Operating Instructions – continued
Alarms Menu
Example for Setting an Alarm
The following shows how to set Relay Alarm 1 to activate if the mass flow rate is greater than 100 lb/hr. You can check
the alarm configuration in the Run Mode by pressing the
keys until Alarm [1] appears. The lower line displays the
mass flow rate at which the alarm activates. Note: all outputs are disabled while using the Setup Menus.
First, set the desired units of measurement:
1. Use
keys to move to the Units Menu (see page 3-12).
2. Press
key until Mass Flow Unit appears. Press ENTER.
3. Press
key until lb appears in the numerator. Press
key to move the underline cursor to the denominator. Press
the
key until hr appears in the denominator. Press ENTER to select.
4. Press
key until Units Menu appears.
Second, set the analog output:
1. Use
keys to move to the Alarms Menu.
2. Press the
key until Relay Alarm 1 appears.
3. Press
key to access Measure selections. Press ENTER and use the
key to select Mass. Press ENTER.
4. Press
key to select the alarm Mode. Press ENTER and use
key to select HIGH Alarm. Press ENTER.
5. Press
key to select the value that must be exceeded before the alarm activates. Press ENTER and use
keys
to set 100 or 100.0. Press ENTER.
6. Press the EXIT key to save your changes. (Alarm changes are always permanently saved.)
(Up to three relay alarm outputs are available depending on meter configuration.)