ARAMA DCIPT12 Скачать руководство пользователя страница 4

- 3-

 

 

 

 

J) Compressor starting fault

 

If  compressor  starting  fails,  3  minutes  later,  it  will  try  to 
start again. It will not display error code at the first 3 times 
fault. If the 4th time fail again, it will not start any more and 
display the error code. 

K) DC-BUS over voltage/under voltage protection

 

Once monitors the DC-BUS is over or under voltage, unit 
stops and display error code. 

L) EEPROM fault

 

When  the  unit  is  powered  on,  if  system  monitors  the 
EEPROM  fault,  displays  error  code  and  will  not  operate 
any more. 

 

•    Intelligent  control

-CPU  will  adjust  the  compressor 

operating  frequency  according  to  the  energy  demand, 
making  the  room  temperature  more  stable  and  more 
comfortable and more energy saving. 

•  Two-speed  outdoor  fan  HIGH/LOW

-When  outdoor 

ambient   temperature   becomes   lower   (for   example, 
during the night), outdoor fan will operating in low speed, 
so to lower the noise and also more energy saving. 

•  

Standard  Physical  Dimensions

-

The  series  PTAC  is 

with the same dimensions   42" wide x 16" high x 13-3/4" 
deep 

Replacement of older units is made easy. 

• 

Weather-Protected  Electrical  Components

-

Vital 

electrical components are protected from the weather by 
locating them on the indoor side of the weather barrier. 

• 

Highly  Featured  Microprocessor  Controls

Microprocessor  controls  are  programmed  to  interface 
with  the  temperature  sensors  to  maximize  comfort 
conditions  for  the  room  occupant  and  provide 
outstanding features. 

Thermistors  are  used  to  sense  small  changes  in 
temperature to give excellent room control and allow the 
microprocessor  to  monitor  and  react  to  changing 
conditions. 

•  Automatic Emergency Heat  on  Heat  Pump  Units

Automatically  uses  electric  resistance  heat  if  the  heat 
pump fails 

•  Fan Motors   Permanently Lubricated

-

All units have 

two  fan  motors  for  quiet  operation  and  maximum 
operating efficiency. 

M o t o r s   a r e   p e r m a n e n t l y   l u b r i c a t e d   t o   r e d u c e 
maintenance  and totally  enclosed  to  keep  dirt  and  water 
out of the motor windings. 

•  Indoor Fan Speed Selections  LOW /HIGH

-

Unit may 

be  operated  in  low  fan  speed  or  high  fan  speed.   Some 
speed     may     not     be     present     based     on     unit 
capacities

•   

LS   Control

(

front

-

desk   control

)-

The   unit   can   be 

turned  ON

/

OFF  by  front

-

desk  control  switch

.

The  control 

wire

,

colored  purple

,

locates  in  the  wall  mounted 

thermostat interface

(

refer to Fig11 on page 7

).

 

 

 

WALL MOUNTED  THERMOSTAT  INTERFACE

 

 

 

R LS GH B Y W GL C

 

 

 

T

he control logic as belw

1

.

Turn  ON  unit

:

short  circuit  R  and  LS  then  release  for 

one time within 5 seconds

2

.

Turn  OFF  unit

:

short  circuit  R  and  LS  then  release  for 

twice within 5 seconds

3

.

Force  unit  shut  down  for  one  time

:

connect  LS  to  R  for 

over 5 seconds

NOTE

After  force  shut  down

you  can  turn  the  unit  ON 

again    by    hand

-

held   remote    controller   or    the   control 

panel

 

 

 

WARNING

 

HIGH VOLTAGE

 

D I S C O N N E C T   A L L   P O W E R   B E F O R E   S E R V I C I N G   O R

 

INSTALLING  THIS  UNIT.  MULTIPLE  POWER  SOURCES  MAY 
BE  PRESENT,  FAILURE  TO  DO  SO  MAY  CAUSE  PROPERTY 
DAMAGE, PERSONAL INJURY OR DEATH.

 

 

UNIT ACCESSORIES

 

 

This unit is designed for through-the-wall installation in 
new  or  existing  buildings.  To  complete  the  installation 
of  this  PTAC,  an  insulated  wall  sleeve  and  an  outdoor 
grille  (either  the  stamped  aluminum  grille,  or  the 
architectural grille ) are required. 

The  chassis  and  the  cabinet  front  are  shipped  in  one 
carton.  Optional  accessories  to  complete  a  particular 
installation are the following: 

 

OPTIONAL ACCESSORIES

 

 

Wall Sleeve Kit 
Key Lock Kit 
Drain Kit 
Filter Kit 
Wire Harness Kit 
Architectural Grille Kit 
Stamped  Louver  Kit 
LCDI Power Cord 
Wireless IR Thermostat 
Electric And  Non  Electric  Sub  Base  Kit 
IR REMOTE CONTROLLER 

 

 

NOTE: 

Consult  sales  literature  for  the  appropriate 

voltage and amperage selections, if applicable. 

Содержание DCIPT12

Страница 1: ...s Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of specific good sa...

Страница 2: ...n death the socket or terminal blocks for p o w e r s u p p l y t o t h e a i r conditioner include 277V and 115V and 208 230V series and the units that have LCDI power cord must connect a Ground Fault Circuit Interrupter 4 D u r i n g i n s t a l l a t i o n t h e w i r e connection must strictly follow the rule which is zero line and fire line of unit should be connected to the zero line and fir...

Страница 3: ...which operational mode is active FAN ON OFF System safety protections To ensure the system running safely electric control has the following protections for problem solving please refer to d i a g n o s t i c c o d e s s o l u t i o n s a n d troubleshooting sections A Outdoor unit overload protection in COOLING mode When condenser coil temperature exceeds the presetting point compressor decreases...

Страница 4: ...icated All units have two fan motors for quiet operation and maximum operating efficiency Motors are permanently lubricated to reduce maintenance and totally enclosed to keep dirt and water out of the motor windings Indoor Fan Speed Selections LOW HIGH Unit may be operated in low fan speed or high fan speed Some speed may not be present based on unit capacities LS Control front desk control The un...

Страница 5: ...ule Indoor Fan Electric heater Front and discharge grille Outdoor coil Inverter compressor Electronic control module assembly Power cord coverplate not show Control box Indoor coil WALL SLEEVE ASSEMBLY OPTIONAL ACCESSORY Two kinds of wall sleeve are optional for customers one is reassemble wall sleeve and the other one is welding integrated wall sleeve Removable Wall Sleeve The removable wall slee...

Страница 6: ...ficient space margins around the unit to facilitate maintenance and repairs refer to Figs 3 and 4 Chart 2 SUB FLOOR Fig 5 Note Do not remove the stiffener support from inside the wall case until the chassis is to be installed NOTE NO 1 means using field supplied sleeve angles 16 18 24 NO 2 means not using field supplied sleeve angles 1 2 Fig 3 In order for condensate water to drain properly inside...

Страница 7: ... set and require no adjustment 2 Check the indoor and outdoor grilles for obstructions to air flow The unit must be located where curtains furniture trees or other objects do not block the air flow to and from the unit If air is obstructed and or deflected back into the unit the air conditioner compressor may cycle on and off rapidly This could damage the compressor or possibly void the warranty A...

Страница 8: ...Receptacles Sub bases WARNING TO AVOID THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE USE ONLY COPPER CONDUCTORS WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT USE AN EXTENSION CORD WITH THIS UNIT WARNING TO AVOID THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE DO NOT INSTALL WITH POWER CORD STRETCHED OR UNDER A STRAIN AS THIS MAY CREATE LOOSE PLU...

Страница 9: ...mounted control panel Operation mode indicator Fan speed indicator Present time indicator TEMP indicator Indicate set temperature Keyboard locked indicator Timer time indicator TEMP setting button This button is used to sent the room temperature Pressing of or button the temperature setting is increased or decreased FAN SPEED button Press this button to select the high low autospeed of air deliver...

Страница 10: ...nd then close the back cover NOTE For some type this function may be not exist SENIOR OPERATION Under OFF mode hold COOL and FAN SPEED two keys at the same time continuously for 5 seconds This time display d0 indicates that system has entered the senior operation status COOL key is used to switch parameter code and parameter value or keys are used to switch parameter code or set parameter value ON...

Страница 11: ...pped If this switch is put to OFF position it will be no freeze protection 6 Electric memory Default setting is ON Fig 13 Shipping Screw Location If the unit is cut out of power during the operation when it is powered up again all last settings will be remembered and the operation will follow the last mode Manual turn on the unit operation mode will be the last settings If this switch is put to OF...

Страница 12: ...ONALINJURYOR DEATH 15 Discharge Air 55 Discharge Air M O N T H LY M AI N T E N AN C E AN D CLEANING IntakeAir Filters To properly maintain the operational performance of your PTAC unit it is extremely important that the inlet air filters be cleaned once per month or more often if operated in dusty or dirty locations or conditions The intake air filters are constructed of durable polypropylene The ...

Страница 13: ...ction schedule for the unit Take the unit out of the sleeve and thoroughly clean and rinse Be sure to include in the yearly cleaning the evaporator coil and condenser coil basepan and drain passages Scheduled maintenance can be accomplished by either qualified local maintenance staff or by an authorized servicer They must follow the instructions described in this manual Adverse Operating Condition...

Страница 14: ...er objects for proper operation Restricted discharge or intake air will reduce the unit s operational performance In severe airflow restrictions damage can occur to unit components such as the compressor electric heater or fan motor NORMAL OPERATING SOUNDS AND CONDITIONS Water trickling sounds Water is picked up and distributed over the coil This improves the efficiency and helps with water remova...

Страница 15: ... sensor is broken replace it E9 Compressor discharge temperature fault Check the sensor s plug is firmly connected If the sensor is broken replace it EC DC compressor starting failure or compressor driving fault Check the DIPswitches on the main board 3 position in red color is correct it must matches the wiring diagram Make sure the compressor power wires is firmly connected EH Indoor EEPROM faul...

Страница 16: ...minutes on starting the compressor after a power outage or restarting after it has been turned off to prevent tripping of the compressor overload Make sure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher temperature setting Remove and clean filters Allow sufficient amount of time for unit to heat or cool the room Start heating or cooling ea...

Отзывы: