Serial Communications – continued
Modbus Communications
Applicable Flow Meter Models
Armstrong Vortex Flow Meters, Models AVF and AVI with Modbus communication protocol and firmware version
4.00.58 and above.
Overview
This document describes the preliminary implementation of the Modbus communication protocol for use in
monitoring common process variables in the Armstrong Vortex Flow Meter. The physical layer utilizes the half-duplex
RS-485 port, and the Modbus protocol.
Reference Documents
The following documents are available online from www.modbus.org.
Modbus Application Protocol Specification V1.1
Modbus Over Serial Line Specification & Implementation Guide V1.0
Modicon Modbus Protocol Reference Guide PI–MBUS–300 Rev. J
Wiring
An RS485 daisy chained network configuration as depicted below is recommended. Do not use a star, ring, or cluster
arrangement.
Pin Labeling (among devices)
“RS-485 –” = “A” = “TxD-/RxD-” = “Inverting pin”
“RS-485 +” = “B” = “TxD+/RxD+” = “Non-Inverting pin”
“RS-485 GND” = “GND” = “G” = “SC” = “Reference”
Figure 4-4.RS-485 Wiring (MODBUS)
Warning!
Place controls in manual mode when making configuration changes to the vortex meter.