ARAMA DCIPT12 Скачать руководство пользователя страница 8

- 7-

 

 

 

 

Operating  Voltage

 

Unit  Voltage

 

Voltage  Utilization  Range

 

Rating

 

Minimum

 

Maximum

 

230

/

208

 

197

 

253

 

 

WIRING

 

 

230~208V  units are equipped with LCDI  power cords and 
can open the electrical circuit to the unit. In the event the 
unit does not operate, check the reset button located on or 
near  the  head  of   the  power  cord  as  part  of  the  normal 
troubleshooting procedure. 

VOLTAGE MEASUREMENTS

 

Once  the  unit  is  properly  wired,  measure  the  unit  supply 
voltage.  Voltage  must  fall  within  the  voltage  utilization 
range given in 

Chart 3

 
 
 
 

 

HIGH VOLTAGE

 

WARNING

 

 

Chart 3 

-

Operating  Voltage

 

DISCONNECT  ALL  POWER  BEFORE  SERVICING  OR  INSTALLING 
THIS  UNIT.  MULTIPLE  POWER  SOURCES  BE  PRESENT,  FAILURE 
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY 
OR DEATH.

 

DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING OFF THE 
POWER  TO  THE  UNIT  FROM  THE  CIRCUIT  BREAKER  AND/OR 
REMOVING THE UNIT CORD SET PLUG FROM THE WALL OUTLET.

 

 

 
 

 

Tandem

 

230

/

208V  15Amp

 

 

Perpendicular

 

230

/

208V  20  Amp 

Large  tandem

 

230

/

208V  30Amp

 

Fig 8 Receptacles

/

Sub

-

bases

 

 

 

 

WARNING

 

TO AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL 
INJURY OR 

FIRE

,   USE ONLY COPPER CONDUCTORS.

 

 

 
 
 

WARNING

 

TO  AVOID  PROPERTY  DAMAGE,  PERSONAL  INJURY  OR 
DEATH  DUE  TO  ELECTRICAL  SHOCK,  DO  NOT  USE  AN 
EXTENSION CORD WITH THIS UNIT.

 

 

 

 

WARNING

 

TO  AVOID  THE  RISK  OF  PROPERTY  DAMAGE,  PERSONAL 
INJURY  OR  FIRE  DO  NOT  INSTALL  WITH  POWER  CORD 
STRETCHED  OR  UNDER  A  STRAIN  AS  THIS  MAY  CREATE 
LOOSE PLUG/RECEPTACLE CONNECTION.

 

WALL MOUNTED THERMOSTAT INTERFACE

 

 
 

R LS GH B Y W GL C

 

 

 
 
 

WARNING

 

TO  AVOID  THE  RISK  OF  PERSONAL  INJURY,  WIRING  TO  THE 
UNIT MUST BE PROPERLY POLARIZED AND GROUNDED.

 

 
 

 

WARNING

 

THIS  AIR  CONDITIONER  IS  NOT  MEANT  TO  PROVIDE 
UNATTENDED COOLING   OR LIFE SUPPORT  FOR  PERSONS 
OR ANIMALS WHO ARE UNABLE  REACT TO THE FAILURE OF 
THIS  PRODUCT.

 

THE  FAILURE  OF  AN  UNATTENDED  AIR  CONDITIONER  MAY 
RESULT IN EXTREME HEAT   IN   THE   CONDITIONED   SPACE

 

 

RED

-

24VAC 

Purple

-

LS control 

Green

-

High fan speed 

Blue

-

Reversing valve 

Yellow

-

Compressor 

White

-

Heater

 

Orange

-

Low fan speed

 

Black

-

Common ground

 

 

 

 
 
 

 
 

R LS GH B Y W GL C

 

 

 

 
 
 
 
 

Thermostat

 

CAUSING  OVERHEATING  OR     DEATH     OF  PERSONS  OR 
ANIMALS.

 

Fig  9  wall  mounted  thermostat wiring

 

 

NOTE: See the “Remote  Thermostat  Change"instructions before 
use the thermostat.

 

Содержание DCIPT12

Страница 1: ...s Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of specific good sa...

Страница 2: ...n death the socket or terminal blocks for p o w e r s u p p l y t o t h e a i r conditioner include 277V and 115V and 208 230V series and the units that have LCDI power cord must connect a Ground Fault Circuit Interrupter 4 D u r i n g i n s t a l l a t i o n t h e w i r e connection must strictly follow the rule which is zero line and fire line of unit should be connected to the zero line and fir...

Страница 3: ...which operational mode is active FAN ON OFF System safety protections To ensure the system running safely electric control has the following protections for problem solving please refer to d i a g n o s t i c c o d e s s o l u t i o n s a n d troubleshooting sections A Outdoor unit overload protection in COOLING mode When condenser coil temperature exceeds the presetting point compressor decreases...

