p18

note

 :  only for 

temperature inputs

 : 

From the menu rEAd, the performed scale shiftings can be visualised in 

the submenu InPut :

5.2.2 Visualisation of the direct measure

Press      and       to visualise the signal directly without processing: 

scale factor, square root, linearisation

− 

in mV, V or mA for process inputs,

− 

in mV for thermocouple inputs,

− 

in

 Ω

 for Pt100, Ni100 inputs,

− 

in 

 for resistance inputs,

− 

in percents for potentiometer inputs.

M

OFFSE.

000.3

offset

shifting

d.diSP

slope and 

offset

shifting

shifting of the dis-

play down scale

display down scale

shifting of the dis-

play full scale

Suppressing of the input shifting: 

(Case of a temperature input only)

The menu AdJuS. in the mode programming of a temperature input 

allows suppressing the entered shifting, or not.

no : 

the instrument will revert to the factory settings

Yes:

the instrument will take the programmed (offset and/or slope) 

adjustments into account.

display full scale

AdJ.Lo

F.diSP

500.2

AdJ.Hi

-000.2

-000.3

000.3

   5.2.3 Visualisation and setting of the alarm setpoints

M

Setting of the setpoints: 

There are 2 ways to adjust setpoints :

- either in mode programming entering the correct safety access code 

(see p15)

- or by pressing simultaneously on 

and  

 

 

 

 

The meter will then show the message SP.x or SPx.x alternating with 

the value of the corresponding setpoint.
The values of the various setpoints can be accessed with        and        .
These setpoints can then be modified (if access code < 6000

 (see p15)

by pressing
When the setpoint is adjusted press        to revert to the setpoints rea-

ding menu.      
Once all the setpoints are adjusted, simply press          and the meter 

will revert to mode measure, taking the new values into account.

If no key is pressed during 60 s. the meter will revert to the measure 

display without modification of the value of the setpoints.

M

Option 2 or 4 relays

5.2.4 Setting of the tare

 (except temperature inputs)

Press       and       to enforce the display for the signal currently present 

on the input as the display down scale

Note

 : The tare will not be memorised in case of power supply cut.

To suppress the tare, validate the menu              in the main menu

 p16

An exit from mode programming with saving of the configuration will 

reset the tare to zero.

d.dISP

CLr.tA

(accessible according to the programmed access code)

Содержание DIP 10

Страница 1: ...ax 04 72 31 31 31 Tel Intern 33 4 72 31 31 30 Fax Intern 33 4 72 31 31 31 ARDETEM TA IN 46 C 11 06 Any data in this documentation may be modified without prior notice ARDETEM Soucieu en Jarrest FRANCE...

Страница 2: ...12 4 6 3 Safeties p13 4 6 4 Display features p14 4 7 Reading of the configuration p14 4 8 Access code p15 4 9 Programming of a new access code p15 4 10 Functions of the the main menu p15 4 10 1 Displa...

Страница 3: ...V typical 60 V Max CJC efficiency 0 03 C C 0 5 C from 5 C to 55 C MR Measure range Cut off the display and the output remain at down scale for an input signal value of the cut off programmable from 0...

Страница 4: ...Voltage direct or reversed 0 10V Load impedance Lr 500k 2 setpoints per relay configurable on the whole MR Hysteresis programmable from 0 to 100 Time delay programmable from 0 to 25 sec 8A 250 VAC on...

Страница 5: ...transmitter VOUT GND VCC 5 6 7 Tc Pt100 3 wire Ni 100 3 wire 4 5 6 7 Potentiometer RESISTANCE AND POTENTIOMETER TEMPERATURE PROCESS Resistance 440 up to 2k 0 8k optional Strap 4 and 7 on terminal 0 4...

Страница 6: ...ation display Entering of a parameter First start by increasing or decreasing the 1st digit and the sign from 9 to 9 the 2nd from 0 to 9 the 3rd from 0 to 9 the 4th from 0 to 9 M M Alarms Led 1 Led 2...

Страница 7: ...is and or sensor rupture and access to disconnecting the sensor rupture option analog or relay output Access to the programming of the display p10 Access to the programming exit menu with p10 or witho...

Страница 8: ...d the analog output SPxx hystx do diS Fo diS If thermocouple if other than thermocouple CJC E CJ t CJC yES no AdJuS to tc diSPL tc S tc CA tc J tc r tc t tc E tc b tc n tc C tc C3 tc C5 tc L oF oC rES...

Страница 9: ...yES 88 88 1 1 setting in display points You can choose to assign the analog output to the input measure PArA InPut or to the displayed measure PArA diSPL Eg with PArA diSPL When the transmitter indic...

Страница 10: ...tus of the relay 1 in case of sensor rupture LO HI OFF status of the relay 2 in case of sensor rupture disconnection of the sensor rupt or yES no value of the output in case of sensor rupture 00 00 rE...

Страница 11: ...max as well as the alarm recordings 4 5 1 Current input Special linearisation For specific applications such as the measurement of volume the meter can memorise an unlinear curve programmable in X an...

Страница 12: ...A F in 20 mA nb 9 d disp 0 000 m3 F disp 0 785 m3 Programming from A01 to A09 and from B01 to B09 according to the table 0 2 4 6 8 10 12 14 16 18 20 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 20 18 16 14...

Страница 13: ...m as the led represents the alarm state OFF OFF OFF ON ON ON setpoints setpt setpt or SP X SP X HYSx HySt x LEdx On OFF SP1 X SP1 X HYSt x SP2 X SP2 X HYSt x SP2 X SP1 X SP2 X SP1 X led lit led lit le...

Страница 14: ...t supplied in case of sensor rupture Relay active coil supplied in case of sensor rupture Note the led is either still or lit according to its programming in the menu rELAY 4 6 3 Safeties Self diagnos...

Страница 15: ...ration indice of the digital filtering Programmable from 0 to 10 for use in case of unsteady input signal To obtain the maximum response time add 240 ms Note For the response time of the analog output...

Страница 16: ...XXXXX 1 2 3 4 5 P CodE OLd no Enter former code if code not valid old display during 2s and revert to the measure display New code registered and revert to the measure display if code correct old Ente...

Страница 17: ...orresponding led starts to blink To revert to the normal status led not blinking and relay in the correct state use menu CLEAr M CLEAr the recorded alarms are not deleted deleting of the recorded alar...

Страница 18: ...can increase or decrease the down or full display scale If you keep pressing during 3s on key or you can access a quick increasing or decreasing of the display value Press to validae the shifting The...

Страница 19: ...Setting of the setpoints There are 2 ways to adjust setpoints either in mode programming entering the correct safety access code see p15 or by pressing simultaneously on and The meter will then show...

Страница 20: ...UE Messages shown by the meter in mode programming and or in mode reading General access Access to the reading of the parameters Access to the programming of the input and output parameters Code for a...

Страница 21: ...l point in mode measure Place of the decimal point Choice of the processing function Linear Input down scale Input full scale Down and full display scale diSPL Point Funct LinEA d in F in F diSP d diS...

Страница 22: ...oints Sepoint and hysteresis in display points Operating mode of the relay x Mode setpoint Mode window Value of the setpoint in mode setpoint Value of the 1st setpoint in mode window Value of the 2nd...

Страница 23: ...ing of the instrument internal features Access to the submenu reading of the internal features Name of the instrument Type of the instrument Available options standard A analog output R relay output I...

Отзывы: