background image

North America  •  Latin America  •  India  •  Europe / Middle East / Africa  •  China  •  Pacific Rim

armstrong

international.com

Designs, materials, weights and performance ratings are approximate and subject to change without notice.  Visit 

armstrong

international.com for up-to-date information.

30

  Note: 

Start-up process requires running heater in "Manual" mode, which overrides all automation and produces hot water 

continuously until heater is manually turned off. 

Commissioning

1. Turn on fuel.

 -Check for leaks in piping

 -Verify that gas pressure is between 2 and 6 psi

2.

 Press "MANUAL START."

Note:

 During initial start-up, low gas pressure fault light may come on. Once pressure is established, reset pressure switch

several attempts to start may be required until fuel enters burner.

3.

Verify the Burner Status on the HMI is in Normal Operation.

4.

Set your desired Set-point on the HMI.

5.

 Check temperature on gauge above transfer pump. Adjust incoming water pressure to obtain target output temperature if

necessary.

6.

Adjust Low and High Speed on Transfer Pump Screen so the VFD cycles between the two speeds.

 

Level should fluctuate

slowly between second and third float switches without seeing a tank full fault or pump turning off.

7.

Check exhaust piping for leaks.

8.

Insert combustion analyzer in port in exhaust stack and tune heater.

-  Oxygen reading must be 3.5–6%

Note: 

Low efficiency may be due to back pressure in exhaust piping if opening at cap is too small.

9.

Adjust for minimum carbon monoxide (CO)

10. Record regulator pressure on fuel train label.
11. Confirm operation of all safety features:

 -Low gas pressure switch
 -High gas pressure switch
 -Proof of closure switch
 -Low water pressure
 -High temperature
 -Flame failure (UV scanner)

12. Perform at least ten start cycles in "MANUAL" mode, allowing heater to reach high fire condition each time, to ensure

reliable starting and operation.

13. Run heater in "AUTOMATIC" mode to confirm proper operation in that mode.
14. Allow heater to sit and cool for several hours, then check for cold start.

Never leave heater unattended in "MANUAL" mode.

Содержание Flo-Direct 2.0 AFD-1000

Страница 1: ...Flo Direct 2 0 Complete Thermal Exchange Gas Fired Water Heater Installation Operation and Maintenance Manual Certified to U S patent 5 924 391 5 706 EN V7 0 Please read and save these instructions...

Страница 2: ...ge Heaters 14 Installing Small Heaters 16 Installing Exhaust Ducting 17 Installing Intake Air Ducting 18 Water Connections 19 Fuel Connection 20 Electrical Panels 21 Control Panel 21 Disconnect Panel...

Страница 3: ...product a ALWAYS select and wear appropriate personal protective equipment PPE before carrying out any physical work at the job site Appropriate PPE may include hard hats safety glasses gloves boots o...

Страница 4: ...u cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or gas supplier Note Operating with any safety device bypas...

Страница 5: ...mate and subject to change without notice Visit armstronginternational com for up to date information 5 The Flo Direct System Armstrong s Flo Direct water heaters Are designed for industrial applicati...

Страница 6: ...integral tank Other available options include Skid packaged heaters Performance matched components Ultra low NOx emissions Non standard fuels Storage tank heating element Peripheral components Digital...

Страница 7: ...ed Consult factory for additional information Materials of Construction Heater Component Material Canister 304 SS 10 ga AFD 9000 3 16 AFD 9000 Canister gasket WARCO white food grade buna rubber Flame...

Страница 8: ...nsions Weight btu hr kW 1 2 A B C D E in mm in mm in mm in mm in mm in mm in mm lb kg AFD 1000 1 25 1 25 95 2413 71 1803 39 991 24 610 8 203 825 375 1 000 000 292 AFD 1500 1 25 1 25 97 2464 73 1854 41...

Страница 9: ...com for up to date information 9 Orientation Lower Canister Upper Canister Top Plate Blower Blower Actuator Exhaust vent Burner Water pressure switch Water inlet High temp shut off switch Level switch...

Страница 10: ...rmance ratings are approximate and subject to change without notice Visit armstronginternational com for up to date information 10 Low gas pressure switch High gas pressure switch Proof of Closure POC...

Страница 11: ...teel Pump Stainless steel TEFC motor Globe valve Stainless steel Stand Carbon steel painted Model Maximum Flow Rate Inlet Connection Outlet Connection Flow Control Valve Pump Power GPM m3 hr in mm in...

Страница 12: ...1 2 Seismic code design None Wind load 0 mph kph Immersion heater port 4 NPT Sight glass port 1 NPT Insulation thickness 2 50 mm Component Material Structural layer Fiber reinforced plastic Structural...

Страница 13: ...ce Visit armstronginternational com for up to date information 13 Orientation Water inlet Screened vent Manway Outlet Outlet for immersion heater 4 NPT Lower sight glass mount 1 NPT optional tank leve...

Страница 14: ...ne of two scenarios may apply Small heaters approximately AFD 5000 and under when shipped with adequate height clearance in vehicle Top plate and upper canister will be attached and upright A fork lif...

Страница 15: ...milarly Attach as shown to keep plate approximately level Orient so union in fuel line can be connected Note Gas and fuel are used interchangeably in this document Note Top plates on largest heaters h...

Страница 16: ...osition over lower canister using lift lugs 4 Lower carefully until a few bolts can be inserted Tip Using several tapered pry bars or long screwdrivers will aid in aligning Note Control panels are typ...

Страница 17: ...1 4 per foot is recommended Condensate will drip from end of horizontal ducting Install where dripping will not be a nuisance or ice a hazard Connect exhaust ducting using either CPVC or single wall w...

Страница 18: ...equired Duct diameter must be at least as large as intake diameter on blower 15 diameter increase is recommended every 10 feet removed from heater Material can be CPVC Galvanized sheet metal Single wa...

Страница 19: ...r inlet piping Maximum recommended water velocity is 9 ft sec in inlet piping Suction hose between heater and transfer pump must be flexible to isolate vibration Line from transfer pump must be routed...

Страница 20: ...te information 20 Fuel Connection Note If codes require pressure test of fuel line close ball valve entering fuel train to heater Failure to do so may damage fuel regulator 1 Connect union in line bet...

Страница 21: ...ings are approximate and subject to change without notice Visit armstronginternational com for up to date information 21 Electrical Panels Control Panel Spark generator LMV3 Controller Hour meter Fuse...

Страница 22: ...and subject to change without notice Visit armstronginternational com for up to date information 22 Disconnect Panel Control transformer 3 phase to 120V Main fused disconnect Transfer Pump VFD Termin...

Страница 23: ...schematic provided with your heater for exact details Remove all cable ties bubble wrap and tape from wiring 4 Reconnect spark rod wire to spark rod in burner 5 Reconnect threaded fitting to burner f...

Страница 24: ...n wires and conduit for these connections may not be the correct length Rewire if necessary 1 Thread high temperature switch wiring into control panel 2 Reconnect conduit 3 Connect wires to correspond...

Страница 25: ...nals on terminal block 1 Install float switches from Armstrong in tank oriented as shown For float orientation consult wiring diagram supplied with unit Main Power Connection Note If facility does not...

Страница 26: ...ucing no undesirable gases Water is dispersed into upper canister and is broken into ever smaller droplets by passing down through palls Water is heated as combustion gases pass up through palls and o...

Страница 27: ...and then the Spark rod will de energize Phase 42 A Flame Signal must be detected by the end of this Phase The HMI displays the Flame Signal ranging from 0 100 A Flame Failure occurs when the Flame Si...

Страница 28: ...canister float switches High temperature switch Transfer pump Remote storage tank switches or field supplied relay coil in control panel Fuel line connected Adequately sized Adequately supported Press...

Страница 29: ...1 Confirm all checks in start up checklist above 2 Check all field connections in control panels 3 Identify any additional wiring in panels 4 Confirm rotation of blower and pump motors 5 Confirm what...

Страница 30: ...er pressure to obtain target output temperature if necessary 6 Adjust Low and High Speed on Transfer Pump Screen so the VFD cycles between the two speeds Level should fluctuate slowly between second a...

Страница 31: ...window Check spark rod connection and wire Check the Siemens controller With heater running close ball valve in fuel train just upstream of burner Burner should go out The Siemens controller should F...

