3.7 Functions and Indicators:
Function
Temp. Set
Temp.
Operation
Defrost
Set point (indoor)
Temp. Discrepency
Operation cycle
Defrost period
Probe calibration (indoor)
Compressor delay protection
Max. temp. Set point (indoor)
Min. temp. Set point (indoor)
3.8 Parameter table:
Function
Min.
Max.
Default
Set point (indoor)
Min. set point
Max. set point
5°C
Temp. Discrepency
1°C
10°C
4°C
Operation cycle
0 HR
99 HR
6 HR
Defrost period
0 MIN.
59 MIN.
30 MIN.
Probe calibration (indoor)
-8°C
7°C
0°C
Compressor delay protection
0 MIN.
15 MIN.
3 MIN.
Max. temp. Set point (indoor)
Set temp.
40°C
40°C
Min. temp. Set point (indoor)
-40°C
Set temp.
-40°C
3.9 Compressor:
3.9.1 When indoor temp
≥
(se temp discrepancy), compressor ON.
When indoor temp
≤
setpoint , compressor OFF.
3.9.2 Compressor delay starts period is 3 mins. (default)
3.9.3 Even compressor delay period is set as 0 min, when power replug in, there will still be 1 min
period delay for protection purpose.
3.9.4 When the indoor sensor is in failure, compressor operates and stopped cyclically for every
15 minutes.
(default setting, cannot be changed)
3.10 Defrost and fan management:
3.10.1 Defrost schedule: when time reaches (operation cycle – defrost period), defrost begin.
3.10.2 When defrost, by schedule or manual, defrost indicator blinking, compressor off and fan runs.
3.10.3 After defrost, fans run, compressor runs according to indoor temp, set point and its
discrepancy.
4. ERROR CODES
:
4.1 “EE”: Parameter memory failure (Re-plug in and operate as factory default)
4.2 “E1”: Indoor sensor failure (Check if the sensor is well connected or replace a new sensor)
Содержание LCF-411-RS
Страница 1: ......
Страница 3: ...artisan 2 ...
Страница 8: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 7 ...
Страница 22: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 21 ...
Страница 26: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 25 ...
Страница 30: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 29 ...
Страница 41: ...artisan 40 Room Sensor black wire need to connect to PIN 1 for ground purpose WIRING DIAGRAM ...
Страница 42: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 41 ...
Страница 50: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 49 ...
Страница 54: ......