Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or 

lines shall be as short as possible to minimise the amount of refrigerant contained in them. 

Cylinders shall be kept upright. 

Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. 

Label the system when charging is complete (if not already). 

Extreme care shall be taken not to overfill the refrigeration system. 

Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. 
The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be 
carried out prior to leaving the site.  
 
Decommissioning  
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its 
detail. lt is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil 
and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. lt is essential 
that electrical power is available before the task is commenced. 
a.  

Become familiar with the equipment and its operation. 

b.  

Isolate system electrically. 

c.  

Before attempting the procedure, ensure that: 

• 

mechanical handling equipment is available, if required, for handling refrigerant cylinders; 

• 

all personal protective equipment is available and being used correctly; 

• 

the recovery process is supervised at all times by a competent person; 

• 

recovery equipment and cylinders conform to the appropriate standards. 

d.  

Pump down refrigerant system, if possible. 

e.  

lf a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the 

system. 
f.  

Make sure that cylinder is situated on the scales before recovery takes place. 

g.  

Start the recovery machine and operate in accordance with manufacturer's instructions 

h.  

Do not overfill cylinders. (No more than 80 % volume liquid charge).  

i.  

Do not exceed the maximum working pressure of the cylinder, even temporarily. 

j. 

When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the 

equipment are removed from site promptly and all isolation valves on the equipment are closed off.  
k. Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked. 
 
Labelling  
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be 
dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment 
stating the equipment contains flammable refrigerant. 
 
Recovery  
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that 
all refrigerants are removed safely.  
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. 
Ensure that the correct number of cylinders for holding the total system charge are available. AII cylinders to be used are 
designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of 
refrigerant). Cylinders shall be complete with pressure-relief valve and assodated shut-off valves in good working order. 
Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.  
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at 
hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, flammable 
refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be 
complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is 
in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to 
prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.  
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant 
waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. 
lf compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to 
make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out 
prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to 
accelerate this process. When oil is drained from a system, it shall be carried out safely.

 

 
 
 
 
 
 
 

                                                                              

 

 

www.argoclima.com 

Содержание LILIUM ART 11

Страница 1: ...UCTIONS Read the instructions carefully before operating or servicing the dehumidifier Observe all the safety instructions failure to observe the instructions may lead to accidents and or damage Keep these instructions in a safe place for future reference EN ...

Страница 2: ...n different ways other than those recommended by the manufacturer Should repair be necessary contact your nearest authorized Service Centre Any repairs carried out by unqualified personnel may be dangerous The appliance has to be stored in a room that doesn t have any continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not p...

Страница 3: ...they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision Make sure the plug is inserted fully Do not use multiple adapters Do not touch the plug with wet hands Make sure the plug is clean Children aged be...

Страница 4: ...s water leaks can cause it to malfunction or cause excessive vibration and running noise The dehumidifier must be positioned at least 50 cm away from the wall or other obstacles so that the heat can dissipate correctly Close all open windows to maximise dehumidification efficiency Do not insert objects or sharp instruments into the air outlet grille Do not cover the air intake and outlet grilles i...

Страница 5: ...ng so can cause leaks and malfunction In the event of interference with other electrical appliances place the two products at a minimum distance of 70cm DESCRIPTION OF PARTS 1 Control panel 8 Side panel 2 Colored LED with humidity sensor 9 Air inlet and air filter 3 Front panel 10 Water tank 4 Casters 11 Water outlet 5 Side panel 12 Air outlet 6 Handle 13 Power cord 7 Rear panel FRONT VIEW REAR VI...

Страница 6: ...t is in operation If you wish to make continuous draining of condensate follow the instructions in the dedicated paragraph OPERATING PRECAUTIONS The dehumidifier starts only if the humidity level in the room is higher than 3 the set one The dehumidifier will continue to operate until the set humidity level is reached except for any interruptions due to filling the tank When the water tank is full ...

Страница 7: ...ich is inside the tank is correctly positioned Make sure not to damage the float and the locking rivet which are inside the tank otherwise the unit will not automatically stop working when the water tank is full and the water could leak out and risk wetting the tank floor and damage the appliance N B Do not use the drainage pipe when you want to collect the condensate in the tank otherwise the wat...

Страница 8: ...lay then set the desired humidity level During operation the Power symbol on the display remains always on and the display shows the humidity level detected in the room during operation of the dehumidifier By pressing this button again the unit stops working and the ventilation stops 2 MODE BUTTON The unit works in the following circular sequence Auto Mode Continuous Mode Sleep Mode the correspond...

Страница 9: ...howing the humidity level detected in the environment To deactivate the Timer 00 must appear on the display flashes 4 times and the Timer symbol on the display will turn off 5 SPEED BUTTON VENTILATION SPEED It is possible to adjust the ventilation speed only in Auto mode Press this button to adjust the speed from high to low the corresponding symbols will light up on the display according to the s...

Страница 10: ...ly then insert it back into its housing Do not use hair dryer or fire to dry the filter Do not use sponges or brushes to clean the filter as they can damage it 2 2 Reposition the filter by inserting it as indicated by the arrow and replace the water tank Do not use the dehumidifier without the filter as dust may affect the efficiency of the evaporator resulting in higher energy consumption CONSERV...

Страница 11: ...d and the dehumidifier stops REGULATION EU N 517 2014 F GAS LILIUM ART 11 The unit contains R290 a natural greenhouse gas with global warming potential GWP 3 Kg 0 045 0 000135 Tons CO2 equiv Do not release R290 into the atmosphere LILIUM ART 13 The unit contains R290 a natural greenhouse gas with global warming potential GWP 3 Kg 0 050 0 000150 Tons CO2 equiv Do not release R290 into the atmospher...

Страница 12: ...se any sources of ignition in such a manner that it may lead to the risk of fire or explosion AII possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which refrigerant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed...

Страница 13: ...ceptable for all refrigerant systems Electronic leak detectors may be used to detect refrigerant leaks but in the case of flammable refrigerants the sensitivity may not be adequate or may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used Leak detection equipm...

Страница 14: ...ed refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked Labelling Equipment shall be labelled stating that it has been de commissioned and emptied of refrigerant The label shall be dated and signed For appliances containing flammable refrigerants ensure that there are labels on the equipment stating the equipment contains flammable refrigerant R...

Отзывы: