Disabling or enabling a fire sounders delay
To disable a configured (and enabled) fire sounders delay, press the Fire
Sounders Delay button. To enable the delay, press the button again.
If an alarm is reported in a zone linked to the extinguishing event, any configured
delay will be ignored and fire sounders will be activated immediately.
Testing sounders
To test the sounders, press the General Test button, and then press the Fire
Sounders Delay button.
Sounders can only be tested when the control panel is in standby state.
The test is indicated as follows:
• A steady General Test LED
• A steady yellow LED for the Fire Sounders Delay button
• The audible sounder test signal (3 seconds on, 5 seconds off) for the duration
of the test, without any configured delay
To end the test, press the General Test button, and then press the corresponding
sounder Fire Sounders Delay button again.
If there is an extinguishing preactivation, activation, release, or fire alarm event
during the test, the control panel exits the test and responds to the alarm event
as configured.
Disabling or enabling fire routing
To disable fire routing, press the General Disable button, and then press the Fire
Routing Start button.
The disablement is indicated as follows:
• A steady General Disable LED
• A steady yellow Fire Routing On LED
To enable fire routing, press the General Disable button, and then press the Fire
Routing On button again.
Note:
Disabled fire routing does not operate or indicate a fault if there is a fire
alarm.
Disabling or enabling a fire routing delay
To disable a configured (and enabled) fire routing delay, press the Fire Routing
Delay button. To enable the delay, press the button again.