AT-G-DETECT

 

Gas Sensing System

LEAK DETECTION SOLUTIONS

7

J. AT-G DETECT 1 OR 2 CHANNEL UNIT 

K. AT-G-DETECT 4 OR 6 CHANNEL UNIT 

L. ADDITIONAL RECOMMENDATIONS 

False Alarms

If false alarms are being triggered by 
background gases, paint fumes, etc, or 
extreme humidity or temperature conditions, 
you may adjust the settings to compensate.

One Level Systems

You should reduce the SSV level in 0.5V 
increments until the condition clears.

Two Level Systems

You should adjust the relevant alarm 
threshold upwards in 0.2Volt increments 
until the condition clears.

Unit 30, Lawson Hunt Industrial Park, 

Broadbridge Heath, Horsham, West Sussex, 

RH12 3JR
+44 (0) 1403 216100
[email protected]
www.aquilar.co.uk

Содержание AquiTron AT-G-DETECT

Страница 1: ...AT G DETECT Refrigerant Gas Sensing System Check Calibration Procedure AquiTron CA L I B R AT I O N P R O C E D U R E...

Страница 2: ...ective is to establish if the sensor is reacting to the gas and all the sensor outputs are working correctly A quantified bump test is one where gas of a know concentration is used CALIBRATION This co...

Страница 3: ...r does not go into alarm carry out a gas calibration If the factory set point information is not on the calibration label as with older units check the serial number of your gas detector on the rating...

Страница 4: ...OULES 1 Make sure that both the ampoules and the calibration beaker are clean and dry 2 Unscrew the beaker hold screw and place the ampoule so that it sits in the base of the beaker 3 Tighten on the s...

Страница 5: ...o the controller to monitor sensor response Expose the sensor to gas from the cylinder You can place the entire sensor into a plastic bag or use a plastic hose hood to direct gas to the sensor head G...

Страница 6: ...3 minute alarm delay on a one level system by moving the jumper link at JP1 to the o position Two adjustments are required and they are all performed on the controller unit A Sensor Standby Voltage S...

Страница 7: ...used drift B Alarm Threshold Voltage ATV Low Treshhold Connect voltmeter between TP5 0V TP2 Ve set the voltage asshown on the calibration label by adjusting pot P8 High Threshold Connect voltmeter bet...

Страница 8: ...r extreme humidity or temperature conditions you may adjust the settings to compensate One Level Systems You should reduce the SSV level in 0 5V increments until the condition clears Two Level Systems...

Страница 9: ...libration label You can monitor this as follows 1 level systems Connect a Voltmeter and monitor voltage between Pins 4 Ve 2 Ve of the sensor terminal connector block for each channel in turn CN1 CN2 E...