DC Inverter Package R32 Duct Type Unit
68
explosion. All possible ignition sources, including cigarette smoking, should be kept
sufficiently far away from the site of installation, repairing, removing and disposal,
during which flammable refrigerant can possibly be released to the surrounding
space. Prior to work taking place, the area around the equipment is to be surveyed
to make sure that there are no flammable hazards or ignition risks. “No Smoking”
signs shall be displayed.
5.4.1.7 Ventilated Area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation shall
continue during the period that the work is carried out. The ventilation should safely
disperse any released refrigerant and preferably expel it externally into the
atmosphere.
5.4.1.8 Checks to the Refrigeration Equipment
Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification. At all times the manufacturer’s
maintenance and service guidelines shall be followed. If in doubt consult the
manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable
refrigerants:
(1) The charge size is in accordance with the room size within which the
refrigerant containing parts are installed.
(2) The ventilation machinery and outlets are operating adequately and are
not obstructed.
(3) If an indirect refrigerating circuit is being used, the secondary circuit shall
be checked for the presence of refrigerant.
(4) Marking to the equipment continues to be visible and legible. Markings
and signs that are illegible shall be corrected.
(5) Refrigeration pipe or components are installed in a position where they
are unlikely to be exposed to any substance which may corrode
refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being corroded
or are suitably protected against being so corroded.
Содержание AEG ECO 100PIH
Страница 9: ...DC Inverter Package R32 Cassette Type Unit 5 2 Product Introduction 2 1 Overall Layout ...
Страница 16: ...DC Inverter Package R32 Cassette Type Unit 12 2 Outdoor unit 35 70 85 A F D E G C B 100 140 A D E G B C ...
Страница 92: ...DC Inverter Package R32 Duct Type Unit 18 4 When outdoor units are installed one above another Unit mm ...
Страница 128: ...DC Inverter Package R32 Duct Type Unit 54 B Wire routing of unified power supply for single phase ...
Страница 130: ...DC Inverter Package R32 Duct Type Unit 56 Only for AEG ECO 160PIH3 ...
Страница 131: ...DC Inverter Package R32 Duct Type Unit 57 B Wire routing of unified power supply for three phase ...
Страница 132: ...DC Inverter Package R32 Duct Type Unit 58 Only for AEG ECO 160PIH3 ...
Страница 157: ...DC Inverter Package R32 Floor Ceiling Type Unit 5 2 Product Introduction 2 1 Overall Layout ...
Страница 164: ...DC Inverter Package R32 Floor Ceiling Type Unit 12 100 140 A D E G B C 160 A C D E G B ...
Страница 226: ...www argoclima com ...
Страница 227: ... LUHG RQWUROOHU ZLWK ZHHNO WLPHU 8VHU DQG LQVWDOODWLRQ 0DQXDO ...
Страница 231: ... QVWDOODWLRQ QVWUXFWLRQV 3DUWV DQG LPHQVLRQ RI LUHG RQWUROOHU QVWDOODWLRQ 5HTXLUHPHQWV QVWDOODWLRQ 0HWKRGV LVDVVHPEO ...
Страница 233: ... LVSOD SSHDUDQFH LJXUH SSHDUDQFH RI ZLUHG FRQWUROOHU LUHG RQWUROOHU ...
Страница 237: ... XWWRQV XWWRQ UDSKLFV LJXUH XWWRQ JUDSKLFV LUHG RQWUROOHU ...
Страница 244: ... LUHG RQWUROOHU ...
Страница 256: ... LJXUH 6WDWXV 9LHZ LUHG RQWUROOHU ...
Страница 258: ... LJXUH XUUHQW UURU 9LHZ LUHG RQWUROOHU ...
Страница 262: ... LUHG RQWUROOHU ...
Страница 263: ... LUHG RQWUROOHU ...
Страница 269: ... LJXUH ORFN VHWWLQJ LUHG RQWUROOHU ...
Страница 275: ... ...
Страница 287: ...www argoclima com ...