DC Inverter Package R32 Duct Type Unit
30
Then, close the switch fully and then stop the vacuum pump.
(6) Wait for 10min to see if the system pressure can remain unchanged. If the
pressure increase, there may be leakage.
(7) Slightly open the liquid valve and let some refrigerant go to the connection
pipe to balance the pressure inside and outside of the connection pipe, so
that air will not come into the connection pipe when removing the hose.
Note that the gas and liquid valve can be opened fully only after the
manifold valve assembly is removed.
(8) Place back the caps of the liquid valve, gas valve and also the service
port.
NOTE:
For large-size units, there are maintenance ports for liquid valve and gas valve.
During evacuation, you may connect the two hoses of the branch valve assembly to
the maintenance ports to speed up the evacuation.
3.2.4.2 Leak Detection Methods
The following leak detection methods are deemed acceptable for systems
containing flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the
sensitivity may not be adequate, or may need re-calibration
(Detection equipment
shall be calibrated in a refrigerant-free area).
Ensure that the detector is not a potential source of ignition and is suitable for
Содержание AEG ECO 100PIH
Страница 9: ...DC Inverter Package R32 Cassette Type Unit 5 2 Product Introduction 2 1 Overall Layout ...
Страница 16: ...DC Inverter Package R32 Cassette Type Unit 12 2 Outdoor unit 35 70 85 A F D E G C B 100 140 A D E G B C ...
Страница 92: ...DC Inverter Package R32 Duct Type Unit 18 4 When outdoor units are installed one above another Unit mm ...
Страница 128: ...DC Inverter Package R32 Duct Type Unit 54 B Wire routing of unified power supply for single phase ...
Страница 130: ...DC Inverter Package R32 Duct Type Unit 56 Only for AEG ECO 160PIH3 ...
Страница 131: ...DC Inverter Package R32 Duct Type Unit 57 B Wire routing of unified power supply for three phase ...
Страница 132: ...DC Inverter Package R32 Duct Type Unit 58 Only for AEG ECO 160PIH3 ...
Страница 157: ...DC Inverter Package R32 Floor Ceiling Type Unit 5 2 Product Introduction 2 1 Overall Layout ...
Страница 164: ...DC Inverter Package R32 Floor Ceiling Type Unit 12 100 140 A D E G B C 160 A C D E G B ...
Страница 226: ...www argoclima com ...
Страница 227: ... LUHG RQWUROOHU ZLWK ZHHNO WLPHU 8VHU DQG LQVWDOODWLRQ 0DQXDO ...
Страница 231: ... QVWDOODWLRQ QVWUXFWLRQV 3DUWV DQG LPHQVLRQ RI LUHG RQWUROOHU QVWDOODWLRQ 5HTXLUHPHQWV QVWDOODWLRQ 0HWKRGV LVDVVHPEO ...
Страница 233: ... LVSOD SSHDUDQFH LJXUH SSHDUDQFH RI ZLUHG FRQWUROOHU LUHG RQWUROOHU ...
Страница 237: ... XWWRQV XWWRQ UDSKLFV LJXUH XWWRQ JUDSKLFV LUHG RQWUROOHU ...
Страница 244: ... LUHG RQWUROOHU ...
Страница 256: ... LJXUH 6WDWXV 9LHZ LUHG RQWUROOHU ...
Страница 258: ... LJXUH XUUHQW UURU 9LHZ LUHG RQWUROOHU ...
Страница 262: ... LUHG RQWUROOHU ...
Страница 263: ... LUHG RQWUROOHU ...
Страница 269: ... LJXUH ORFN VHWWLQJ LUHG RQWUROOHU ...
Страница 275: ... ...
Страница 287: ...www argoclima com ...