---That no live electrical components and wiring are exposed while charging, recovering or purging the system;  
---That there is continuity of earth bonding.  

 

Repairs to sealed components  

During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked 
upon prior to any removal of sealed covers, etc. lf it is absolutely necessary to have an electrical supply to equipment 
during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of 
a potentially hazardous situation.  
Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not 
altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of 
connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. 
• 

Ensure that the apparatus is mounted securely. 

• 

Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of 

preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's 
specifications.  
NOTE: The use of silicon sealant can inhibit the effectiveness of some types of leak detection equipment. lntrinsically 
safe components do not have to be isolated prior to working on them. 
Repair to intrinsically safe components  
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the 
permissible voltage and current permitted for the equipment in use.  
lntrinsically safe components are the only types that can be worked on while live in the presence of a flammable 
atmosphere. The test apparatus shall beat the correct rating.  
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in 
the atmosphere from a leak. 
 
Cabling  
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other 
adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from 
sources such as compressors or fans. 
Detection of flammable refrigerants  
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A 
halide torch (or any other detector using a naked flame) shall not be used. 
Leak detection methods 
The following leak detection methods are deemed acceptable for all refrigerant systems. 
Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity 
may not be adequate, or may need re-calibration.  
(Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of 
ignition and is suitable for the refrigerant used.  
Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the 
refrigerant employed, and the appropriate percentage of gas (25 % maximum) is confirmed. 
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chiarine shall be 
avoided as the chiarine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked 
flames shall be removed/extinguished. 
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or 
isolated (by means of shut off valves) in a part of the system remote from the leak. For appliances containing flammable 
refrigerants, oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing 
process. 
 
Removal and evacuation  
When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be 
used. However, for flammable refrigerants it is important that best practice is followed since flammability is a 
consideration. The following procedure shall be adhered to: 
• remove 

refrigerant; 

• 

purge the circuit with inert gas; evacuate; 

• 

purge again with inert gas; 

• 

open the circuit by cutting or brazing. 

The refrigerant charge shall be recovered into the correct recovery cylinders. 
For appliances containing flammable refrigerants, the system shall be flushed with OFN to render the unit safe. This 
process may need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant 
systems.  
For appliances containing flammable refrigerants, flushing shall be achieved by breaking the vacuum in the system with 
OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to 
a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, 
the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital 
if brazing operations on the pipe-work are to take place.  
Ensure that the outlet for the vacuum pump is not close to any ignition sources and that ventilation is available. 
 
Charging procedures 
In addition to conventional charging procedures, the following requirements shall be followed. 

Содержание LILIUM ART 11

Страница 1: ...UCTIONS Read the instructions carefully before operating or servicing the dehumidifier Observe all the safety instructions failure to observe the instructions may lead to accidents and or damage Keep these instructions in a safe place for future reference EN ...

Страница 2: ...n different ways other than those recommended by the manufacturer Should repair be necessary contact your nearest authorized Service Centre Any repairs carried out by unqualified personnel may be dangerous The appliance has to be stored in a room that doesn t have any continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not p...

Страница 3: ...they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision Make sure the plug is inserted fully Do not use multiple adapters Do not touch the plug with wet hands Make sure the plug is clean Children aged be...

Страница 4: ...s water leaks can cause it to malfunction or cause excessive vibration and running noise The dehumidifier must be positioned at least 50 cm away from the wall or other obstacles so that the heat can dissipate correctly Close all open windows to maximise dehumidification efficiency Do not insert objects or sharp instruments into the air outlet grille Do not cover the air intake and outlet grilles i...

Страница 5: ...ng so can cause leaks and malfunction In the event of interference with other electrical appliances place the two products at a minimum distance of 70cm DESCRIPTION OF PARTS 1 Control panel 8 Side panel 2 Colored LED with humidity sensor 9 Air inlet and air filter 3 Front panel 10 Water tank 4 Casters 11 Water outlet 5 Side panel 12 Air outlet 6 Handle 13 Power cord 7 Rear panel FRONT VIEW REAR VI...

Страница 6: ...t is in operation If you wish to make continuous draining of condensate follow the instructions in the dedicated paragraph OPERATING PRECAUTIONS The dehumidifier starts only if the humidity level in the room is higher than 3 the set one The dehumidifier will continue to operate until the set humidity level is reached except for any interruptions due to filling the tank When the water tank is full ...

Страница 7: ...ich is inside the tank is correctly positioned Make sure not to damage the float and the locking rivet which are inside the tank otherwise the unit will not automatically stop working when the water tank is full and the water could leak out and risk wetting the tank floor and damage the appliance N B Do not use the drainage pipe when you want to collect the condensate in the tank otherwise the wat...

Страница 8: ...lay then set the desired humidity level During operation the Power symbol on the display remains always on and the display shows the humidity level detected in the room during operation of the dehumidifier By pressing this button again the unit stops working and the ventilation stops 2 MODE BUTTON The unit works in the following circular sequence Auto Mode Continuous Mode Sleep Mode the correspond...

Страница 9: ...howing the humidity level detected in the environment To deactivate the Timer 00 must appear on the display flashes 4 times and the Timer symbol on the display will turn off 5 SPEED BUTTON VENTILATION SPEED It is possible to adjust the ventilation speed only in Auto mode Press this button to adjust the speed from high to low the corresponding symbols will light up on the display according to the s...

Страница 10: ...ly then insert it back into its housing Do not use hair dryer or fire to dry the filter Do not use sponges or brushes to clean the filter as they can damage it 2 2 Reposition the filter by inserting it as indicated by the arrow and replace the water tank Do not use the dehumidifier without the filter as dust may affect the efficiency of the evaporator resulting in higher energy consumption CONSERV...

Страница 11: ...d and the dehumidifier stops REGULATION EU N 517 2014 F GAS LILIUM ART 11 The unit contains R290 a natural greenhouse gas with global warming potential GWP 3 Kg 0 045 0 000135 Tons CO2 equiv Do not release R290 into the atmosphere LILIUM ART 13 The unit contains R290 a natural greenhouse gas with global warming potential GWP 3 Kg 0 050 0 000150 Tons CO2 equiv Do not release R290 into the atmospher...

Страница 12: ...se any sources of ignition in such a manner that it may lead to the risk of fire or explosion AII possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which refrigerant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed...

Страница 13: ...ceptable for all refrigerant systems Electronic leak detectors may be used to detect refrigerant leaks but in the case of flammable refrigerants the sensitivity may not be adequate or may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used Leak detection equipm...

Страница 14: ...ed refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked Labelling Equipment shall be labelled stating that it has been de commissioned and emptied of refrigerant The label shall be dated and signed For appliances containing flammable refrigerants ensure that there are labels on the equipment stating the equipment contains flammable refrigerant R...

Отзывы: