![Artesis AMT Toolkit Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/artesis/amt-toolkit/amt-toolkit_user-manual_2977657025.webp)
AMU Use
23
Changing the value of this item from OFF to ON allows the detected phase ordering to be
altered by moving the cursor to the required position and scrolling UP/DOWN to select the
desired value. Set the phase ordering according to installation. Capital and small letters
refer to voltage and current, respectively. ‘+’ and ‘-‘ signs refer to direction of the CT
output.
It is also possible to fine-tune the algorithm by altering the value of the load threshold. A
higher value will tend to favor the unloaded solutions and vice versa. The load threshold
can be found under:
MENU: Edit Settings / Alarm Thresholds / Load threshold
3.4.5.
Running LEARN and IMPROVE
3.4.5.1.
LEARN
AMU should learn the motor under normal operating conditions. The LEARN period consists
of a preset number of data acquisition cycles and periods of data analysis. Once the preset
number of cycles has been reached, the acquired and preprocessed data are further
processed to produce a database consisting of a collection of data sets representing the
behavior of the motor system under the load conditions that the motor has met in practice.
It is therefore important to have the motor operating under its expected running conditions
during a learning period. In order to adequately cover the range of load conditions
experienced by a motor system, a sufficient number of acquisition cycles or iterations is
required.
NOTE
We recommend that you use somewhere between 15
to 30 iterations for LEARN and 7-10 iterations for
IMPROVE modes
Since additional learning can also be performed if needed during the testing phase, a larger
number of learning iterations is not generally required. The number of learning iterations
can be set from the menu path:
MENU: Edit Settings / Password / Run settings / Learn iterations.
3.4.5.2.
IMPROVE
Once the initial learning period is complete, the AMU unit will automatically try to improve
its estimation of the motor characteristics by updating the database obtained during the
learning mode. The database is updated with different load and line conditions in the
Содержание AMT Toolkit
Страница 2: ......
Страница 34: ...Equipment Faults Diagnosis and Reporting 32...
Страница 69: ...Appendices 67 7 6 Appendix 6 Flowcharts for AMU use 7 6 1 Running AMU Edit Settings and Check Motor...
Страница 70: ...Appendices 68 7 6 2 Running AMU Learn...
Страница 71: ...Appendices 69 7 6 3 Running AMU MONITOR IMPROVE UPDATE...
Страница 72: ...Appendices 70 7 6 4 Running AMU Alarm conditions...
Страница 73: ...Appendices 71...
Страница 74: ...Appendices 72...