Страница 32: ...ternational com for up to date information 32 High Temperature Switch Check 1 With heater on but not running unscrew cover on switch shown removed below 2 Compress spring to trip switch 3 Confirm that...

Страница 33: ...losed Open all upstream valves Defective pressure regulator spring Replace spring Defective pressure regulator Replace regulator High Gas Pressure Transitory alarm or to confirm fault Press red reset...

Страница 34: ...n Water Pressure Fault Flow control valve restricted Open flow control valve Shut off valve defective Repair or replace valve Restriction in inlet line Check filters and piping for obstructions Low sy...

Страница 35: ...D17513 Flange Gasket WARCO White 1 Spark Rod 47232 D19194 10 AFD 1000 D7564 2 3 AFD Spark Plug Wire Kit Includes Pug End Connector Spark Plug Boot 15 Spark Plug Wire and Terminal Ring D89821 AFD 1500...

Страница 36: ...nternational com for up to date information 36 Water Train Ref No Description Part No 1 Water Pressure Switch D16905 2 Pressure Gauge 0 110 psi D11554 Globe Valve Stainless Steel 3 1 D14596 1 1 2 D145...

Страница 37: ...on 37 Control Panel Ref No Description Part No 1 HMI Panelview Plus 7 9 Inch D106961 2 Emergency Stop Button D106011 3 Ignition Transformer D19185 4 Siemens LMV3 D115428 5 Modbus Module D115434 6 PLC...

Страница 38: ...use Cover Bus Indicating 15A D19614 5 30A D19762 17 1 2A D19615 60A D22629 20A D19616 100A D21900 25A D19617 6 Fuse Cover Bus Non Indicating D17413 30A D19618 Disconnect Handle 35A D19619 7 30A 60A D1...

Страница 39: ...FD 5000 to AFD 10000 FRS 720 6 D14807 Gas Regulator Spring 4 AFD 1000 to AFD 4000 Yellow 12 28 w c D11555 AFD 1000 to AFD 4000 Black 24 44 w c D14809 AFD 5000 to AFD 10000 Yellow 12 28 w c D19189 AFD...

Страница 40: ...5 100 D27358 5 Drain Plug 1 NPT 304 SS D16918 6 Plug NPT 304 SS D11018 7 Wiring Trough Drilled for Standpipe D17265 All 4 float switches swing downward Secured to float switches pumped only For pumpe...

Страница 41: ...ange without notice Visit armstronginternational com for up to date information 41 Storage Tank Ref No Description Part No 1 Bushing CPVC 4 x 1 2 NPT D18785 2 Float Switch Polypropylene D16907 3 Therm...

Страница 42: ...in detail on navigating though the HMI Depending on the options installed additional selections may be available The base selections are shown below NOTE BLUE denotes a user selection button or input...

Страница 43: ...grees Air Actr Pos Position of the air actuator in degrees Outlet Temp Outlet water temperature in degrees Fahrenheit Basin Level Level of the lower basin corresponding with the float switches in the...

Страница 44: ...ing in MANUAL mode When AUTO mode is selected the heater will switch to MODULATING mode To adjust your setpoint either degrees Fahrenheit in Modulating mode or Output position in Positioning mode You...

Страница 45: ...nu Screen This screen is used to navigate through the HMI Each button will take you to its corresponding screen These screens will be explained in detail below Main Screen This button takes you to the...

Страница 46: ...een displays all the PLC inputs outputs and VFD commands with an indicator denoting their status The indicator will be lit when the input output or command is on Pressing the BACK button will return y...

Страница 47: ...Trending Screen The Trending screen records a 10 minute trend of the heaters Setpoint Outlet Water Temp and Burner Position Pressing the BACK button will return you to the MENU screen 47...

Страница 48: ...emperature Fault Low Gas Pressure and High Gas Pressure require a manual reset of that component All active FSF will display an Error and Diagnostic Code at the bottom of the screen for more details o...

Страница 49: ...s the status of the transfer pump See example below The water level in the lower basin is at the second float switch The transfer pump is running at LOW speed To adjust the speeds of the VFD press eit...

Страница 50: ...to Armstrong i within 30 days of last day of the applicable warranty period or ii within 30 days of the date of the manifestation of the condition or occurrence giving rise to the claim whichever is...

Отзывы: