Switches 8 and 9 - Cooling Mode Blower Speed-
The unit is shipped from the factory with the DIP switches
positioned for high speed (4) indoor blower motor operation
during the cooling mode. The table below provides the
cooling mode blower speeds that will result from different
switch settings.
Switches 10 and 11 - Cooling Mode Blower Speed
Adjustment -
The unit is shipped from the factory with
the DIP switches positioned for NORMAL (no) adjustment.
The DIP switches may be positioned to adjust the blower
speed by +10% or -10% to better suit the application. Table
18 provides blower speed adjustments that will result from
different switch settings. Refer to air flow tables for values.
With switches 10 and 11 set to ON, motor will bypass
ramping profiles and all delays and will immediately run at
selected COOLING speed upon a call for cool. LED will
continue to operate as normal. This mode is used to check
motor operation.
Switches 12 and 13 - Cooling Mode Blower Speed
Ramping -
Blower speed ramping may be used to enhance
dehumidification performance. The switches are factory set
at option A which has the greatest effect on blower motor
performance. Table 19 provides the cooling mode blower
speed ramping options that will result from different switch
settings. The cooling mode blower speed ramping options
are detailed below.
NOTE:
The OFF portion of the selected ramp profile only
applies during heat pump operation in dual fuel applications.
Ramping Option “A” (Factory Selection)
•
Motor runs at 50% for 30 seconds.
•
Motor then runs at 82% for approximately 7-1/2 min-
utes.
•
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
•
Once demand is met, motor runs at 50% for 30 sec-
onds then ramps down to stop.
Ramping Option “B”
•
Motor runs at 82% for approximately 7-1/2 minutes.
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
•
Once demand is met, motor ramps down to stop.
Ramping Option “C”
•
Motor runs at 100% until demand is satisfied.
•
Once demand is met, motor runs at 100% for 45 sec-
onds then ramps down to stop.
Ramping Option “D”
•
Motor runs at 100% until demand is satisfied.
•
Once demand is met, motor ramps down to stop.
Cooling Mode Blower Speed Adjustment
Table 18
Cooling Mode Blower Speed Ramping
Table 19
Cooling Mode Blower Speeds
Table 17
Содержание A97DSMV
Страница 3: ...507029 03 Page 3 of 68 Issue 1622 A97DSMV Exploded View Figure 1...
Страница 13: ...507029 03 Page 13 of 68 Issue 1622 OUTDOOR TERMINATION KITS USAGE Table 3...
Страница 17: ...507029 03 Page 17 of 68 Issue 1622 Table 5 Maximum Allowable Intake or Exhaust Vent Length feet...
Страница 24: ...507029 03 Page 24 of 68 Issue 1622 Figure 29...
Страница 27: ...507029 03 Page 27 of 68 Issue 1622 Figure 36 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC...
Страница 33: ...507029 03 Page 33 of 68 Issue 1622 Figure 43 Typical A97DSMV Wiring Diagram...
Страница 34: ...507029 03 Page 34 of 68 Issue 1622 Figure 45...
Страница 35: ...507029 03 Page 35 of 68 Issue 1622 Figure 46...
Страница 36: ...507029 03 Page 36 of 68 Issue 1622 Figure 47 Integrated Control...
Страница 40: ...507029 03 Page 40 of 68 Issue 1622 Low Voltage Field Wiring Table 14 Single Stage 2 Stage...
Страница 44: ...507029 03 Page 44 of 68 Issue 1622 BLOWER DATA...
Страница 46: ...507029 03 Page 46 of 68 Issue 1622 Table 22 COOLING OPERATING SEQUENCE A97DSMV and Single Stage Outdoor Unit...
Страница 47: ...507029 03 Page 47 of 68 Issue 1622 Table 23 COOLING OPERATING SEQUENCE A97DSMV and Two Stage Outdoor Unit...
Страница 51: ...507029 03 Page 51 of 68 Issue 1622 Figure 50 Operation Signal Delta P Measurement Manifold Pressure Measurement...
Страница 57: ...507029 03 Page 57 of 68 Issue 1622...
Страница 58: ...507029 03 Page 58 of 68 Issue 1622...
Страница 59: ...507029 03 Page 59 of 68 Issue 1622...
Страница 60: ...507029 03 Page 60 of 68 Issue 1622 Configuring Unit Size Codes...
Страница 61: ...507029 03 Page 61 of 68 Issue 1622 Troubleshooting Heating Sequence of Operation...
Страница 62: ...507029 03 Page 62 of 68 Issue 1622 Troubleshooting Heating Sequence of Operation continued...
Страница 63: ...507029 03 Page 63 of 68 Issue 1622 Troubleshooting Heating Sequence of Operation continued...
Страница 64: ...507029 03 Page 64 of 68 Issue 1622 Troubleshooting Heating Sequence of Operation continued...
Страница 65: ...507029 03 Page 65 of 68 Issue 1622 Troubleshooting Cooling Sequence of Operation...
Страница 66: ...507029 03 Page 66 of 68 Issue 1622 Troubleshooting Continuous Fan Sequence of Operation...