background image

 

Planning and installation

Planning and installation shall be carried out in a professional manner, attention being 
paid to general and local rules and regulations. Operating pressure is max. 1,5 bar. 
Before taking the installation into service, and always at the beginning of the heating 
season, the following checks shall be carried out:
•  that the heating system is fi lled and bled
•  that the circulation pump is working
•  that the system valves are open
•  that the automatic control and safety devices are in working order
•  that the chimney has the necessary draught and that the fresh air ventilation 

is open.

 

Safety valve

If a closed expansion vessel has been installed in the radiator system, the safety valve 
must be checked 4 times a year. Activate the valve by pressing or turning the control 
button and check that water escapes from the overfl ow pipe connecting the valve to 
the drain.

 

Boiler temperature

Th

  e higher the temperature on the boiler the greater the capacity to generate hot water 

for the taps from the separate hot water tank (recommended setting = 80°C). Th

 e 

temperature on the boiler must never be set so low that condensation forms in the 

boiler.

Before you begin heating, the heating system must be fi lled with water.
To fi ll the system, do as follows:
1.  Open all shut-off  valves, including the shunt valve. 

Th

  e pump must be switched off .   

2.  Fill the boiler and the radiator system with water. 

Bleed the system at the radiators.  

3.  Once the system is fi lled completely, the circulation pump can be started and 

heating can begin.  

4.  When the boiler water has reached its pre-set operating temperature, the pump 

should be stopped and the system bled at the radiators once again. Th

  is should be 

repeated several times.  

Remember that much air is enclosed in tap water. Th

  e enclosed air volume may reach 

as much as 10%, which explains why bleeding takes time – especially where there are 
large water volumes. A closed system shall be fi lled until the pressure gauge indicates 
the correct system pressure, i.e. the distance from the pressure gauge to the highest ra-
diator in meter times 0,1 which gives the system pressure in bar. Adjust the red needle 
of the pressure gauge to the same value as the big needle.

ARITERM SWEDEN AB

 

  

Installation, Operation and Maintenance - 2007.10.26- 7/12

 WATER PIPING

 FILLING OF WATER

Содержание Bionet 12

Страница 1: ...INSTALLATION OPERATION AND MAINTENANCE Bionet 12 ...

Страница 2: ...ding authorities Sweeping According to the fire protection laws a chimney shall be swept regularly This is done by the local chimneysweep Sweeping of the boiler shall be carried out in such a manner that good operating economy is achieved see under Maintenance Prepare to chimney sweeping by turning off the boiler at least one hour before cleaning to minimize the amount of glowing ash Warning Make su...

Страница 3: ...ing pellets 12 kW Dimension Dimensions width x depth x height Weight Water contents 436 x 581 x 1340 mm 125 kg 50 l Design values Design pressure Design temperature Recommended draught 0 5 1 5 bar max 100 o C 5 20 Pa Connection Expansion Drain Flue pipe connection DN 25 male DN 15 female Ø 102 mm ARITERM SWEDEN AB Installation Operation and Maintenance 2007 10 26 3 12 DIMENSIONS ITEMS INCLUDED IN ...

Страница 4: ... pump or solar energy powered systems The 12 kW output is sufficient for most detached house heating systems For domestic hot water needs the Bionet can beneficially be connected to a separate hot water storage system pre prepared for solar energy Ariterm Bionet s compact shape permits instal lation even in tight spaces Shunt connection The water from the boiler tank and the return water are mixed in...

Страница 5: ...örvärmning 1 2 1 3 7 8 4 6 5 13 10 11 9 14 11 12 vv kv kv 7b Hot tap water Bionet does not have an in built function for hot water through the taps Hot water is produced for example through a separate solar heating tank or equivalent please refer to relevant drawing Note Before starting any work on the boiler please switch the mains power to the boiler off to ensure that no electrical current runs ...

Страница 6: ...notied for inspection of the flue CAUTION The boiler has low flue gas temperatures which under certain conditions might lead to condensation of flue gases 30 Mortar Flue pipe 30 mm incom bustible insulation Water piping shall be carried out in accordance with current local and national hot water and building regulations Safety equipment shall be installed in accordance with regulations in force If...

Страница 7: ...d setting 80 C The temperature on the boiler must never be set so low that condensation forms in the boiler Before you begin heating the heating system must be filled with water To fill the system do as follows 1 Open all shut off valves including the shunt valve The pump must be switched off 2 Fill the boiler and the radiator system with water Bleed the system at the radiators 3 Once the system is fil...

Страница 8: ...d loosen the hose and electric connections Pull out the burner and remove the ash by brushing the walls of the combustion chamber Empty the ash box The burner Carry out checks and measures when needed or in connection with boiler cleaning When new pellet fuel is used always check the burn pot for sintered ashes crust of ash or gravel and stone like particles Such particles must be removed from the...

Страница 9: ...re penetration Take special care to avoid damp penetration through the walls and floor It is also important that pellets are not exposed to direct contact with water in the form of rain or condensation Pellets do not however absorb moisture from surrounding moist air and can therefore be stored outdoors as long as they are under cover The fuel store should be planned according to your estimated con...

Страница 10: ...n high low and min modes be tested manually Returning to normal position Press minus key once ATTENTION In this function the burner won t stop when the boiler water reaches desired temperature boiling risk Flue gas temp High CO Retailer Installer Installed by Inst date O2 CO2 Efficiency Draught mm Fan Effect Flue gas temp Low CO O2 CO2 Efficiency Draught mm Fan Effect Flue gas temp Min CO O2 CO2 E...

Страница 11: ...ARITERM SWEDEN AB Installation Operation and Maintenance 2007 10 26 11 12 NOTES DECLARATION OF CONFORMITY ...

Страница 12: ...ARITERM SWEDEN AB Flottiljvägen 15 39241 Kalmar www ariterm se 0771 442850 ...

Отзывы: