25
English
The connections can be swapped to allow for flexible
installation of the appliances for residential ventilation.
The difference in the connections regards the position
of the air connections, of the filters and of the conden-
sate drain and RH sensor.
Left side connection (Standard version)
A
C
B
D
A - Outdoor air
B - Supply air
C - Exhaust air
D - Extracted stale air
Right side connection (supplementary version)
A
C
B
D
A - Outdoor air
B - Supply air
C - Exhaust air
D - Extracted stale air
How to change connection
(For Appliances not equipped with internal modu-
lating electric resistance)
1
1. Unscrew the top cover.
2. Remove the top cover.
2
3. Position the DIP n°1 of the power board based on
the desired connection:
DIP 1 = OFF LH installation (default)
DIP 1 = ON RH installation
3
1
2
3
4
5
6
7
8
9
10
ON
DIP 1
The default appliance is set in the version with
left
side connections.
To change the machine to the RIGHT side version,
proceed as follows:
COMMISSIONING
PLEASE NOTE: Apply the labels, supplied with the
unit, based on the new configuration
Always disconnect power