Argo AUR210CL Series Скачать руководство пользователя страница 23

23

Cool

YES

Outdoor unit
runs

NO

YES

RCU

YES

Outdoor unit
runs

NO

YES

RCU

A/C

Heat (AU 310 HL/HLQ only)

Try to lower setting tempera-
ture by temperature setting
button "COOLER".

Try to raise setting tempera-
ture by temperature setting
button "WARMER".

Set operation selector switch
in TEST position on indoor
unit.

Set operation selector switch
in TEST position on indoor
unit.

(6) Check setting temperature.

Temperature is too low.

Temperature is too high.

Try to run with another remo-
te control unit.

Try to run with another remo-
te control unit.

Check selector "B" on back
of remote control to see
which is selected,  A/C or
RCU.

Check selector "B" on back
of remote control to see
which is selected,  A/C or
RCU.

First remote control unit is
defective. (Room sensor in
remote control unit is defec-
tive. That is, sensor is
SHORT).

First remote control unit is
defective. (Room sensor in
remote control unit is defecti-
ve. That is, sensor is OPEN).

Room sensor (TH2) in
indoor unit is defecti-
ve. (Sensor is OPEN). 

Room sensor (TH2) in
indoor unit is defective.
(Sensor is SHORT). 

A/C

If fuse blows, there is a
possibility of short circuit.

OK

OK

Check fuse on PCB Ass’y in indoor unit
for continuity.

Measure resistance of indoor fan motor
winding (FMI).

PCB Ass’y in indoor unit is defective.

Measure resistance of primary winding
of transformer.

(5) Check fuse on PCB Ass’y in indoor unit.

IMPORTANT

During normal operation, the operation selector switch must be set in the ON position.

Содержание AUR210CL Series

Страница 1: ...TECHNICAL DATA SERVICE MANUAL ROOM AIR CONDITIONER WITH REMOTE CONDENSER TEST OFF ON AUR210CLXXXX AU213CLXXXX AUR310HLXXX COOLING ONLY VERSION R407C HEAT PUMP VERSION R407C 0 8180 090 1 05 2000...

Страница 2: ...aker trips or fuse blows Circuit breaker trips in several minutes after turning air conditioner ON Water level alarm lamp is flashing Outdoor unit and compressor do not run Some part of air conditione...

Страница 3: ...Width mm 440 525 525 Depth mm 230 250 250 Net weight indoor unit outdoor unit kg 44 9 5 44 15 44 15 PERFORMANCES COOLING COOLING HEATING Voltage rating V 220 240 Available voltage range V 198 264 Run...

Страница 4: ...C 3 0 5 10 C 9 9 5 50 C 2 1 5 Resistance k 10 C 10 0 4 30 C 4 0 4 15 C 7 9 4 35 C 3 3 4 20 C 6 3 4 40 C 2 7 4 25 C 5 0 4 50 C 1 8 4 COMPRESSOR Rotary hermetic Controls Microprocessor Control circuit f...

Страница 5: ...pen C 115 4 Close C 95 10 MODEL AUR210CLXXX AUR213CLXXX AUR310HLXXX Overload relay OLR External type Operating temp Open C 140 5 135 7 140 5 Close C 69 11 69 11 69 11 F 56 VAC 330 Run capacitor C4 Rat...

Страница 6: ...intake temp Temperature air C intake temp Maximum 32 C DB 22 C WB 46 C DB Minimum 19 C DB 14 C WB 19 C DB Maximum 27 C DB 19 C WB 24 C DB 18 C WB Minimum DB WB 8 C DB 9 C WB Open C 150 10 Close C Aut...

Страница 7: ...7 C DIMENSIONAL DATA Indoor unit Outdoor unit 580 835 245 230 440 425 DIMENSIONS mm HEAT PUMP MODEL AND AUR213CLXXX 790 580 440 490 230 250 435 490 245...

Страница 8: ...25 30 35 40 45 OUTDOOR INLET AIR D B TEMP C AUR213CLXXX AUR210CLXXX 32 27 19 Operating characteristics versus outdoor ambient temperature and indoor temperature Conditions Power source 230 V 1 50Hz Si...

Страница 9: ...G CURRENT A OUTDOOR INLET AIR D B TEMP C INDOOR INLET AIR D B TEMP C 20 25 30 35 40 45 Operating characteristics versus outdoor ambient temperature and indoor temperature Conditions Power source 230 V...

Страница 10: ...cal filter Heat exchanger Heat exchanger Outdoor unit Indoor unit REFIGERANT FLOW DIAGRAM HEAT PUMP MODELS Heat exchanger Muffler Stainer 4 way valve Accumulator Compressor Heat exchanger Drier Capill...

Страница 11: ...rmo OFF When the room temperature in equal to or below set temperature T C Compressor OFF F FUNCTION 1 ROOM TEMPERATURE CONTROL Cooling Room temperature control is obtained by cycling the compressor O...

Страница 12: ...emperature T C Compressor OFF Heating Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit The room tempera...

Страница 13: ...ORE THAN 6 MINUTES INDOOR FAN COMPRESSOR INDOOR HEAT EXCH COIL TEMP T 1 C T C SET TEMP 1 C 3 OVERLOAD PREVENTION HEATING This function prevents overheating for the indoor heat exchange coil COMPRESSOR...

Страница 14: ...D HEATING HEAT PUMP MODEL When auto mode is selected the microprocessor calculates the difference between the set temperature and the room temperature and automatically switches to cooling or heating...

Страница 15: ...for at least 6 minutes Outdoor fan is either operated or stopped for more than 10 minutes Is outdoor fan continuolsy opera ting for more than 10 minutes Integrate operating time of com pressor is more...

Страница 16: ...N ON OFF OFF OFF OFF OFF OFF OFF ON ON ON 32 SEC MAX 12 MIN 32 SEC 2 SEC START OF DEFROSTING RELEASE OF DEFROSTING RELEASE OF COLD DRAFT PREVENTION INDOOR HEAT EXCH COIL TEMP 35 C STANDBY LAMP COMPRES...

Страница 17: ...RSION SCHEMA ELETTRICO VERSIONE SOLO RAFFREDDAMENTO SCH MA LECTRIQUE VERSION FROID SEUL SCHALTPLAN AUSF HRUNG NUR K LUNG ESQUEMA ELECTRICO SCHALTPLAN MODELOS QUE SOLO EINFRIAN HLEKTRIKODIAGRAMMA EKDOS...

Страница 18: ...EAT PUMP VERSION SCHEMA ELETTRICO VERSIONE POMPA DI CALORE SCH MA LECTRIQUE VERSION POMPE CHALEUR SCHALTPLAN W RMEPUMPE AUSF HRUNG ESQUEMAELECTRICO SCHALTPLAN MODELOS BOMBADE CALOR HLEKTRIKODIAGRAMMA...

Страница 19: ...insu lation is defective B There is a possibility of short circuit Circuit breacker trips in several minutes after turning air conditioner ON NO NO YES YES Check capacity of circuit breaker Capacity o...

Страница 20: ...pump PC without it Connect the first white wire to N terminal of unit terminal strip The connetc the second white wire to the power relay PR NO ter mial for AU 310 HL unit 8 termial for AU 213 CL uni...

Страница 21: ...tor DEFECTIVE DEFECTIVE OK Check fan motor capacitor Replace Measure resistance of fan motor winding Replace fan motor Fan cannot be turned Check fan rotation Turn fan gently once or twice by hand Rem...

Страница 22: ...control unit AIR CONDITIONER OPERATES BUT ABNORMALITIES ARE OBSERVED HEAT PUMP MODEL 1 Operation does not switch from heat to cool or cool to heat Remote control unit may be defective Measure resistan...

Страница 23: ...ck selector B on back of remote control to see which is selected A C or RCU First remote control unit is defective Room sensor in remote control unit is defec tive That is sensor is SHORT First remote...

Страница 24: ...LOW Measure temperatures of suction and discharge air of air conditioner Review cooling or heating load esti mate if performance of air conditio ner is normal Air filter is clogged Change position of...

Страница 25: ...ventilation Fault with serial communication between the two controllers PCB1 PCB2 ground fault on connecting wires When the air conditioner is submit to an high magnetic noise electronic locking of m...

Страница 26: ...plunger welded to the service connection quick connection to the pump pipes Reload of the system after a maintenance intervention or after an uncorrect detach of the connection pipe Before disconnecti...

Страница 27: ...sealing of the aeroquip quick connections The full charge of refrigerant must be restored to the indoor unit Outdoor unit little bag bleeding Connect the vacuum pump already equipped with service conn...

Страница 28: ...d measure the resistance by placing a probe on N terminal and then on L terminal the terminal plate Fig 2 b Measurement of Insulation Resistance for Electrical Parts Disconnect the lead wires of the d...

Страница 29: ...citor is good if the pointer bounces to a great extent and the gradually returns to its origi nal position The range of deflection and deflection time deffer according to capacity of the capacitor Fig...