The device monitors the system pressure of machines and installations.

Order number

Measuring range

Pressure resistance

  (max. permissible pressure) *)

Bursting pressure

bar

PSI

bar

PSI

bar

PSI

Pressure sensor switch with G¼ external thread

TSE3-D

0 ... 400

0 … 5 800

800

11 580

1 700

24 650

*)

 With static overload pressure or max. 100 million pressure cycles.

MPa = (measured value in bar) ÷ 10

kPa = (measured value in bar) x 100

3 Functions and features

3.1 

Applications

Type of pressure: Relative pressure

Avoid static and dynamic overpressure exceeding the specified overload pressure by taking appropriate measures.
The indicated bursting pressure must not be exceeded.
Even if the bursting pressure is exceeded only for a short time, the unit may be destroyed. 
ATTENTION: Risk of injury!

The units are vacuum resistant. With a nominal pressure range ≤ 300 mbar observe the specifications in the data sheet!

Pressure Equipment Directive (PED):
The units comply with the Pressure Equipment Directive and are designed and manufactured for group 2 fluids in accordance with the 
sound engineering practice.
Use of group 1 fluids on request!

4 Function

 › The unit displays the current system pressure.
 › It generates output signals according to the operating mode and the parameter setting.
 › It moreover provides the process data via IO-Link.
 › The unit is laid out for fully bidirectional communication. So, the following options are possible:

 

- Remote display: reading and display of the current system pressure.

 

- Remote parameter setting: reading and changing the current parameter setting.

 

- IO-Link parameter setting 

 4.4.

4.1 Communication, parameter setting, evaluation

OUT1 (pin 4)

 › Switching signal (250 mA) for system pressure limit value
 › Communication via IO-Link

OUT2 (pin 2)

 › Switching signal (250 mA) for system pressure limit value
 › Analogue signal 4 ... 20 mA / 0 ... 10 V

4.2 Switching function

OUTx changes its switching status (250 mA) if it is above or below the set switching limits (SPx, rPx). 
The following switching functions can be selected:

 › Hysteresis function / normally open: [ou1/ou2] = [Hno] (

 fig. 1).

 › Hysteresis function / normally closed: [ou1/ou2] = [Hnc] (

 fig. 1).

  First the set point (SPx) is set, then the reset point (rPx).
  The hysteresis defined remains even if SPx is changed again.

 › Window function / normally open: [ou1/ou2] = [Fno] (

 fig. 2).

 › Window function / normally closed: [ou1/ou2] = [Fnc] (

 fig. 2).

  The width of the window can be set by means of the difference between FHx and FLx. FHx = upper value, FLx = lower value.

When set to the window function the set and reset points have a fixed hysteresis of 0.25 % of the final value of the measuring span.

P    = system pressure;
HY = hysteresis;
FE  = window

Содержание TSE3-D

Страница 1: ...s of the warranty claims 1 Preliminary note 1 1 1 Symbols used 1 2 Safety instructions 1 3 Functions and features 2 3 1 Applications 2 4 Function 2 4 1 Communication parameter setting evaluation 2 4 2...

Страница 2: ...tem pressure It generates output signals according to the operating mode and the parameter setting It moreover provides the process data via IO Link The unit is laid out for fully bidirectional commun...

Страница 3: ...o indicated System pressure above AEP2 20 20 5 mA System pressure below ASP2 4 3 8 mA Fault indication according to Namur 21 5 mA 4 4 IO Link General information This unit has an IO Link communication...

Страница 4: ...onnected only by using any Listed CYJV 7 or R C CYJV2 8 cord in respect of Condition of Acceptability having suitable ratings Core colours BK black BN brown BU blue WH white OUT1 switching output or I...

Страница 5: ...pressure at which OUTx switches with hysteresis setting Prerequisite OUTx setting is Hno or Hnc FHx FLx Upper lower limit value for system pressure at which OUTx switches with window setting Prerequis...

Страница 6: ...ur window in the coLr parameter r cF or G cF diS Update rate and orientation of the display 9 Parameter setting During parameter setting the unit remains in the operating mode It continues to monitor...

Страница 7: ...isplayed During operation Loc is briefly displayed if you try to change parameter values For unlocking Make sure that the unit is in the normal operating mode Press imultaneously for 10 s uLoc is disp...

Страница 8: ...ing function Hno hysteresis function NO Hnc hysteresis function NC Fno window function NO Fnc window function NC Select OU2 and set the analogue function Hno hysteresis function NO Hnc hysteresis func...

Страница 9: ...ss and hold or until is displayed Briefly press 9 4 7 Reset all parameters to factory setting Select rES Press Press and hold or until is displayed Briefly press We recommend noting down your own sett...

Страница 10: ...r change display red 1 Initial value of the measuring range 2 Final value of the measuring range Representation r 12 G 12 only possible when ou2 switching output Display colour change for the paramete...

Страница 11: ...Display Status LED OUT1 Status LED OUT2 Type of fault Fault warning Corrective measures none F Supply voltage too low Check correct the supply voltage SC flashes flashes flashes F Excessive current at...

Страница 12: ...11 2 Further technical data Further technical data and scale drawing at www argo hytos com 12 Factory setting Factory setting User setting SP1 25 MEW rP1 23 MEW ou1 Hno ou2 I SP2 75 MEW rP2 73 MEW ASP...

Отзывы: