ARAMA DCIPT12 Скачать руководство пользователя страница 6

- 5-

 

 

 

 

 

minium finished opening 

dimensions

 

 

sleeve dimensions

 

Height

 

width

 

height

 

width

 

depth

 

NO

.

1

 

16

-

1

/

4

"

 

42

-

1

/

2

"

 

 

16

"

 

 

42

"

 

13

-

3

/

4

"

 

NO

.

2

 

16

-

1

/

4

"

 

42

-

1

/

4

"

 

 

Dimensions

 

Recommended installation clearance

 

 

D1

 

Projection of case into room

-

1

/

2

"

minimum up to1

-

3

/

4

"

maximum 

without use of electrical sub

-

base

.

 

Note

2

-

3

/

8

minmum when sub

-

base is used

.

 

 

D2

 

Height above finished   floor or top of carpet

-

1

/

2

"

minimum

,

 

2

recommended without sub

-

base

-

3

minimum with sub

-

base

.

 

 

SLEEVE INSTALLATION

 

Wall sleeve location

 

When  making  the  wall  opening,   please  observe  the 
following requirement:

 

A) The air inlet and outlet should be unblocked and the air

 

 

MAIN STUD

 

JACK STUDS

 

 

 
 
 
 

16

-

1

/

4

"

MIN

 

 

HEADER

-

4

4

"

OR

 

2

-

2

4

"

ON EDGE

 

can be delivered to every corner of the room

 

B) Install the unit in places that are away from heat source 
or sources of flammable gases.

 

C) Do not install the unit in places that are subject to strong 
dust

 

 

 

 
 
 

 
 

JACK  STUD

 

 
 
 
 

 

 

CRIPPLE

 

ADJUSTABLE FRAMING TO SECURE 

THIS DIMENSION

 

42

-

1

/

4

"

MIN

 

 

 
 
 
 
 

FINISHED  FLOOR

 

D)  Do not install the unit in places where the operational

 

noise and exhausted air might trouble your neighbour.

 

E)  There  should  be  sufficient  space  margins  around  the 
unit  to  facilitate  maintenance  and  repairs(refer  to  Figs  3 
and 4)

 

 
 

 

Chart 2

 

SUB

-

FLOOR

 

 

Fig   5

 

Note

:

Do not remove the stiffener

 

support from inside the wall case 

until the chassis is to be installed

.

 

 

 
 

NOTE

NO

.

1 means using field supplied sleeve angles

 

(

16

"/

18

"/

24

")

 

NO

.

2 means not using field supplied sleeve angles

 

 

1

 

 

 

2

 

 

Fig  3

 

 

In order for condensate water to drain properly inside the 
unit, the sleeve must be installed properly: 

• 

Level from right to left. 

• 

A slight downward pitch from the indoor side to the 

out-door side as shown below

(

Fig 6

)

• 

Fasten the wall sleeve

(

Fig 7

).

 

 

 

 
 

Fig  4

 

Inside 

Outside 

Level

 

 

Chart 1

 

 

Wall

 

Sleeve

 

1

/

4  Bubble 

Tilt  to 

Outside

 

 

 
 

 

 

Preparation of the wall

 

The  sleeve  should  be  installed  during  construction  and 
lintels should be used to support the block above the wall 
sleeve.  The  sleeve  can  not  support  the  load  of  bricks/ 
blocks.

 

For  existing  construction,  wall  opening  must  be  created, 
the proper dimensions are necessary to avoid use of fillers

 

 

 
 

Fig   6

 

Outside

 

Wall

 

 

Proper Sleeve Tilt

 

or additional framing .The sleeve is modular in height and 
width(refer to Fig 5& Chart 2).

 

Height: Fits 2 courses 
concrete block Fits 6 courses 
standard brick Fits 5 courses 
jumbo brick Width:

 

 

WOOD 

SCREW

 

 

MOLLY

 

OR  TOGGLE 

BOLT

 

 

EXPANSION 

ANCHOR 

BOLT

 

Fit approximately 3 stud spaces.

 

Fig   7

 

Содержание DCIPT12

Страница 1: ...s Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of specific good sa...

Страница 2: ...n death the socket or terminal blocks for p o w e r s u p p l y t o t h e a i r conditioner include 277V and 115V and 208 230V series and the units that have LCDI power cord must connect a Ground Fault Circuit Interrupter 4 D u r i n g i n s t a l l a t i o n t h e w i r e connection must strictly follow the rule which is zero line and fire line of unit should be connected to the zero line and fir...

Страница 3: ...which operational mode is active FAN ON OFF System safety protections To ensure the system running safely electric control has the following protections for problem solving please refer to d i a g n o s t i c c o d e s s o l u t i o n s a n d troubleshooting sections A Outdoor unit overload protection in COOLING mode When condenser coil temperature exceeds the presetting point compressor decreases...

Страница 4: ...icated All units have two fan motors for quiet operation and maximum operating efficiency Motors are permanently lubricated to reduce maintenance and totally enclosed to keep dirt and water out of the motor windings Indoor Fan Speed Selections LOW HIGH Unit may be operated in low fan speed or high fan speed Some speed may not be present based on unit capacities LS Control front desk control The un...

Страница 5: ...ule Indoor Fan Electric heater Front and discharge grille Outdoor coil Inverter compressor Electronic control module assembly Power cord coverplate not show Control box Indoor coil WALL SLEEVE ASSEMBLY OPTIONAL ACCESSORY Two kinds of wall sleeve are optional for customers one is reassemble wall sleeve and the other one is welding integrated wall sleeve Removable Wall Sleeve The removable wall slee...

Страница 6: ...ficient space margins around the unit to facilitate maintenance and repairs refer to Figs 3 and 4 Chart 2 SUB FLOOR Fig 5 Note Do not remove the stiffener support from inside the wall case until the chassis is to be installed NOTE NO 1 means using field supplied sleeve angles 16 18 24 NO 2 means not using field supplied sleeve angles 1 2 Fig 3 In order for condensate water to drain properly inside...

Страница 7: ... set and require no adjustment 2 Check the indoor and outdoor grilles for obstructions to air flow The unit must be located where curtains furniture trees or other objects do not block the air flow to and from the unit If air is obstructed and or deflected back into the unit the air conditioner compressor may cycle on and off rapidly This could damage the compressor or possibly void the warranty A...

Страница 8: ...Receptacles Sub bases WARNING TO AVOID THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE USE ONLY COPPER CONDUCTORS WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT USE AN EXTENSION CORD WITH THIS UNIT WARNING TO AVOID THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE DO NOT INSTALL WITH POWER CORD STRETCHED OR UNDER A STRAIN AS THIS MAY CREATE LOOSE PLU...

Страница 9: ...mounted control panel Operation mode indicator Fan speed indicator Present time indicator TEMP indicator Indicate set temperature Keyboard locked indicator Timer time indicator TEMP setting button This button is used to sent the room temperature Pressing of or button the temperature setting is increased or decreased FAN SPEED button Press this button to select the high low autospeed of air deliver...

Страница 10: ...nd then close the back cover NOTE For some type this function may be not exist SENIOR OPERATION Under OFF mode hold COOL and FAN SPEED two keys at the same time continuously for 5 seconds This time display d0 indicates that system has entered the senior operation status COOL key is used to switch parameter code and parameter value or keys are used to switch parameter code or set parameter value ON...

Страница 11: ...pped If this switch is put to OFF position it will be no freeze protection 6 Electric memory Default setting is ON Fig 13 Shipping Screw Location If the unit is cut out of power during the operation when it is powered up again all last settings will be remembered and the operation will follow the last mode Manual turn on the unit operation mode will be the last settings If this switch is put to OF...

Страница 12: ...ONALINJURYOR DEATH 15 Discharge Air 55 Discharge Air M O N T H LY M AI N T E N AN C E AN D CLEANING IntakeAir Filters To properly maintain the operational performance of your PTAC unit it is extremely important that the inlet air filters be cleaned once per month or more often if operated in dusty or dirty locations or conditions The intake air filters are constructed of durable polypropylene The ...

Страница 13: ...ction schedule for the unit Take the unit out of the sleeve and thoroughly clean and rinse Be sure to include in the yearly cleaning the evaporator coil and condenser coil basepan and drain passages Scheduled maintenance can be accomplished by either qualified local maintenance staff or by an authorized servicer They must follow the instructions described in this manual Adverse Operating Condition...

Страница 14: ...er objects for proper operation Restricted discharge or intake air will reduce the unit s operational performance In severe airflow restrictions damage can occur to unit components such as the compressor electric heater or fan motor NORMAL OPERATING SOUNDS AND CONDITIONS Water trickling sounds Water is picked up and distributed over the coil This improves the efficiency and helps with water remova...

Страница 15: ... sensor is broken replace it E9 Compressor discharge temperature fault Check the sensor s plug is firmly connected If the sensor is broken replace it EC DC compressor starting failure or compressor driving fault Check the DIPswitches on the main board 3 position in red color is correct it must matches the wiring diagram Make sure the compressor power wires is firmly connected EH Indoor EEPROM faul...

Страница 16: ...minutes on starting the compressor after a power outage or restarting after it has been turned off to prevent tripping of the compressor overload Make sure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher temperature setting Remove and clean filters Allow sufficient amount of time for unit to heat or cool the room Start heating or cooling ea...

Отзывы: