Gradient of second ramp  expressed in unit/minute. 

"dur.t"

 - Dwell time of Set Point “SP1” before automatic switching 

to Set Point “SP2” (expressed in hrs. and min.). 
The  functions  are  deactivated  when  the  relative  parameters  are  = 
InF. 

Note:

  In  case  of  PID  control,  if  Auto-tuning  is  desired  whilst  the 

ramp  function  is  active,  this  will  not  be  carried  out  until  the  tuning 
cycle has been completed. It is therefore recommended that Auto-

tuning  be  started  avoiding  activating  the  ramp  function  and,  once 
the  tuning  is  finished,  deactivate  Auto-tuning    (“Auto”  =  OFF), 
program  the  desired  ramp  and,  if  it  automatic  tuning  is  desired, 
enable the Self-tuning function. 

If  is  desired  only  one  ramp  (ex.  to  reach  “SP1”)  it  is  enough  to 
program on  the par. "SLor" the desired value.    
The  ramp  "SLor"  it  will  always  active  at  power  on  and  when  the 
Active Set Point value is changed. 

S P 1

[U n it]

P V

S P 1  V a lu e

c h a n g e

S P 1

tim e  [m in .]

S L o r

S L o r

If  it  is  desired  an  automatic  cycle  from  the  power  on  instead  it  is 
necessary  to  program  the  par.  "nSP"  =  2,  to  program  the  two  Set 
Point  values  "SP1"  and  "SP2"  and  naturally  to  program  the  par. 
"SLor", "dur.t" and "SLoF" with the desired values.    
In  this  case  at  the  end  of  the  cycle  all  the  ramps  won't  be  more 
active. 

[ U n it ]

S P 1

P V

A U T O

c h a n g e

S e t

d u r . t

S P 2

t im e   [ m in . ]

S L o r

S L o F

Examples  with  starts  from  values  lower  than  SP  and  with 
decreasing of SP. 

4.5 - ALARMS OUTPUTS FUNCTIONS (AL1, AL2)

 

The instrument can have up to 2 alarm outputs to drive solid state 
relays type (SSR). 
All the parameters referring to the alarms functioning are contained 
in the groups 

]

AL1” 

and

 “

]

AL2”.

Note:

 In all the examples that follow is made reference to the alarm 

AL1. Naturally the operation of the alarm AL2 results analogous.

 

The alarm functioning is instead defined by parameters : 

"AL1t "

 - ALARM TYPE 

"Ab1"

 - ALARM CONFIGURATION 

“AL1”

 - ALARM THRESHOLD  

“AL1L”

  -  LOW  ALARM  THRESHOLD  (for  band  alarm)  OR 

MINIMUM  SET  OF  AL1  ALARM  THRESHOLD  (for  low  or  high 
alarm) 

“AL1H”

  -  HIGH  ALARM  THRESHOLD  (for  band  alarm)  OR 

MAXIMUM  SET  OF  AL1  ALARM  THRESHOLD  (for  low  or  high 
alarm) 

“HAL1” - 

ALARM HYSTERESIS 

“AL1d”

 - ALARM ACTIVATION DELAY (in sec.) 

"AL1i"

 

ALARM 

BEHAVIOUR 

IN 

THE 

EVENT 

OF 

MEASUREMENT ERROR 

"AL1t"  –  ALARM  TYPE  :

    the  alarm  output  can  behave  in  six 

different ways.

 

LoAb

 = ABSOLUTE LOW ALARM: The alarm is activated when the 

process  value  goes  below  the  alarm  threshold  set  on  parameter 
"AL1”  and  will  be  deactivated  when  it  goes  above  the  value 
[AL1+HAL1].  
With  this  mode  is  possible  to  program  the  minimum  and  the 
maximum set  of  “AL1” by “AL1L” and “AL1H” parameters. 

HiAb

 = ABSOLUTE HIGH ALARM: The alarm is activated when the 

process  value  goes  higher  than  the  alarm  threshold    set  on 
parameter  "AL1"  and  will  be  deactivated  when  it  goes  below  the 
value [AL1 - HAL1]. 

Содержание TLK 33

Страница 1: ...PUTS 4 8 RS 485 SERIAL INTERFACE 4 9 PARAMETERS CONFIGURATION BY A01 5 PROGRAMMABLE PARAMETERS TABLE 6 PROBLEMS MAINTENANCE AND GUARANTEE 6 1 ERROR SIGNALLING 6 2 CLEANING 6 3 GUARANTEE AND REPAIRS 7...

Страница 2: ...an one second the value increases or decreases rapidly and after two seconds in the same condition the changing speed increases in order to allow the desired value to be reached rapidly Once the desir...

Страница 3: ...electing the desired state from the main selection menu suing the keyboard By using the key U on the keyboard suitably programming par USrb USrb tunE USrb OPLO USrb OFF it is possible to pass from rEG...

Страница 4: ...upply for each instrument as there is no isolation between the power supply and input We recommend that a check should be made that the parameters are those desired and that the application functions...

Страница 5: ...is possible to obtain a heating effect polarizing in one direction and a cooling effect when polarizing in the other direction The Double Action PID control works on the output depending on the active...

Страница 6: ...Point SP2 after a set time thus obtaining a simple automatic process cycle These functions are available for all the programmable controls PID single and double action ON OFF and Neutral Zone ON OFF...

Страница 7: ...onditions and then back in alarm conditions P V 1 0 t i m e A L 1 O N O N O N o f f o f f o f f o f f A b 1 exemple with absolute low alarm ALARM DELAY the alarm output may behave in two different way...

Страница 8: ...485 GND B HOST PC PLC 120 ohm Rt 10 8 9 10 8 9 If the instrument is equipped with a serial interface the parameters to be programmed are the following all present in the parameters group SEr Add Addre...

Страница 9: ...9 9999 0 16 rot Rotation of the measuring straight line 0 000 2 000 1 000 17 InE OPE functioning in case of measuring error Our Or Ur OUr 18 OPE Output power in case of measuring error 100 100 0 19 dI...

Страница 10: ...the correct functioning of the probe uuuu The measured variable is under the probe s limits under range oooo The measured variable is over the probe s limits over range ErAt Auto tuning not possible b...

Страница 11: ...34 MAX 12 mm 7 4 FUNCTIONAL FEATURES Control PID double action Measurement range according to the used probe see range table Display resolution according to the probe used 1 0 1 0 01 0 001 Overall acc...

Страница 12: ...a b c d e f g hh i a POWER SUPPLY G 12 24 VDC b INPUT D thermoresistances Pt100 thermocouples J K S I R mV E thermistors PTC NTC thermocouples J K S I R mV I normalized signals 0 4 20 mA V normalized...

Отзывы: