ECOcycle Aurora Ⅱ
● Follow the following procedure when R410A or refrigerant at high pressure by heat is recovered.
See “Liquid/Vapor Recovery Procedure” for the standard operation.
● Cooling Unit (Code No. ES801) can lower the temperature of refrigerant at high pressure by
approximately 5 to 10℃ .
It improves the recovery rate.
See the instruction manual of Cooling Unit for detailed information.
● Use an evacuated spare cylinder.
■ Use Cooling Unit CL3 (optional accessory)
■ Replacement of spare cylinder
Recovery Procedure of R410A or When the Pressure of Refrigerant is High
HOW
TO
USE
◆ Noncondensable substance (air) may exist in the cylinder when the temperature of the
cylinder rises abnormally during recovery.
Remove the air or replace the cylinder.
◆ The method of removing air is refer to
Page
18
“
How to Purge Non condensable Gases
”
CAUTION