MAGX2 User Guide
22
V2.14 1-2-2017
User Settings > Current Loop > Calibration
This function serves to modify current loop output signal.
Possible range:
4
– 20 mA
;
0.5000
– 1.5000
Back with no change
Selection of digit position
Value setting
Confirmation of setup and saving to memory
Calibration
point 1,2
Setup of calibration point 1, 2. First point must be less
than second point.
Calibration
constant 1,2
Setup of calibration constant for first and for second
calibration point.
Formula for calibration constant calculation:
Expected value: 6 mA, Measured value: 6.1 mA
Calibration point one: 6 mA
Calibration constant one = = 0.9836
Expected value: 18 mA, Measured value: 17.9 mA
Calibration point two: 18mA
Calibration constant two = = 1.0056
3.5.13. User Settings > Pulse Output
Back with no change
Item selection
Enter this part of the menu
User Settings > Pulse Output > RE1 & RE2
Back with no change
Item selection
Enter this part of the menu
User Settings > Pulse Output > RE1 & RE2 > RE1 (RE2) function
This function serves to select which signal the output should be
giving. The relays are independent to each other.
Back with no change
Item selection
Selection identification
Confirmation of setup and saving to memory
OFF
Output:
OFF
, fixed status signal
Fixed
Output:
ON
, fixed status signal
Flow+
Output:
ON
, for any positive flow
Flow
–
Output:
ON
, for any negative flow
Error
Output:
ON
, for any error identified by the device
The signal can be cancelled by pressing any
push button on the flowmeter.
Air Detect
Output:
ON
, during air detection (empty pipe)
Comparator
On In
Output:
ON
, if the actual flow-rate is within the given
range (can be set under Comparator Flow)
6
6.1
18
17.9
Содержание MAGX2
Страница 1: ......
Страница 4: ...MAGX2 User Guide 3 V2 14 1 2 2017 ...
Страница 55: ...MAGX2 User Guide 54 V2 14 1 2 2017 8 Flowmeter Dimensions 8 1 IP67 Transmitter Compact version Remote version ...
Страница 57: ...MAGX2 User Guide 56 V2 14 1 2 2017 8 2 IP68 Transmitter Compact version Remote version ...
Страница 63: ...MAGX2 User Guide 62 V2 14 1 2 2017 ...