CONTROLLER INSTRUCTIONS FOR BLAST FREEZER
TL5-66E
Para
Metro
Operating mode
Range
Default
E1
Set Point
-50°C ~ +50°C
-20°C
E2
Differential
1°C ~ 25°C
3°C
E3
Minimum set point
-50°C ~ dl
-30°C
E11
Outputs activation delay at start up
0 ~ 30 (min.)
0 (min.)
E12
Interval between defrost cycles
0 ~ 120 (hr.)
4 (hr.)
E13
Length for defrost
0 ~ 120 (min.)
25 (min.)
E14
Defrost termination temperature
-40°C ~ +50°C
30°C
E17
Drain time
0 ~ 120 (min.)
2 (min.)
E18
Fan operating mode
0= runs with the compressor;
1= continuous mode
1
E19
Fan start temperature
-20°C ~ +50°C
15°C
E20
Fan delay after defrost
0 ~ 120 (min.)
2 (min.)
E21
Thermostat probe calibration
-12°C ~ +12°C
0°C
E22
Evaporator probe calibration
-12°C ~ +12°C
0°C
Содержание LCF-411-RS
Страница 1: ......
Страница 3: ...artisan 2 ...
Страница 8: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 7 ...
Страница 22: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 21 ...
Страница 26: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 25 ...
Страница 30: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 29 ...
Страница 41: ...artisan 40 Room Sensor black wire need to connect to PIN 1 for ground purpose WIRING DIAGRAM ...
Страница 42: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 41 ...
Страница 50: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 49 ...
Страница 54: ......