7.7
Start Delay
Select START DELAY from the ADJUSTMENTS submenu. Adjust the start delay to the desired
setting. The actual start of the unit is delayed further by the soft start control or “walk in” that is en-
gaged at the end of the delay sequence selected.
7.8
High Output Voltage Shutdown
Select O/P HV LEVEL ADJ from the ADJUSTMENTS submenu . Adjust the level to the desired
setting. Wait to confirm the setting until after set up of the low output voltage alarm level.
The High Output Voltage Shutdown level should not be adjusted when the Module is in current limit.
7.9
Low Output Voltage Alarm
Select LO O/P (VOLTS) ALARM from the ADJUSTMENTS submenu . Adjust the level to the de-
sired setting. Confirm the low output voltage level and the high output voltage shutdown level using
MANUAL
or AUTO TEST.
7.10
High Output Voltage Alarm (not on all models)
Select HI O/P ALARM from the ADJUSTMENTS submenu . Adjust the level to the desired setting
using the up/down arrow keys. Confirm the low output voltage level, the high voltage level, and the
high output voltage shutdown level using MANUAL or AUTO TEST.
7.11
Protected Adjustments
The unit is equipped with the following adjustments which require a password to access:
Current limit alarm disable/enable
Equalize Time-out
Display Calibration
Local access alarm disable/enable
Security code set
The factory default password is set to 123. Anytime a menu item that requires a password is se-
lected, the message SECURITY = —- will show and the first dash will be replaced with a zero as
the first digit. Use the Up and Down keys to select the first digit and press the Enter/Select key.
Do the same for the second and third digits. The display will wrap around from 9 to 0 (or 0 to 9)
when the Up (or Down) key is pressed.
7.11.1
Current Limit Alarm
When disabled a current limit condition will not cause the minor alarm to be activated. The control
toggles between an enabled and disabled condition. Use the Enter/Select key to toggle the condi-
tion.
7.11.2
Equalize Time-out
A maximum equalize time is set by this control. If the equalize mode is selected locally the maxi-
mum time the unit will remain in the mode is up to 30 hours. This is a cautionary control to prevent
accidental over charge of the batteries. The control is overridden by the remote equalize signal. Us-
ing the up and down adjustment keys alters the time from 1 to 30 hours.
ARGUS TECHNOLOGIES
010-030-C0 Rev E Page 33 of 42