Страница 4: ...icated All units have two fan motors for quiet operation and maximum operating efficiency Motors are permanently lubricated to reduce maintenance and totally enclosed to keep dirt and water out of the motor windings Indoor Fan Speed Selections LOW HIGH Unit may be operated in low fan speed or high fan speed Some speed may not be present based on unit capacities LS Control front desk control The un...

Страница 5: ...ule Indoor Fan Electric heater Front and discharge grille Outdoor coil Inverter compressor Electronic control module assembly Power cord coverplate not show Control box Indoor coil WALL SLEEVE ASSEMBLY OPTIONAL ACCESSORY Two kinds of wall sleeve are optional for customers one is reassemble wall sleeve and the other one is welding integrated wall sleeve Removable Wall Sleeve The removable wall slee...

Страница 6: ...ficient space margins around the unit to facilitate maintenance and repairs refer to Figs 3 and 4 Chart 2 SUB FLOOR Fig 5 Note Do not remove the stiffener support from inside the wall case until the chassis is to be installed NOTE NO 1 means using field supplied sleeve angles 16 18 24 NO 2 means not using field supplied sleeve angles 1 2 Fig 3 In order for condensate water to drain properly inside...

Страница 7: ... set and require no adjustment 2 Check the indoor and outdoor grilles for obstructions to air flow The unit must be located where curtains furniture trees or other objects do not block the air flow to and from the unit If air is obstructed and or deflected back into the unit the air conditioner compressor may cycle on and off rapidly This could damage the compressor or possibly void the warranty A...

Страница 8: ...Receptacles Sub bases WARNING TO AVOID THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE USE ONLY COPPER CONDUCTORS WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT USE AN EXTENSION CORD WITH THIS UNIT WARNING TO AVOID THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE DO NOT INSTALL WITH POWER CORD STRETCHED OR UNDER A STRAIN AS THIS MAY CREATE LOOSE PLU...

Страница 9: ...mounted control panel Operation mode indicator Fan speed indicator Present time indicator TEMP indicator Indicate set temperature Keyboard locked indicator Timer time indicator TEMP setting button This button is used to sent the room temperature Pressing of or button the temperature setting is increased or decreased FAN SPEED button Press this button to select the high low autospeed of air deliver...

Страница 10: ...nd then close the back cover NOTE For some type this function may be not exist SENIOR OPERATION Under OFF mode hold COOL and FAN SPEED two keys at the same time continuously for 5 seconds This time display d0 indicates that system has entered the senior operation status COOL key is used to switch parameter code and parameter value or keys are used to switch parameter code or set parameter value ON...

Страница 11: ...pped If this switch is put to OFF position it will be no freeze protection 6 Electric memory Default setting is ON Fig 13 Shipping Screw Location If the unit is cut out of power during the operation when it is powered up again all last settings will be remembered and the operation will follow the last mode Manual turn on the unit operation mode will be the last settings If this switch is put to OF...

Страница 12: ...ONALINJURYOR DEATH 15 Discharge Air 55 Discharge Air M O N T H LY M AI N T E N AN C E AN D CLEANING IntakeAir Filters To properly maintain the operational performance of your PTAC unit it is extremely important that the inlet air filters be cleaned once per month or more often if operated in dusty or dirty locations or conditions The intake air filters are constructed of durable polypropylene The ...

Страница 13: ...ction schedule for the unit Take the unit out of the sleeve and thoroughly clean and rinse Be sure to include in the yearly cleaning the evaporator coil and condenser coil basepan and drain passages Scheduled maintenance can be accomplished by either qualified local maintenance staff or by an authorized servicer They must follow the instructions described in this manual Adverse Operating Condition...

Страница 14: ...er objects for proper operation Restricted discharge or intake air will reduce the unit s operational performance In severe airflow restrictions damage can occur to unit components such as the compressor electric heater or fan motor NORMAL OPERATING SOUNDS AND CONDITIONS Water trickling sounds Water is picked up and distributed over the coil This improves the efficiency and helps with water remova...

Страница 15: ... sensor is broken replace it E9 Compressor discharge temperature fault Check the sensor s plug is firmly connected If the sensor is broken replace it EC DC compressor starting failure or compressor driving fault Check the DIPswitches on the main board 3 position in red color is correct it must matches the wiring diagram Make sure the compressor power wires is firmly connected EH Indoor EEPROM faul...

Страница 16: ...minutes on starting the compressor after a power outage or restarting after it has been turned off to prevent tripping of the compressor overload Make sure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher temperature setting Remove and clean filters Allow sufficient amount of time for unit to heat or cool the room Start heating or cooling ea...

Отзывы: