13
English
TECHNICAL DATA / ENERGY - SPM
(Models fitted with enthalpy heat exchangers)
Model
ENY-SPM-180 ENY-SPM-280 ENY-SPM-370 ENY-SPM-460
Length
mm
580
630
680
680
Width
mm
600
600
660
660
Height
mm
1041
1041
980
980
Diameter of Connections
-
DN125
DN160
DN160
DN180
Weight
kg
52
56
61
64
Maximum Flow Rate
m3/h
180
280
370
460
Available Static pressure
at maximum flow rate
Pa
100
100
100
100
Flow rate of reference
m3/h
130
200
260
320
Available Static pressure
at flow rate of reference
Pa
50
50
50
50
Minimum Flow Rate
m3/h
50
70
50
90
Maximum Available
Static Pressure
Pa
160
240
390
400
Thermal Efficiency
at flow rate of reference
EN 13141-7
%
88.6%
84.8%
82.7%
81.5%
Thermal hygromeric
at flow rate of reference
EN 13141-7
%
72.1%
65.6%
63.4%
58.4%
Filtering Efficiency
EN779 - ISO 16890
-
F7 supply - M5 exhaust
ePM1 70% - ePM10 50%
Fan Type
-
Centrifugal with EC brushless motor - Blades back - Curves at constant
speed
Maximum power output
(fans and controllers)
W
50
70
120
215
Maximum current output
(fans and controllers)
A
0.6
1.0
1.0
2.0
Electric power supply
-
Single phase -230 V – 50 Hz
Consumption in standby
-
<1W
Safety Property
-
Protection: IP21
EC Compliant
Models with integrated
modulating resistance
-
ENY-SPMEL-180
ENY-SPMER-180
ENY-SPMEL-280
ENY-SPMER-280
ENY-SPMEL-370
ENY-SPMER-370
ENY-SPMEL-460
ENY-SPMER-460
Preheating resistance
power
W
500
900
1250
1600
Maximum current output
with resistance
A
3
5
7
9.2
Содержание Sabiana Energy Smart Series
Страница 2: ......
Страница 22: ...22 English Installing controller on the wall 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56 ...