11
NOTA
●
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least
3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant
pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
●
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of com-
pressor operation.
●
Thermo ON:
When the room temperature is above T + 1 °C (T°C is set temperature).
Compressor
➜
ON.
●
Thermo OFF: When the room temperature in equal to or below set temperature T°C.
Compressor
➜
OFF.
F
FUNCTION
1) ROOM TEMPERATURE CONTROL
Cooling
●
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the remote control unit.
●
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to
the controller in the indoor unit.
TERMO.
OFF
3 MINUTES
MORE THAN
5 MINUTES
OFF
OFF
ON ON
ON
ON
OFF
OFF
ON
ON
5 MINUTES
3 MINUTES
SET SPEED
OFF
OFF
3 MINUTES
3 MINUTES
3 MINUTES
3 MINUTES
3 MINUTES
3 MINUTES
TERMO.
OFF
TERMO.
ON
TERMO.
ON
TERMO.
ON
TERMO.
ON
SIGNAL FROM REMOTE CONTROL UNIT
ROOM TEMP.
TERMOSTATO
OFF
COMPRESSOR
INDOOR FAN
OUTDOOR FAN
T + 1°C
T °C
SET TEMP.