Site Preparation
Centellis 2100 Shelf Release 3.0 Installation and Use (6806800T37D
)
76
The cooling system is able to supply greater than 54 CFM for the front blade and greater than
12 CFM for the RTM in each slot.
The actual cooling performance also depends on the slot population and the heatsink design
of the installed blades and should be validated based on the used system configuration.
The cooling system is designed to provide sufficient cooling with a single fan tray at work at
normal operating temperatures of up to 40 °C.
If you install the system into a closed frame, ensure that the air inlet and outlet are kept free.
2.6
Acoustic Noise Control
This system has a built-in noise control due to the fan speed control. If the system is installed in
an environment where the noise may be harmful to personnel being exposed to the noise
during extended time periods, additional protective measures should be considered.
The distance to other equipment must be sufficient to avoid an overheating of the system.
Содержание Centellis 2100 Shelf Release 3.0
Страница 1: ...Centellis 2100 Shelf Release 3 0 Installation and Use P N 6806800T37D August 2017...
Страница 8: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Contents 8 Contents Contents...
Страница 10: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 10 List of Tables...
Страница 12: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 12 List of Figures...
Страница 18: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D About this Manual 18 About this Manual...
Страница 32: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Safety Notes 32...
Страница 46: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Sicherheitshinweise 46...
Страница 66: ...Introduction Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 66...
Страница 112: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 112...
Страница 124: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 124...
Страница 130: ...Non Field Replaceable Units Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 130...
Страница 132: ...Cooling Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 132...
Страница 140: ...Power Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 140...
Страница 160: ...Network Management and System Access Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 160...
Страница 168: ...Configuration and Network Boot Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 168...
Страница 174: ...Redundancy Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 174...
Страница 186: ...Troubleshooting Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 186...
Страница 188: ...Related Documentation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 188...
Страница 189: ......