Quick Start Guide: 7300 Series Modular Data Center Switches
Cabling the AC Power Supply
Chapter 4: Powering the Modular Switch
4.1
Cabling the AC Power Supply
4.1.1
Grounding the Switch
After mounting the switch into the rack, connect the switch to the data center ground.
displays the location of the grounding pads located on the front panel (left illustration) and rear panel
(right illustration). After the switch is grounded, ESD wrist straps can be grounded by connecting them
to one of the grounding pads.
Important!
Grounding wires and grounding lugs (M4 x 0.7) are not supplied. Wire size should meet local and
national installation requirements. Commercially available 6 AWG wire is recommended for
installations in the U.S.
Figure 4-1: Grounding Pad and ESD Grounding Pad Sockets
4.1.2
Connecting Power Cables to an AC Power Supply
displays an AC power supply module, including the power input socket.
Figure 4-2: Power Input Sockets
The power supplies require power cables that comply with IEC-320 and have a C19 plug. The
accessory kit provides 14 AWG, C19 to C20 power cables.
To insert a power cable:
Step 1
Pull the retaining clip back on each power input socket.
Содержание DCS-7304
Страница 10: ...6 Quick Start Guide 7300 Series Modular Data Center Switches Specifications Chapter 1 Overview ...
Страница 48: ...44 Quick Start Guide 7300 Series Modular Data Center Switches Two Post Rack Mount Parts Appendix C Parts List ...
Страница 52: ...48 Quick Start Guide 7300 Series Modular Data Center Switches Appendix D Front Panels ...
Страница 55: ...Appendix E Rear Panels Quick Start Guide 7300 Series Modular Data Center Switches 51 DCS 7316 Rear Panel ...
Страница 56: ...52 Quick Start Guide 7300 Series Modular Data Center Switches Appendix E Rear Panels ...
Страница 58: ...54 Quick Start Guide 7300 Series Modular Data Center Switches Appendix F Line Cards DCS 7320X 32C LC ...