Subject to change · TSE3-D_9193_1en_09/2019
More information at www.argo-hytos.com
Page 9
9.4 User settings (optional)
9.4.1 Set delay for the switching outputs
[dS1] / [dS2] = switching delay for OUT1 / OUT2.
[dr1] / [dr2] = reset delay for OUT1 / OUT2.
►
Select [dS1], [dS2], [dr1] or [dr2] and set a value between 0 and 50 s (at 0 the delay time is not active).
For this unit the parameters [dSx] and [drx] for the set and reset points are designed strictly to the VDMA
guideline!
9.4.2 Set output logic for the switching outputs
►
Select [P-n] and set [PnP] or [nPn].
9.4.3 Set damping for the switching signal
►
Select [dAP] and set the damping constant in seconds (value T: 63 %); setting range 0.000 ... 4.000 s.
Damping affects [dAP] the switch point / process data flow (IO-Link communication) and the display.
9.4.4 Damping for analogue output
►
Select [dAA] and set the damping constant (rise time 10 ... 90 %) in seconds; setting range 0.000 ... 4.000 s.
Damping [dAA] only affects the analogue output / analogue signal path.
9.4.5 Zero-point calibration
►
Select [coF] and set a value between -5 % and 5 % of the final value of the measuring range
(if PN2x69 and PN2x99 ±5 % of the measuring span). The internal measured value „0“ is shifted by this value.
9.4.6 Read min/max values for the system pressure
►
Select [HI] or [Lo] and briefly press [
●
].
[HI] = maximum value, [Lo] = minimum value.
Delete memory:
►
Select [HI] or [Lo].
►
Press and hold [
▲
] or [
▼
] until [----] is displayed.
►
Briefly press [
●
].
9.4.7 Reset all parameters to factory setting
►
Select [rES].
►
Press [
●
].
►
Press and hold [
▲
] or [
▼
] until [----] is displayed.
►
Briefly press [
●
].
We recommend noting down your own settings before carrying out a reset (
→
12 Factory setting).
9.4.8 Set colour change of the display
►
*) The parameters [cFL] and [cFH ] can only be selected in the menu tree when [r-cF] or [G-cF] were activated.
►
Select [cFH] and set the upper limit value. (only possible when [r-cF] or [G-cF] were activated).
> The setting range corresponds to the measuring range and its minimum limit is [cFL].
►
Select [cFL] and set the lower limit value (only possible when [r-cF] or [G-cF] were activated).
> The setting range corresponds to the measuring range and its maximum limit is [cFH].
Select [coLr] and set the function:
- [rEd]
= display colour red (independent of the measured value).
- [GrEn] = display colour green (independent of the measured value).
- [r1ou] = display colour red when OUT1 switches.
- [G1ou] = display colour green when OUT1 switches.
- [r2ou] = display colour red when OUT2 switches ([ou2] = [Hxx] / [Fxx]).
- [G2ou] = display colour green when OUT2 switches ([ou2] = [Hxx] / [Fxx]).
- [r-12] = display colour red when the measured value is between the limit values of OUT1 and OUT2 ([ou2] = [Hxx] / [Fxx]).
- [G-12] = display colour green when the measured value is between the limit values of OUT1 and OUT2 ([ou2] = [Hxx] / [Fxx]).
- [r-cF]
= display colour red when the measured value is between the freely definable limit values [cFH]*) and [cFL]*).
- [G-cF] = display colour green when the measured value is between the freely definable limit values [cFH]*) and [cFL]*).