- Translated original instructions -
Operating and installation instructions
Thrust actuator ARI-PREMIO
®
-Plus 2G
- Single conductors with safety extra-low voltage (< 50 V) must be laid/fastened into the actuator
separately from single conductors with low voltage (50 - 1000 V) or they must be separated by
reinforced insulation.
- Single conductors must be bundled per connector strip directly behind the terminal with a cable tie,
so that a loosened cable cannot get to other parts/circuits.
Fig. 11: Single conductors with cable ties
- For the system side mains fuse we recommend:
Up to 15 kN
25 kN
24 V AC/DC
6 A
8 A
100 - 240 V AC
2 A
3~400 V
2 A
cable ties