Loop Power Flow Meter Wiring Connections
The NEMA 4X enclosure contains an integral wiring compartment with one dual strip terminal block (located in the
smaller end of the enclosure). Two 3/4-inch female NPT conduit entries are available for separate power and signal
wiring. For all hazardous area installations, only suitable certified cable glands, blanking plugs or thread adapters may
be used. The cable entry device shall be of a certified flame-proof type, suitable for the conditions of use and correctly
installed. The degree of protection of at least IP66 to EN 60529 is only achieved if certified cable entries are used that
are suitable for the application and correctly installed. Unused apertures shall be closed with suitable blanking elements.
If conduit seals are used, they must be installed within 18 inches (457 mm) of the enclosure.
Figure 2-14. Loop Power Wiring Terminals
Warning!
To avoid potential electric shock, follow National Elec-tric Code safety practices or your local code when
wiring this unit to a power source and to peripheral devices. Failure to do so could result in injury or
death. All wiring procedures must be per-formed with the power off.
Use a Class I or Class II power supply.
A power switch is not pro-vided with this meter, an approved switch meeting the power requirements
listed in Appendix A must be provided by the user. It must be easily accessible and marked as the discon-
nect for the flow meter.
Only the connectors sup-plied with the meter are to be used for connecting wiring.
If the equipment is used in a manner not specified the protection provided by the equipment may be
impaired.
Caution!
The DC wire insulation tem-perature rating must meet or exceed 85°C (185°F), max-imum operating voltage
300 VRMS.