Operating and installation instructions
Thrust actuator ARI-PREMIO
®
-Plus 2G
4.5 Interface description
4.5.1 Control - Run commands
Control
Description - Technical data
Required options
OPEN-STOP-CLOSE
(3-point)
2 Binary input
- 12 V AC/DC to 250 V AC/DC
-
Modbus-RTU
- Protocol: Modbus, Modbus-integer
- Baud rate: 4200 ... 115200 (default)
- Device address: 1 ... 247
- Max. number of participants: 247
- Anybus-Interface
Profibus-DP
- Device address: 0 ... 125
-
dTRON316
with Profibus card (dTRON options)
Set point control for
position controller
4 - 20 mA DC
- Burden 125 Ohm
- Resolution: Dead band ±0,5 %
- Electrically isolated
- Optional ±0,25 %
0 - 10 V DC
- Burden 500 kOhm
- Resolution: Dead band ±0,5 %
- Electrically isolated
-
Modbus-RTU
- Protocol: Modbus, Modbus-integer
- Baud rate: 9600, 19200, 38400
- Device address: 0 ... 255
- Max. number of participants: 32
- Anybus-Interface
Profibus-DP
- Device address: 0 ... 125
- Anybus-Interface
Set point control for
PID-Process controller
(Option dTRON 316)
4 - 20 mA DC
- Burden 75 Ohm
- Resolution 10 Bit
-
dTRON316
with analogue output card and
analogue input card (dTRON options)
0-10 V DC
- Burden > 100 kOhm
- Resolution 10 Bit
-
dTRON316
with analogue output card and
analogue input card (dTRON options)