VMX Series Manual
page 12
rev 1.06
RS-485 Connection
HMI
Arcus Controller (RS-485)
COM1/COM2 (DB9)
Note on VMX-30 – HMI to Arcus Controller
VMX-30 only has one physical COM port.
RS-232 communication setup:
1)
Connect the necessary RS-232 signals
2)
The switch on the back of the VMX-30 must be moved to the “T” position for
RS-232 communication.
3)
Select COM1 in the VIEWX software when adding protocol and controllers.
Only use COM2 when using RS-485 communication.
1 RS422 R+
2 RS232 RX
3 RS232 TX
4RS485 D+/RS422 T+
5 GND
6 RS422 R-
7 RS232 RTS
8 RS232 CTS
9RS485 D-/RS422 T-
SH (shell)
RS-485 +
RS-485 -
GND