Appendix A: Configuration presets
1X-X3 Installation Manual
69
The configured actuator delay is applied when the MCP Start is activated.
Table 30: Presets and zone characteristics
Preset
Zone description
Zone detection
01
Passive
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
02
Passive, CleanMe enabled Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
Basic evacuation mode
Fire sounders can be manually activated at the operator user level in this
operating mode (a fire alarm is not required).
The actuator is activated immediately when the MCP Start is activated.
Table 31: Presets and zone characteristics
Preset
Zone description
Zone detection
04
Passive
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
05
Passive, CleanMe enabled
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
Expansion board functions
Table 32: Expansion board functions
Preset ON status
Output Delay
01
Z1 alarm
1
Yes
Z2 alarm
2
Yes
Z3 alarm
3
Yes
05
Z1 alarm
1
Yes
2
Yes
Z2 alarm
3
Yes
4
Yes
06
Z3 alarm
1
Yes
2
Yes
22
Z1 and Z2 alarm
1
Yes
2
Yes
Z2 and Z3 alarm
3
Yes
4
Yes
Содержание 1X-X3
Страница 1: ...1X X3 Installation Manual P N 501 419003 1 11 REV 01 10 ISS 11NOV13 ...
Страница 6: ...iv 1X X3 Installation Manual ...
Страница 26: ...Chapter 2 Installation 20 1X X3 Installation Manual ...
Страница 64: ...Chapter 4 Maintenance 58 1X X3 Installation Manual ...
Страница 71: ...Chapter 5 Technical specifications 1X X3 Installation Manual 65 Figure 17 Control panel cabinet without cover ...
Страница 72: ...Chapter 5 Technical specifications 66 1X X3 Installation Manual Figure 18 Control panel cabinet with cover ...
Страница 82: ...Appendix B Regulatory information 76 1X X3 Installation Manual ...
Страница 86: ...Index 80 1X X3 Installation Manual ...
Страница 87: ......
Страница 88: ......