1X-X3 Operation Manual
11
Control panel status indications
This section includes a summary of the default control panel status indications.
Standby
Standby, or normal status, is indicated as follows:
• A steady Supply LED
• A steady Fire Sounders Delay LED (if a delay is enabled)
• A steady Fire Routing Delay LED (Figure 1, item 30) (if a delay is enabled)
There is no audible indication.
Fire alarm (fire-only)
The fire alarm state applies to zones that are not linked to the extinguishing area,
and act as fire-only zones.
A fire alarm in a detection zone that is not linked to the extinguishing area is
indicated as follows:
• General Fire Alarm LEDs: Flashing if the alarm was activated by a detector.
Steady if the alarm was activated by a manual call point.
• Zone LED: Flashing if the alarm was activated by a detector. Steady if the
alarm was activated by a manual call point. Shows which zones are in alarm.
• Fire Sounders Delay LED: Flashing while a delay countdown is in progress.
Steady if a delay is enabled.
• Fire Sounders Start/Stop LED: Steady if fire sounders are active (or will be
activated shortly). Flashing when a delay countdown is in progress. Fire
sounders are activated when the configured delay elapses or when the delay
is cancelled. Off when the fire sounders are off (or will be deactivated shortly).
• Fire Routing Delay and Fire Routing On LEDs: If the system has been
configured to use fire routing, the indicators display accordingly.
After the first detector alarm in the system, the Fire Routing Delay LED
flashes to indicate that a configured delay countdown is in progress. When
the delay expires (or is cancelled), fire routing is activated, and the red Fire
Routing LED flashes.
If the system detects an MCP alarm, the Fire Routing Delay LED turns on
steady if a delay is enabled, the fire routing is activated immediately, and the
Fire Routing LED flashes.
Consult your system installer or maintenance contractor to determine whether
your system has a zone configured for fire-only operation.
The control panel buzzer sounds continuously.