26
1X-X3 Operation Manual
Disabling other extinguishing devices
The devices listed in Table 3 can also be disabled at the operator user level.
To disable any of these devices, press the General Disable button for more than
3 seconds, press the 1 and 3 buttons (the Up and Down buttons) to select the
option to be disabled (the corresponding LED flashes), and then press Enter to
confirm the disablement.
The disablement is indicated by:
• A steady General Disable LED
• A steady disabled LED for the corresponding device
To enable a disabled option, press the General Disable button for more than 3
seconds, press the 1 and 3 buttons to select the option to be enabled, and then
press Enter.
Table 3: Additional device disablement options
Device
LED used
All installed expansion boards [1]
Expansion I/O Fault/Disabled
Actuator
Released yellow
Door monitor [2]
Door Fault/Disabled
Pressure switch monitoring
Low Pressure yellow
Extinguishing agent flow monitoring
Extinguishing Agent Flow yellow
Extinguishing release optical warning panel/sign Optical Panel On yellow
Start extinguishing manual call points
MCP Start yellow
Hold extinguishing manual call points
MCP Hold yellow
Abort extinguishing manual call points
MCP Abort yellow
[1] Expansion boards cannot be disabled individually.
[2] If a safety door monitoring is not used, make sure that your installer has not configured this
option or disable it to avoid preventing the extinguishing event.
Testing other extinguishing devices
The devices listed in Table 4 and Table 5 can also be tested at the operator user
level.
To test any of these devices, press the General Test button for more than 3
seconds, press the 1 and 3 buttons (the Up and Down buttons) to select the
option to be tested (the corresponding LED flashes), and then press Enter to
confirm the test condition.
The test condition is indicated by:
• A steady General Test LED
• A steady test LED for the corresponding device
To exit from a test condition, press the General Test button for more than 3
seconds, press the 1 and 3 buttons to select the option, and then press Enter.