BEFORE REQUESTING REPAIR OR SERVICES

Symptom

Cause

Solution

The machine will 

not start.

① The power cord is not plugged in.

① Plug in the power cord

② The safety cable is not connected.

② Connect the safety cable.

③ The machine is in high pressure shut 

off.

③ Reduce the pressure in the high 

pressure line.

④ The breaker tripped.

④ Reset the breaker.

⑤ The thermal protector operates due to 

overheating of the motor.

⑤ Wait until the motor cools down.

⑥ The cylinder is full.

⑥ Replace the cylinder

⑦ The float sensor of the cylinder is out 

of order.

⑦ Repair

⑧ The motor is burned.

⑧ Repair

⑨ The compressor is locked.

⑨ Repair

⑩ Wiring disconnection

⑩ Repair

⑪ The high pressure switch is out of 

order.

⑪ Repair

⑫ The low pressure switch is out of 

order.

⑫ Repair

The machine 

stops soon after 

starting.

① The valve on the discharge side hose 

is closed.

① Open the valve on the hose of 

discharge side.

② The liquid valve on the cylinder is 

closed.

② Open the liquid valve on the cylinder.

③ The pressure in the cylinder is high.

③ Cool the cylinder or use Cooling Unit.

④ Voltage drop

④ Connect to a 220V power source.  

Use appropriate extension code. 

The recovery 

speed is slow or 

the machine will 

not recover.

① The suction side hose is connected to 

vapor port.

① Connect to liquid port of suction side 

hose.

② The filter dryer is clogged.

② Clean or replace the filter dryer.

③ The pressure in the cylinder is high.

③ Cool the cylinder.

④ The hose has a core depressor.

④ Remove the core depressor in the 

hose.

⑤ The refrigerant in the system is 

frozen.

⑤ Perform liquid recovery after melting.

The machine will 

not restart.

① The motor is overheated.

① Wait until the motor cools down.

② The difference in pressure between 

the suction side and the discharge 

side is too large as the pressure in the 

cylinder is high.

② Balance the pressure.

③ The breaker tripped.

③ Reset the breaker.

④ The low pressure switch tripped.

④ Make suction side pressure higher 

than atmospheric pressure.

Turn on the oil 

flooded lamp.

① Flooded of oil in the oil separator.

① Discharge oil operation following Page 

16.

BEFORE

 REQUESTING

 

REPAIR

 OR

 SERVICES

Содержание ECOcycle Aurora II

Страница 1: ...INSTRUCTION MANUAL Recovery and Reclaim machine ECOcycle Aurora IM1401 Please read this manual before operating...

Страница 2: ...sories Other Air Conditioning Equipment 8 HOW TO USE 9 Preparation before Operation 9 Recovery Reclaim Operation 10 Discharge Oil Method Oil separator 16 Discharge Oil Method Electrostatic filter 16 W...

Страница 3: ...d smoking during the work in process Cigarette light may creates Carbon Oxy Chloride and ignite fire Use protective eye glass and hand glove when disconnecting hoses If Freon gas was touch your skin o...

Страница 4: ...generator is not large enough it may lead to heating smoking or fire See the machine plate or this manual for the detailed specifications Do not setup the machine at location where gasoline thinner or...

Страница 5: ...esult is unpredictable Do not use the machine for purposes other than the original intent This machine is designed to recover the specified refrigerants Do not operate under an excessive heavy load to...

Страница 6: ...ation strange noise is noticed stop the unit and refer to the Page22 BEFORE REQUESTING REPAIR OR SERVICES in the manual Request for repair or service instead of disassembling for repair contact the st...

Страница 7: ...de Safety cable Oil discharge port for Electrostatic lter Speci cation label Description label Dry lter Discharge valve Suction valve Auto OFF Manual switch Power Breaker COMPONENTS OF THE MACHINE Lab...

Страница 8: ...ion 587 622W 50 60Hz Electric current of operation Electric current of starting 8 9 6 0A 50 60Hz 34A Operating temperature 5 35 Applicable cylinder over fill protection method Float sensor type Recove...

Страница 9: ...liquid Adapter for different diameter for auto A C quick type 3 16 female x 1 4 male Y19120 Adapter to connect to the small service port 3 16 for R12 High pressure quick joint for R134a M12 Y03100A Fo...

Страница 10: ...r when the vacuum reaches 0 095MPa 13 8psi 0 1MPa 14 5psi Switch off the vacuum pump Disconnect the hose between the vacuum pump and the cylinder In case of the temperature under 10 it needs warming u...

Страница 11: ...side CLOSE Vapor valve System Manifold Optional Acc Eco Cycle Aurora Cylinder with over protection sensor Low pressure side High pressure side High pressure side Liquid port Safety cable Filter CLOSE...

Страница 12: ...e Purge position Connect hose to liquid side of cylinder after the suction pressure gauge was reach vacuum again Set the Power switch to the OFF position 2 Evacuation of the recovery machine and the h...

Страница 13: ...valve OPEN Ball valve AutoOFF 2 ON 3 OFF 7 OPEN Suction valve RECOVERY Switching valve OPEN Discharge valve OPEN SLOWLY OPEN 4 CLOSE 6 CLOSE 8 CLOSE 8 Low pressure side High pressure side CLOSE Low pr...

Страница 14: ...lve Slowly open the ball valve of the suction hose which almost opened with taking 20 seconds Follow ordinal recovery reclaim procedure SLOWLY OPEN OPEN Liquid valve CLOSE Vapor valve System Manifold...

Страница 15: ...rate See the instruction manual of Cooling Unit for detailed information Use an evacuated spare cylinder Use Cooling Unit CL3 optional accessory Replacement of spare cylinder Recovery Procedure of R4...

Страница 16: ...ry machine and the hose of the discharge side Connect the hose of the discharge side to an evacuated cylinder to recover the refrigerant left in the recovery machine and the hose 4 Refrigerant Dischar...

Страница 17: ...of machine Slowly open the valve and discharge oil to other container The oil is collecting about 2L when the tank is full CLOSE the valve after discharge oil CLOSE the cap of oil discharge port afte...

Страница 18: ...e side OPEN Suction valve RECOVERY Switching valve CLOSE Discharge valve OPEN 5 At 0 2MPa 29psi Maintain 4 HOW TO USE Connect hoses as above after carry out Page11 2 Evacuation of the recovery machine...

Страница 19: ...0 3063 0 5616 0 1335 4 0 3349 0 6069 0 1519 2 0 3650 0 6545 0 1714 0 0 3996 0 7044 0 1920 2 0 4298 0 7569 0 2138 4 0 4647 0 8119 0 2369 6 0 5012 0 8695 0 2612 8 0 5395 0 9300 0 2868 10 0 5796 0 9930...

Страница 20: ...e inside of the cylinder is under this condition and this chart is useful for field operation When a cylinder is almost full with liquid and no vapor the pressure rises rapidly even with a slight incr...

Страница 21: ...ecular sieve No need to take off filter at the bottom in the Molecular sieve pack Dry filter is installed back side of machine Replacement period amount of refrigerant 150 200 kg Fill up all of new mo...

Страница 22: ...ing hose Turn ON the vacuum pump and OPEN the valve of oil discharge port CLOSE the oil discharge valve and turn OFF the vacuum pump after more than 1 hour of vacuum Take off connected hose between va...

Страница 23: ...liquid valve on the cylinder The pressure in the cylinder is high Cool the cylinder or use Cooling Unit Voltage drop Connect to a 220V power source Use appropriate extension code The recovery speed i...

Страница 24: ...oat switch Oil full fill bypass switch Full fill lamp Safety cable Low pressure switch Auto off Manual switch for operation Power switch Power cord Circuit breaker 15A Electrostatic filter system High...

Страница 25: ...Safety relief valve Check valve Purge Recovery Purge Molecular sieve Low pressure switch Compressor Condenser Low pressure gauge High pressure gauge Electrostatic lter system Oil separator Double pip...

Страница 26: ...25 ECOcycle Aurora...

Страница 27: ...26 ECOcycle Aurora...

Страница 28: ...Customer Memo Please ll in for your record in the future The information is helpful for inquiry and ordering parts Products Number Date Purchased Store Purchased the Unit Code No IM0345 A...

Отзывы: