14
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit
armstrong
international.com for up-to-date information.
Chapter 2 – Installation Overview
The Armstrong Vortex Flow Meter installations are simple and straightforward. Both the Series AVF In-Line and Series
AVI Insertion type flow meter installations are covered in this chapter. After reviewing the installation requirements given
below, see page 16 for Series AVF installation instructions. See page 19 for Series AVI installation instructions. Wiring
instructions begin on page 32.
Warning!
Consult the flow meter nameplate for specific flow meter approvals before any hazardous location installation.
Flow Meter Installation Requirements
Before installing the flow meter, verify the installation site allows for these considerations:
1. Line pressure and temperature will not exceed the flow meter rating.
2. The location meets the required minimum number of pipe diameters upstream and downstream of the sensor head as
illustrated in Figure 2-1.
3. Safe and convenient access with adequate overhead clearance for maintenance purposes.
4. Verify that the cable entry into the instrument meets the specific standard required for hazardous area installa-tions.
The cable entry device shall be of a certified flameproof type, suitable for the conditions of use and correctly installed.
The degree of protection of at least IP66 to EN 60529 is only achieved if certified cable en-tries are used that are
suitable for the application and correctly installed. Unused apertures shall be closed with suitable blanking elements.
5. For remote installations, verify the supplied cable length is sufficient to connect the flow meter sensor to the re-mote
electronics.
Also, before installation check your flow system for anomalies such as:
• leaks
• valves or restrictions in the flow path that could create disturb-ances in the flow profile that might cause unexpected
flow rate indications