4.3 Analogue function

OUT2 is an analogue output:

 › [ou2] defines whether the set measuring range is provided as 4...20 mA ([ou2]= [I]) or as 0 ... 10 V ([ou2] = [U]).
 › Analogue start point [ASP2] determines at which measured value the output signal is 4 mA or 0 V.
 › Analogue end point [AEP2] determines at which measured value the output signal is 20 mA or 10 V. 

 

 › Minimum distance between [ASP2] and [AEP2] = 20 % of the measuring span.

Voltage output 0 ... 10 V:

Current output 4 ... 20 mA: 

Factory setting

Measuring range scaled

Factory setting

Measuring range scaled

P =         System pressure

MEW =  Final value of the measuring range

ASP =    Analogue start point [ASP2]

AEP=     Analogue end point [AEP2]

P =         System pressure

MEW =  Final value of the measuring range

ASP =    Analogue start point [ASP2]

AEP=     Analogue end point [AEP2]

In the measuring range of the respective unit the output signal is 

between 0 and 10 V.

It is also indicated:

 › System pressure above [AEP2]: 10 ... 10.3 V
 › Fault indication according to Namur: 11 V

In the measuring range, the output signal is between 4 and 20 mA.

It is also indicated:

 › System pressure above [AEP2]: 20 ... 20.5 mA
 › System pressure below [ASP2]: 4 ... 3.8 mA
 › Fault indication according to Namur: 21.5 mA.

4.4 IO-Link

General information

This unit has an IO-Link communication interface which requires an IO-Linkcapable module (IO-Link master) for operation.
The IO-Link interface enables direct access to the process and diagnostic data and provides the possibility to set the parameters of the unit during 
operation.
In addition communication is possible via a point-to-point connection with a USB adapter cable.
Further information about IO-Link at 

www.argo-hytos.com

 →

 „Products“ 

 „Pressure Switches“ 

 „TSE3-D“.

Device-specific information

You can find the IODDs necessary for the configuration of the IO-Link unit and detailed information about process data structure, diagnostic 
information and parameter addresses at 

www.argo-hytos.com 

 „Products“ 

 „Pressure Switches“ 

 „TSE3-D“.

Before installing and removing the unit: make sure that no pressure is applied to the system.

5 Installation

  Insert the unit in a G¼ process connection.

  Tighten firmly. Recommended tightening torque:

Pressure range in bar

Tightening torque in Nm

-1 ... 400

25 ... 35

Depends on lubrication, seal and pressure load!

Do not rotate past the end stop!

The sensor housing can be rotated by 345° with regard to the process connection.

Содержание TSE3-D

Страница 1: ...s of the warranty claims 1 Preliminary note 1 1 1 Symbols used 1 2 Safety instructions 1 3 Functions and features 2 3 1 Applications 2 4 Function 2 4 1 Communication parameter setting evaluation 2 4 2...

Страница 2: ...tem pressure It generates output signals according to the operating mode and the parameter setting It moreover provides the process data via IO Link The unit is laid out for fully bidirectional commun...

Страница 3: ...o indicated System pressure above AEP2 20 20 5 mA System pressure below ASP2 4 3 8 mA Fault indication according to Namur 21 5 mA 4 4 IO Link General information This unit has an IO Link communication...

Страница 4: ...onnected only by using any Listed CYJV 7 or R C CYJV2 8 cord in respect of Condition of Acceptability having suitable ratings Core colours BK black BN brown BU blue WH white OUT1 switching output or I...

Страница 5: ...pressure at which OUTx switches with hysteresis setting Prerequisite OUTx setting is Hno or Hnc FHx FLx Upper lower limit value for system pressure at which OUTx switches with window setting Prerequis...

Страница 6: ...ur window in the coLr parameter r cF or G cF diS Update rate and orientation of the display 9 Parameter setting During parameter setting the unit remains in the operating mode It continues to monitor...

Страница 7: ...isplayed During operation Loc is briefly displayed if you try to change parameter values For unlocking Make sure that the unit is in the normal operating mode Press imultaneously for 10 s uLoc is disp...

Страница 8: ...ing function Hno hysteresis function NO Hnc hysteresis function NC Fno window function NO Fnc window function NC Select OU2 and set the analogue function Hno hysteresis function NO Hnc hysteresis func...

Страница 9: ...ss and hold or until is displayed Briefly press 9 4 7 Reset all parameters to factory setting Select rES Press Press and hold or until is displayed Briefly press We recommend noting down your own sett...

Страница 10: ...r change display red 1 Initial value of the measuring range 2 Final value of the measuring range Representation r 12 G 12 only possible when ou2 switching output Display colour change for the paramete...

Страница 11: ...Display Status LED OUT1 Status LED OUT2 Type of fault Fault warning Corrective measures none F Supply voltage too low Check correct the supply voltage SC flashes flashes flashes F Excessive current at...

Страница 12: ...11 2 Further technical data Further technical data and scale drawing at www argo hytos com 12 Factory setting Factory setting User setting SP1 25 MEW rP1 23 MEW ou1 Hno ou2 I SP2 75 MEW rP2 73 MEW ASP...

Отзывы: