Appendices
74
7.8.
Appendix 8: Technical Specifications of AMU Unit
GENERAL INFORMATION
Net Weight
1170g (Inverter models 980g)
2.58lb (Inverter models 2.16lb)
Device Dimensions (W x H x L)
90x90x140 mm (3.54x3.54x5.67 in)
Mounting
Front Panel Mounting (indoor use)
Relay Contact Rating
30VDC, 2A, SELV
Current Connector Wire Gauge
Minimum: 30 AWG, Maximum: 12 AWG
Current Connector Screw Torque
Minimum: 0.5Nm (4.4 lb-in)
Maximum: 0.6Nm (5.3 lb-in)
Voltage Connector Wire Gauge
Minimum: 30 AWG, Maximum: 12 AWG
Voltage Connector Screw Torque
Minimum: 0.5Nm (4.4 lb-in)
Maximum: 0.6Nm (5.3 lb-in)
Power Supply Connector Wire Gauge
Minimum: 30 AWG, Maximum: 12 AWG
Power Supply Connector Screw Torque
Minimum: 0.5Nm (4.4 lb-in)
Maximum: 0.6Nm (5.3 lb-in)
Cables of Rear Connectors
Cables must be suitable for minimum 80°C
(176°F)
AMBIENT CONDITIONS
Operating Temperature
0-40°C (32-104 °F)
Humidity
90%, non-condensing
Pollution Degree
2
Altitude
2000 m (6562 ft)
IP Rating Front
40 (whole unit IP20)
INPUT SUPPLY VOLTAGE
The power supply voltage must be connected to the AMU unit
Via a UL listed fuse
15A
Over voltage category
CAT II
Voltage
100-240VAC (-15%+10%), 47-64Hz, 19VA,
200mA (Use UL listed 15A fuse with proper
voltage ratings)
120-300VDC, 19VA, 200mA (Use UL listed 15A
fuse with proper voltage ratings)
Содержание AMT Toolkit
Страница 2: ......
Страница 34: ...Equipment Faults Diagnosis and Reporting 32...
Страница 69: ...Appendices 67 7 6 Appendix 6 Flowcharts for AMU use 7 6 1 Running AMU Edit Settings and Check Motor...
Страница 70: ...Appendices 68 7 6 2 Running AMU Learn...
Страница 71: ...Appendices 69 7 6 3 Running AMU MONITOR IMPROVE UPDATE...
Страница 72: ...Appendices 70 7 6 4 Running AMU Alarm conditions...
Страница 73: ...Appendices 71...
Страница 74: ...Appendices 72...