Subject to change · TSE3-D_9193_1en_09/2019

More information at www.argo-hytos.com

Page 9 

9.4 User settings (optional)
9.4.1 Set delay for the switching outputs

[dS1] / [dS2] = switching delay for OUT1 / OUT2.

[dr1] / [dr2] = reset delay for OUT1 / OUT2. 

 Select [dS1], [dS2], [dr1] or [dr2] and set a value between 0 and 50 s (at 0 the delay time is not active).

 For this unit the parameters [dSx] and [drx] for the set and reset points are designed strictly to the VDMA 

guideline!

9.4.2 Set output logic for the switching outputs

 Select [P-n] and set [PnP] or [nPn].

9.4.3 Set damping for the switching signal

 Select [dAP] and set the damping constant in seconds (value T: 63 %); setting range 0.000 ... 4.000 s.

Damping affects [dAP] the switch point / process data flow (IO-Link communication) and the display.

9.4.4 Damping for analogue output

 Select [dAA] and set the damping constant (rise time 10 ... 90 %) in seconds; setting range 0.000 ... 4.000 s.

Damping [dAA] only affects the analogue output / analogue signal path.

9.4.5 Zero-point calibration

 Select [coF] and set a value between -5 % and 5 % of the final value of the measuring range 

    (if PN2x69 and PN2x99 ±5 % of the measuring span). The internal measured value „0“ is shifted by this value.

9.4.6 Read min/max values for the system pressure

 Select [HI] or [Lo] and briefly press [

].

[HI] = maximum value, [Lo] = minimum value. 

Delete memory:

 Select [HI] or [Lo].

 Press and hold [

] or [

] until [----] is displayed.

 Briefly press [

].

9.4.7 Reset all parameters to factory setting

 Select [rES].

 Press [

].

 Press and hold [

] or [

] until [----] is displayed.

 Briefly press [

].

We recommend noting down your own settings before carrying out a reset (

 12 Factory setting).

9.4.8 Set colour change of the display

 

*) The parameters [cFL] and [cFH ] can only be selected in the menu tree when [r-cF] or [G-cF] were activated.

 Select [cFH] and set the upper limit value. (only possible when [r-cF] or [G-cF] were activated). 

>  The setting range corresponds to the measuring range and its minimum limit is [cFL].

 Select [cFL] and set the lower limit value (only possible when [r-cF] or [G-cF] were activated). 

>  The setting range corresponds to the measuring range and its maximum limit is [cFH].

 

Select [coLr] and set the function:

- [rEd]  

=  display colour red (independent of the measured value).

- [GrEn]   =  display colour green (independent of the measured value).

- [r1ou]  =  display colour red when OUT1 switches.

- [G1ou]   =  display colour green when OUT1 switches.

- [r2ou]   =  display colour red when OUT2 switches ([ou2] = [Hxx] / [Fxx]).

- [G2ou]   =  display colour green when OUT2 switches ([ou2] = [Hxx] / [Fxx]).

- [r-12]   =  display colour red when the measured value is between the limit values of OUT1 and OUT2 ([ou2] = [Hxx] / [Fxx]).

- [G-12]   =  display colour green when the measured value is between the limit values of OUT1 and OUT2 ([ou2] = [Hxx] / [Fxx]).

- [r-cF]  

=  display colour red when the measured value is between the freely definable limit values [cFH]*) and [cFL]*).

- [G-cF]  =  display colour green when the measured value is between the freely definable limit values [cFH]*) and [cFL]*).

Содержание TSE3-D

Страница 1: ...s of the warranty claims 1 Preliminary note 1 1 1 Symbols used 1 2 Safety instructions 1 3 Functions and features 2 3 1 Applications 2 4 Function 2 4 1 Communication parameter setting evaluation 2 4 2...

Страница 2: ...tem pressure It generates output signals according to the operating mode and the parameter setting It moreover provides the process data via IO Link The unit is laid out for fully bidirectional commun...

Страница 3: ...o indicated System pressure above AEP2 20 20 5 mA System pressure below ASP2 4 3 8 mA Fault indication according to Namur 21 5 mA 4 4 IO Link General information This unit has an IO Link communication...

Страница 4: ...onnected only by using any Listed CYJV 7 or R C CYJV2 8 cord in respect of Condition of Acceptability having suitable ratings Core colours BK black BN brown BU blue WH white OUT1 switching output or I...

Страница 5: ...pressure at which OUTx switches with hysteresis setting Prerequisite OUTx setting is Hno or Hnc FHx FLx Upper lower limit value for system pressure at which OUTx switches with window setting Prerequis...

Страница 6: ...ur window in the coLr parameter r cF or G cF diS Update rate and orientation of the display 9 Parameter setting During parameter setting the unit remains in the operating mode It continues to monitor...

Страница 7: ...isplayed During operation Loc is briefly displayed if you try to change parameter values For unlocking Make sure that the unit is in the normal operating mode Press imultaneously for 10 s uLoc is disp...

Страница 8: ...ing function Hno hysteresis function NO Hnc hysteresis function NC Fno window function NO Fnc window function NC Select OU2 and set the analogue function Hno hysteresis function NO Hnc hysteresis func...

Страница 9: ...ss and hold or until is displayed Briefly press 9 4 7 Reset all parameters to factory setting Select rES Press Press and hold or until is displayed Briefly press We recommend noting down your own sett...

Страница 10: ...r change display red 1 Initial value of the measuring range 2 Final value of the measuring range Representation r 12 G 12 only possible when ou2 switching output Display colour change for the paramete...

Страница 11: ...Display Status LED OUT1 Status LED OUT2 Type of fault Fault warning Corrective measures none F Supply voltage too low Check correct the supply voltage SC flashes flashes flashes F Excessive current at...

Страница 12: ...11 2 Further technical data Further technical data and scale drawing at www argo hytos com 12 Factory setting Factory setting User setting SP1 25 MEW rP1 23 MEW ou1 Hno ou2 I SP2 75 MEW rP2 73 MEW ASP...

Отзывы: