DC Inverter Package R32 Cassette Type Unit
62
5.4.3 Repair to Intrinsically Safe Components
Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and current
permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while
live in the presence of a flammable atmosphere. The test apparatus shall be at
the correct rating.
Replace components only with parts specified by the manufacturer. Other
parts may result in the ignition of refrigerant in the atmosphere from a leak.
5.4.4 Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges or any other adverse environmental effects. The check
shall also take into account the effects of ageing or continual vibration from
sources such as compressors or fans.
5.4.5 Detection of Flammable Refrigerants
Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks. A halide torch (or any other
detector using a naked flame) shall not be used.
5.4.6 Removal and Evacuation
When breaking into the refrigerant circuit to make repairs – or for any other
purpose –conventional procedures shall be used. However, it is important that
best practice is followed since flammability is a consideration. The following
procedure shall be adhered to
φ
(1) Remove refrigerant.
(2) Purge the circuit with inert gas.
(3) Evacuate.
(4) Purge again with inert gas.
(5) Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders.
The system shall be “flushed” with OFN to render the unit safe. This process may
need to be repeated several times. Compressed air or oxygen shall not be used
for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN
Содержание AEG ECO 100PIH
Страница 9: ...DC Inverter Package R32 Cassette Type Unit 5 2 Product Introduction 2 1 Overall Layout ...
Страница 16: ...DC Inverter Package R32 Cassette Type Unit 12 2 Outdoor unit 35 70 85 A F D E G C B 100 140 A D E G B C ...
Страница 92: ...DC Inverter Package R32 Duct Type Unit 18 4 When outdoor units are installed one above another Unit mm ...
Страница 128: ...DC Inverter Package R32 Duct Type Unit 54 B Wire routing of unified power supply for single phase ...
Страница 130: ...DC Inverter Package R32 Duct Type Unit 56 Only for AEG ECO 160PIH3 ...
Страница 131: ...DC Inverter Package R32 Duct Type Unit 57 B Wire routing of unified power supply for three phase ...
Страница 132: ...DC Inverter Package R32 Duct Type Unit 58 Only for AEG ECO 160PIH3 ...
Страница 157: ...DC Inverter Package R32 Floor Ceiling Type Unit 5 2 Product Introduction 2 1 Overall Layout ...
Страница 164: ...DC Inverter Package R32 Floor Ceiling Type Unit 12 100 140 A D E G B C 160 A C D E G B ...
Страница 226: ...www argoclima com ...
Страница 227: ... LUHG RQWUROOHU ZLWK ZHHNO WLPHU 8VHU DQG LQVWDOODWLRQ 0DQXDO ...
Страница 231: ... QVWDOODWLRQ QVWUXFWLRQV 3DUWV DQG LPHQVLRQ RI LUHG RQWUROOHU QVWDOODWLRQ 5HTXLUHPHQWV QVWDOODWLRQ 0HWKRGV LVDVVHPEO ...
Страница 233: ... LVSOD SSHDUDQFH LJXUH SSHDUDQFH RI ZLUHG FRQWUROOHU LUHG RQWUROOHU ...
Страница 237: ... XWWRQV XWWRQ UDSKLFV LJXUH XWWRQ JUDSKLFV LUHG RQWUROOHU ...
Страница 244: ... LUHG RQWUROOHU ...
Страница 256: ... LJXUH 6WDWXV 9LHZ LUHG RQWUROOHU ...
Страница 258: ... LJXUH XUUHQW UURU 9LHZ LUHG RQWUROOHU ...
Страница 262: ... LUHG RQWUROOHU ...
Страница 263: ... LUHG RQWUROOHU ...
Страница 269: ... LJXUH ORFN VHWWLQJ LUHG RQWUROOHU ...
Страница 275: ... ...
Страница 287: ...www argoclima com ...