EFORE SWITCHING ON THE POWER
1.
Detectors (or key switches) can be connected in two ways:
Conventional:
One zone each is required for both tamper and the alarm. Both zones should be
closed with an end-loop resistor (4.7 kOhm). Program the ‘zones’ menu as ‘Alarm’
Figure 1. Separate alarm and tamper connection
Dual loop:
The alarm and tamper are placed together in one zone. The zone has two end-loop
resistors (4.7 kOhm) to differentiate between alarm and tamper. Figure 2 shows how
they are connected. Program the ‘zones’ menu as ‘Dual’.
Figure 2. Joint Connecting the alarm & tamper
This connection method gives the following input values:
The zone is
Resistance
Panel zone
voltages
Remote zone
voltages
Reaction
on standby
3k5 - 6k2
2.1 - 2.8 V
4.7 - 6.8 V
none
triggered
6k6 - 11k7
2.9 - 3.6 V
6.9 - 8.6 V
alarm
open
> 12k7
> 3.7 V
> 8.7 V
tamper
short-circuited
< 2k9
< 1.9 V
< 4.6 V
tamper
Table 1. Operation of the inputs
Содержание Advisor CD15012
Страница 1: ...142938999 1 Installation Manual Software from Version V6 0 ADVISOR CD 7212 CD95 15012 ...
Страница 4: ...Page 4 Installation manual for CD72 95 15012 ...
Страница 34: ...Page 34 Installation manual for the CD72 95 15012 ...
Страница 35: ...Installation manual for the CD72 95 15012 Page 35 ...
Страница 36: ...Page 36 Installation manual for the CD72 95 15012 ...
Страница 38: ...Page 38 Installation manual for the CD72 95 15012 ...
Страница 39: ...Installation manual for the CD72 95 15012 Page 39 ...
Страница 40: ...Page 40 Installation manual for the CD72 95 15012 ...