P44x/EN AP/E33
Application Notes
Page 80/220
MiCOM P441/P442 & P444
2.16
Broken conductor detection
The majority of faults on a power system occur between one phase and ground or two
phases and ground. These are known as shunt faults and arise from lightning discharges
and other overvoltages which initiate flashovers. Alternatively, they may arise from other
causes such as birds on overhead lines or mechanical damage to cables etc. Such faults
result in an appreciable increase in current and hence in the majority of applications are
easily detectable.
Another type of unbalanced fault which can occur on the system is the series or open circuit
fault. These can arise from broken conductors, maloperation of single phase switchgear, or
the operation of fuses. Series faults will not cause an increase in phase current on the
system and hence are not readily detectable by standard overcurrent relays. However, they
will produce an unbalance and a resultant level of negative phase sequence current, which
can be detected.
It is possible to apply a negative phase sequence overcurrent relay to detect the above
condition. However, on a lightly loaded line, the negative sequence current resulting from a
series fault condition may be very close to, or less than, the full load steady state unbalance
arising from CT errors, load unbalance etc. A negative sequence element therefore would
not operate at low load levels.
The relay incorporates an element which measures the ratio of negative to positive phase
sequence current (I
2
/I
1
). This will be affected to a lesser extent than the measurement of
negative sequence current alone, since the ratio is approximately constant with variations in
load current. Hence, a more sensitive setting may be achieved.
2.16.1 Setting
Guidelines
The sequence network connection diagram for an open circuit fault is detailed in Figure 1.
From this, it can be seen that when a conductor open circuit occurs, current from the positive
sequence network will be series injected into the negative and zero sequence networks
across the break.
In the case of a single point earthed power system, there will be little zero sequence current
flow and the ratio of I2/I1 that flows in the protected circuit will approach 100%. In the case of
a multiple earthed power system (assuming equal impedances in each sequence network),
the ratio I2/I1 will be 50%.
It is possible to calculate the ratio of I2/I1 that will occur for varying system impedances, by
referring to the following equations:-
I
1F
=
E
g
(Z
2
+ Z
0
)
Z
1
Z
2
+ Z
1
Z
0
+ Z
2
Z
0
I
2F
=
–E
g
Z
0
Z
1
Z
2
+ Z
1
Z
0
+ Z
2
Z
0
Where:
E
g
=
System
Voltage
Z
0
=
Zero
sequence
impedance
Z
1
=
Positive sequence impedance
Z
2
= Negative
sequence
impedance
Therefore:
I
2F
I
1F
=
Z
0
Z
0
+ Z
2
Содержание MiCOM P441
Страница 1: ...MiCOM P441 P442 P444 Numerical Distance Protection VC2 x Technical Guide P44x EN T E44...
Страница 2: ......
Страница 4: ...P44x EN T E44 Technical Guide Page 2 2 MiCOM P441 P442 P444 BLANK PAGE...
Страница 5: ...Pxxxx EN SS C11 SAFETY SECTION...
Страница 6: ......
Страница 8: ...Pxxxx EN SS C11 Page 2 10 Safety Section BLANK PAGE...
Страница 17: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 UPDATE DOCUMENTATION VERSION C2 X...
Страница 18: ......
Страница 22: ...P44x EN AD E44 Update Documentation Page 4 82 MiCOM P441 P442 P444 BLANK PAGE...
Страница 23: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 5 82 P44X EN IT E33 INTRODUCTION...
Страница 24: ......
Страница 33: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 15 82 P44X EN HW E33 RELAY DESCRIPTION...
Страница 34: ......
Страница 43: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 25 82 APPLICATION GUIDE P44X EN AP E33...
Страница 44: ......
Страница 96: ...P44x EN AD E44 Update Documentation Page 78 82 MiCOM P441 P442 P444 BLANK PAGE...
Страница 97: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 79 82 TECHNICAL DATA P44X EN TD E33...
Страница 98: ......
Страница 100: ...P44x EN AD E44 Update Documentation Page 82 82 MiCOM P441 P442 P444 BLANK PAGE...
Страница 101: ...Introduction P44x EN IT E33 MiCOM P441 P442 P444 INTRODUCTION...
Страница 102: ......
Страница 104: ...P44x EN IT E33 Introduction Page 2 24 MiCOM P441 P442 P444 BLANK PAGE...
Страница 127: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 RELAY DESCRIPTION...
Страница 128: ......
Страница 132: ...P44x EN HW E33 Relay Description Page 4 44 MiCOM P441 P442 P444 BLANK PAGE...
Страница 152: ...P44x EN HW E33 Relay Description Page 24 44 MiCOM P441 P442 P444 Example isolated AC fault...
Страница 153: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 Page 25 44...
Страница 173: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 APPLICATION NOTES...
Страница 174: ......
Страница 180: ...P44x EN AP E33 Application Notes Page 6 220 MiCOM P441 P442 P444 BLANK PAGE...
Страница 357: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 Page 183 220...
Страница 364: ...P44x EN AP E33 Application Notes Page 190 220 MiCOM P441 P442 P444 BLANK PAGE...
Страница 394: ...P44x EN AP E33 Application Notes Page 220 220 MiCOM P441 P442 P444 BLANK PAGE...
Страница 395: ...Technical Data P44x EN TD E33 MiCOM P441 P442 P444 TECHNICAL DATA...
Страница 396: ......
Страница 400: ...P44x EN TD E33 Technical Data Page 4 30 MiCOM P441 P442 P444 BLANK PAGE...
Страница 427: ...Installation P44x EN IN E33 MiCOM P441 P442 P444 INSTALLATION...
Страница 428: ......
Страница 430: ...P44x EN IN E33 Installation Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Страница 438: ...P44x EN IN E33 Installation Page 10 10 MiCOM P441 P442 P444 BLANK PAGE...
Страница 439: ...Commissioning P44x EN CM E33 MiCOM P441 P442 P444 COMMISSIONING...
Страница 440: ......
Страница 494: ...P44x EN CM E33 Commissioning Page 54 54 MiCOM P441 P442 P444 BLANK PAGE...
Страница 495: ...Commissioning Test Record Sheets P44x EN RS E33 MiCOM P441 P442 P444 COMMISSIONING TEST RECORD SHEETS...
Страница 496: ......
Страница 498: ...P44x EN RS E33 Commissioning Test Record Sheets Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Страница 507: ...Connection Diagrams P44x EN CO E33 MiCOM P441 P442 P444 CONNECTION DIAGRAMS...
Страница 508: ......
Страница 510: ...P44x EN CO E33 Connection Diagrams Page 2 12 MiCOM P441 P442 P444 BLANK PAGE...
Страница 520: ...P44x EN CO E33 Connection Diagrams Page 12 12 MiCOM P441 P442 P444 BLANK PAGE...
Страница 521: ...Courrier Data Base P44x EN GC E44 MiCOM P441 P442 P444 CONFIGURATION MAPPING...
Страница 610: ...Courier Data Base P44x EN GC E44 MiCOM P441 P442 P444 DEFAULT PROGRAMMABLE SCHEME LOGIC PSL...
Страница 615: ...Menu Content Tables P44x EN HI E44 MiCOM P441 P442 P444 MENU CONTENT TABLES...
Страница 616: ......
Страница 624: ......
Страница 626: ......
Страница 634: ...P44x EN VC E44 Hardware Software Version Page 8 8 MiCOM P441 P442 P444 BLANK PAGE...
Страница 635: ......